ZENN
iO
AVANCE
Y
TECNOLOGÍA
www.zennio.com
39
Dimming Step
Necessary pulsations for a
complete regulation (0 – 100%)
1. 3.1%
32
0. 1.5%
64
SENDING A SCENE
This function results on sending a (1 byte) Scene Control Object to the
BUS; a scene on the BUS may be managed with the input through this
Object.
RESPONSE
Æ
Choose whether the scene will be “Run” or “Saved”.
SCENE
Æ
This parameter identifies the scene to Run/Save with the
corresponding Input.
2.3.1.2.
LONG PRESS
Configuration options are exactly the same as in the previous case “Short
Press”.
2.3.1.3.
THRESHOLD TIME
This parameter defines the time limit where a short press turns into a long press.
If a press on the screen ends before the long press time, then it is a short press.
This value must be set with precision to tenths of a second (e.g. to get “0.5”
seconds, set “5”)
2.3.1.4.
RESPONSE DELAY
This parameter sets the time to wait for the object to be sent to the BUS since
the action on the input took place. This value must be set with precision to
tenths of a second (e.g. to get “1” second, set “10”).
Note: To get an immediate sending (no delay), set the value “0” in this field.
2.3.1.5.
BLOCK
Selecting “Yes” on the pull down menu, the corresponding “Communication
Object” will disable the input.
¾
When receiving a “1” through this object, the InZennio Z38i
will ignore any pulsation on the input.