SECTION 9 - MAINTENANCE
JOHNSON CONTROLS
167
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
9
TABLE 27 -
TROUBLESHOOTING GUIDE (CONT'D)
PROBLEM
POSSIBLE CAUSE
ACTION
SYSTEM STATUS:
MOTOR CURRENT
LIMITING
A high motor current anticipatory control
has activated current limiting
Ambient temperature is high, normal
response from controller
Remote or panel limiting is in effect,
Normal response.
Excess charge in system, adjust charge.
Condenser coils dirty, Clean condenser.
Fans NOT operating. Check fans.
VSD FAULT:
HIGH BASEPLATE
TEMPERATURE
Coolant level low.
Add coolant.
Glycol Pump is defective.
Replace Glycol Pump.
VSD Board is defective
Replace VSD Logic Board.
IBGT Module is defective.
Check defective IGBT Module.
VSD FAULT:
LOW DC BUS VOLTAGE
SCR / Diode Module is defective.
Check SCR / Diode Module.
SCR Trigger Board is defective.
Check SCR Trigger Board.
NOTE:
Always remove power to the chiller and assure the DC Bus voltage has bled off.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...