SECTION 8 - MICROPANEL
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
Compressor #1 Run Time
SYS 1 RUN TIME
XX DAYS XX HOURS XX MINUTES XX SECONDS
This message displays the system run time since the
last start in days, hours, minutes, and seconds at the
time of the fault.
System #1 Run Signals
SYS 1 RUN SIGNALS
RELAY = XXX
RUN PERM = XXX
SOFTWARE = XXX
This message displays the System Run Signal Relay
(Relay Output Board) status, Run Permissive Input
status, and the Internal Software (microprocessor com-
mand) ON/OFF Start status. The status of each will in-
dicate either ON or OFF.
System 2 Data
Data for the system 2 at the time of the fault is dis-
played in the same sequence as the system #1 data.
Compressor Operating Hours and Starts
HOURS 1=XXXXX, 2=XXXXX
START 1=XXXXX, 2=XXXXX
This message displays compressor operating hours and
compressor starts at the time of the fault.
Chilled Liquid Setpoint Cooling Setpoints
SETPOINTS
LOCAL COOLING SETPOINT
= XXX.X °F
This message displays the programmed cooling
setpoint at the time of the fault.
SETPOINTS
LOCAL CONTROL RANGE
= +/- X.X °F
This message displays the programmed Control Range
at the time of the fault.
Remote Setpoint and Range
SETPOINTS REMOTE SETPOINT = XXX.X °F
REMOTE CONTROL RANGE = +/- X.X °F
This message displays the remote setpoint and Control
Range at the time of the fault.
Maximum Remote Temperature Setpoint
SETPOINTS
MAXIMUM REMOTE TEMP RESET = XXX.X °F
This message displays the maximum remote reset pro-
grammed at the time of the fault.
Options
Display Language
OPTIONS
DISPLAY LANGUAGE
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message displays the language selected at the time
of the fault.
Chilled Liquid Cooling Mode
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
WATER COOLING
This message displays the chilled liquid temperature
mode (water or glycol) selected at the time of the fault.
Local / Remote Control Mode
OPTIONS
CHILLED LIQUID COOLING MODE
◄ ►
GLYCOL COOLING
This message indicates whether Local or Remote Con-
trol Mode was selected at the time of the fault.
OPTIONS LOCAL / REMOTE CONTROL MODE
◄ ►
XXXXXXXXXXXXXXXXXXXXX
When Remote Control Mode is selected, control of the
Chilled Liquid Setpoint is from a remote device such
as an ISN/BAS controller.
Display Units Mode
OPTIONS DISPLAY UNITS
◄ ►
XXXXXXXXXXXXXXXXXXXX
This message indicates whether SI (°C, barg) or
Imperial units (°F, PSIG) was selected at the time of
the fault.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...