Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 92
Appendix E: Classic 2000 Programming Menus
Menu Description
Default Setting
Access
Level
Required
Main Screen
0
Reset (resets the panel)
Active Event Screen
0
Reset (resets the panel)
Silence (silences any active events)
Program
0
1. Clock
Default = 00:00:00
1. Time
Default = 01/01/1998
2. Date
Default = 12-Hour Mode
3. Time Mode
2. System
2
1. Options
1. LatchTroubles
Default = No (Non-Latching)
2. TroubleRemind
Default = No (trouble reminder disabled)
3. WaterflowSil
Default = No (waterflow not silenceable)
4. Printer
Default = Disabled
5. FloorConfig
Default = 1A/1B
2. Timing
1. AC Low Delay
Default = 0h
2. Auto Silence
Default = 0m (i.e. disabled)
3. Silence Inhibit Time
Default = 0s (i.e. disabled)
4. Alarm Verify
Default = 30s
5. Holidays
Default = 00/00
6. Schedules
1. Day/Night Sch #1
1. Day Start:
Default = 00:00
2. Day End:
Default = 00:00
3. Day Sens:
Default = Low
4. Night Sens:
Default = High
5. Days:
MTWTF
2. Day/Night Sch #2
…same as #1…
3. Day/Night Sch #3
…same as #1…
4. Day/Night Sch #4
…same as #1…