
SECTION 8 - MICROPANEL
JOHNSON CONTROLS
141
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
8
Precharge Signal Status and VSD Cooling
Status
VSD
PRECHARGE SIGNAL = XXX
This display provides the state of the precharge signal,
where XXX is either ON or OFF at the time of the
fault.
Compressor #1 and #2, 105% FLA Motor
Overload Current Setting
VSD
COMP 1 MOTOR OVERLOAD = XXX AMPS
COMP 2 MOTOR OVERLOAD = XXX AMPS
This message displays the setting of the VSD’s 100%
FLA potentiometer for Compressor #1 and #2 at the
time of the fault.
System Data
System #1 Pressures
SYS 1 PRESSURES
OIL = XXXX PSIG
DISCHARGE = XXXX PSIG
This message displays the measured system oil and
discharge pressures at the time of the fault.
SYS 1 PRESSURES
SUCTION = XXXX PSIG
CONDENSER LIQUID = XXXX PSIG
This message displays the measured system suction
and condenser liquid line pressure at the time of the
fault.
System # 1 Temperatures
SYS 1 TEMPERATURES
OIL = XXX.X °F
EDUCTOR = XXX.X °F
This message displays the measured system oil and
eductor temperatures at the time of the fault.
SYS 1 CONDENSER LIQUID TEMP = XXX.X °F
SUBCOOLING = XXX.X SAT TEMP = XXX.X °F
This message displays the condenser liquid, liquid line
subcooling and saturated discharge temperatures at the
time of the fault.
SYS 1 DISCHARGE
TEMP = XXX.X °F
SUPERHEAT = XXX.X SAT TEMP = XXX.X °F
This message displays the system discharge, discharge
superheat and saturated discharge temperatures at the
time of the fault.
Compressor Speed and Heater Status
SYS 1 COMPRESSOR SPEED = XXX.X %
HEATER = XXX.X °F
This message indicates the compressor speed in % and
the heater status at the time of the fault.
System #1 Motor Temperatures
SYS 1 MOTOR TEMPS
T1 = XXX.X °F
T2 = XXX.X
T3 = XXX.X °F
This message displays the System 1 motor thermistor
temperatures at the time of the fault.
Flash Tank Level and Economizer Position
SYS 1
FLASH TANK LEVEL Y 512 ADC
ECONOMIZER VALVE = XXX.X %
This message displays the flash tank level and the
economizer valve position in % at the time of the fault.
Condenser Subcooling and Condenser Drain
Valve Position
SYS 1 CONDENSER SUBCOOLING = XXX.X
°
F
CONDENSER DRAIN VALVE = XXX.X %
This message displays the condenser subcooling and
the Condenser Drain Valve position at the time of the
fault.
Condenser Fans
SYS 1
CONDENSER FANS ON = X
SYS 1
CONDENSER FANS ON = X
VSD FAN SPEED XX.X V = XXX %
This message displays the number of condenser fans
ON or the optional VSD fan control speed signal to the
inverter and the % of full speed.
VI Step Solenoid
SYS 1
VI STEP SOLENOID 1 = XXX
VI STEP SOLENOID 2 = XXX
This message displays whether the VI solenoids were
ON or OFF at the time of the fault.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...