Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 68
5.5 Time Control Operations
Time schedule groups are groups 92-95, with each group being associated with a different timing
schedule. By placing an output point in output group 92 and setting the associated schedule, the
output point will turn on and off at the times recorded in output schedule 1. Output groups 93-95
provide timing schedules #2, #3, and #4.
To program an output point for use on a Timing Schedule, follow these instructions:
1. Install the ZZRM relay, or supervised output control moduleor I/O relay and connect (See Sec-
tion 2 for connection).
2.
Select PROG from the menu (enter access privilege code if necessary).
3.
Select 6. Points from the main programming menu.
4.
Select 5. Auto-Program. Wait while the panel loads the “new” device information.
5.
Select 1. Point, then enter the loop. Press ENTER, enter the device address, then
ENTER again.
6.
Select 2. Edit.
7.
Select 3 Groups.
8.
Enter Group 92, 93, 94, or 95 (Note: If an output is in one of the on/off schedule groups, it can
be in any number of other groups).
9.
Make sure the output schedule has been programmed.
Review all programming selections to insure programming accuracy.