ZENN
iO
AVANCE
Y
TECNOLOGÍA
www.zennio.com
15
TYPE
Æ
Select the control type to use:
¾
On/Off:
This is the most basic control type; Turn On/Off;
pretends to simulate a common switch action.
¾
On/Off + Simple Regulation (4 bits):
Users can simulate a
common switch action,
turn On/Off
(short press on the
buttons), or a
discreet regulation
(long press on the buttons),
where depending on the
“dimming step”
set, keeping the
button pressed will reduce or increase the brightness on the
controlled lamps.
•
Dimming Step:
Six different regulation levels are
available for this duty. A long press on the display
buttons will reduce or increase the brightness level step
by step the percentage set in this parameter; once the
desired level is reached, stop pressing the button on the
display to keep the desired value.
Dimming Step
Necessary button presses for a
complete regulation (0 – 100%)
6. 100%
1
5. 50%
2
4. 25%
4
3. 12.5%
8
2. 6.25%
16
1. 3.1%
32
0. 1.5%
64
•
Indicator:
This will inform users about the brightness
percentage applied at any time.
Note: In this case, for this indicator to be
functional, it is necessary to use a KNX
dimmer to give back the brightness applied to
the load.
¾
Precise Dimming (1 byte):
This is the most accurate control
method, as any short press on the display buttons will increase
or reduce (1%) the brightness level.
A long press on any of the two buttons will increase or reduce
gradually 10 % the brightness level.