SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
81
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
ALL DIMENSIONS - INCHES (MM)
YVAA
A
B
C
D
E-NOZZLE
SIZE
WATER
VOLUME
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER
FLOW RATE
GPM (L/S)
FRAME
COND.
39
8
16.3
(414)
30.3
(770)
252.5
(6414)
83.5
(2121)
8
147
(556)
370 (23)
1440 (91)
41
3
15.5
(394)
29.5
(749)
164.6
(4181)
83.8
(2129)
6
128
(485)
320 (20)
1230 (77)
42
5
15.5
(394)
29.5
(749)
252.6
(6416)
83.8
(2129)
6
128
(485)
320 (20)
1230 (77)
42
8
16.3
(414)
30.3
(770)
296.5
(7531)
83.5
(2121)
8
147
(556)
370 (23)
1440 (91)
44
3
15.8
(401)
28.8
(732)
287.1
(7292)
94.2
(2393)
6
94
(356)
280 (18)
1100 (69)
47
5
16.3
(414)
30.3
(770)
308.4
(7833)
71.5
(1816)
8
147
(556)
370 (23)
1440 (91)
48
3
15.8
(401)
28.8
(732)
331.2
(8412)
94.2
(2393)
6
94
(356)
280 (18)
1100 (69)
49
0
15.5
(394)
29.5
(749)
176.2
(4476)
71.5
(1817)
6
130
(492)
320 (20)
1230 (77)
50
0
16.3
(414)
30.3
(770)
176.2
(4475)
71.5
(1816)
8
147
(556)
370 (23)
1440 (91)
52
3
16.3
(414)
30.3
(770)
308.4
(7833)
71.5
(1816)
8
147
(556)
370 (23)
1440 (91)
TABLE 9 -
OPTIONAL THREE-PASS REAR INLET/FRONT OUTLET EVAPORATOR (CONT'D)
NOTE
: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Office for ratings and further information.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...