SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
69
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
TABLE 6
- PHYSICAL DATA - ROUND TUBE COIL (CONT'D)
UNIT FRAME
32
33
34
37
41
44
48
49
50
52
CONDENSER CODE
3
3
3
3
3
3
3
0
0
3
EVAPORATOR CODE
E
C
E
F
H
G
G
K
J
J
GENERAL UNIT DATA
Number of Independent
Refrigerant Circuits
2
Refrigerant Charge, R-134a,
Ckt.-1/Ckt.-2, lbs (kg)
367/367
(166/166)
371/371
(168/168)
391/391
(177/177)
537/308
(244/140)
568/417
(258/189)
478/478
(217/217)
502/502
(228/228)
480/480
(218/218)
495/495
(224/224)
562/562
(255/255)
Oil Charge, Ckt.-1/Ckt.-2,
gal (liters)
3.7/3.7
(14.0/
14.0)
3.7/3.7
(14.0/
14.0)
3.8/3.8
(14.4/
14.4)
4.0/2.9
(15.1/
11.0)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.0/4.0
(15.1/
15.1)
4.2/4.2
(15.9/
15.9)
Minimum Load (%)
10%
Chassis Dimensions - Length,
inches (mm)
379.2
(9631)
423.1
(10748)
423.1
(10748)
467.1
(11864)
467.1
(11864)
555.3
(14104)
599.3
(15222)
467.1
(11864)
467.1
(11864)
599.3
(15222)
Chassis Dimensions -
Width, inches (mm)
88.3
(2242)
88.3
(2242)
88.3
(2242)
88.3
(2243)
88.3
(2243)
88.3
(2243)
88.4
(2244)
88.3
(2242)
88.4
(2244)
88.3
(2243)
Chassis Dimensions - Height,
inches (mm)
94.6
(2403)
94.6
(2403)
94.6
(2403)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.7
(2405)
94.6
(2403)
94.7
(2405)
94.7
(2405)
COMPRESSORS, SEMI-HERMETIC SCREW
Qty per Chiller
2
CONDENSER FANS
Number Ckt-1/Ckt-2
8/8
9/9
9/9
13/7
12/8
12/12
13/13
10/10
10/10
13/13
Air on Condenser
(Min/Max), °F (°C)
0/125
(-17.8/51.7)
EVAPORATOR, SHELL AND TUBE HYBRID FALLING FILM
Water Volume, gal (liters)
113 (428) 71 (269) 113 (428) 96 (363) 130 (492) 96 (363) 96 (363) 130 (492) 147 (556) 147 (556)
Leaving Water Temperature
(Min/Max), °F (°C)
2
40/60
(4.4/15.6)
Maximum Water Side
Pressure, psig (barg)
150
(10.3)
Maximum Refrigerant Side
Pressure, psig (barg)
235
(16.2)
Evap Drain Connection,
inches (mm)
3/4
Minimum Chilled Water Flow
Rate, gpm (l/sec)
400
(25.2)
300
(18.9)
400
(25.2)
460
(29.0)
520
(33.0)
460
(29.0)
460
(29.0)
470
(30)
550
(34.1)
550
(34.1)
Maximum Chilled Water Flow
Rate, gpm (l/sec)
1500
(94.7)
1150
(72.6)
1500
(94.7)
1540
(97.0)
1700
(107.0)
1540
(97.0)
1540
(97.0)
1870
(118)
1880
(118.1)
1880
(118.1)
Inlet and Outlet Water
Connections, in
8
6
8
8
8
8
8
8
8
8
NOTES:
Shipping and operating weights shown are for base unit; selected options may add weight to unit. Contact your nearest Johnson Controls Sales
office for weight data.
1. R-513A is not an option.
2. For leaving liqu
id temperature below 40°F(4.4°C) or above 60°F (15.6°C), contact your nearest Johnson Controls Sales Office for application
requirements.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...