ETS PARAMETERIZATION
To begin with the parameterization process of the IRSC controller it is necessary, once the
ETS program has been opened, to import the data base of the product (
IRSC-Zone
application
program).
Next, the device should be added to the project where desired. And then, one right-click on the
device will permit selecting "Edit parameters", in order to start the configuration.
In the following sections a detailed explanation can be found about each of the different
functionalities of IRSC-Zone in ETS.
2.2. DEFAULT CONFIGURATION
This section shows the default configuration the device parameterization starts from.
Figure 3.1. IRSC-Zone. Default topology
The following communication objects appear: "A/C Unit - ON/OFF Status", "A/C Unit - Setpoint
Status" and "A/C Unit - Fan Status", all of them associated to the sending of the basic statuses of
the A/C unit (ON/OFF, setpoint and fan)
Seven more objects, with different lengths, are shown, referred in this case to different
functionalities that may be controlled for Zone 1 (Zone 1 is the only zone enabled by default). These
are:
Zone X
– ON/OFF
: permits turning ON or OFF each of the enabled zones independently.
Being ON implies the normal function of the zone, i.e., the automatic control of its airing grille
and the inclusion of its setpoint temperature into the calculation process of the general
setpoint temperature sent to the air conditioning machine. On the other hand, when a zone is