SECTION 9 - MAINTENANCE
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
TABLE 27 -
TROUBLESHOOTING GUIDE (CONT'D)
PROBLEM
POSSIBLE CAUSE
ACTION
SYSTEM FAULT:
HIGH DISCHARGE
PRESSURE
Coils dirty.
Check and clean coils.
Coils are damaged.
Comb out fins.
Fans NOT operating.
Check fan fuses.
Check fan rotation.
Check fan motor/blade.
System is overcharged.
Remove charge and check subcooling.
SYSTEM FAULT:
HIGH DISCHARGE
TEMPERATURE
Discharge Temperature Sensor is defective.
Check Sensor.
Condenser Fans NOT operating or are run-
ning backwards.
Check Fans.
Coils dirty.
Check and clean Coils.
High Superheat.
Measure Superheat with gauges and
thermocouple. Determine cause.
SYSTEM FAULT:
HIGH MOTOR
TEMPERATURE
High Motor temperature input from one of the
sensors.
Refrigerant charge low. Check subcooling.
Excess charge in system, High discharge
pressure. Check subcooling.
High Superheat. Drain/Feed Valves NOT
controlling. Isolate cause.
Motor Sensor reading incorrectly. Program
panel to ignore a single sensor.
Economizer Solenoid energized at low
speeds. Valve is leaking through.
SYSTEM FAULT:
LOW SUCTION
PRESSURE
Low charge.
Check subcooling.
Transducer reads incorrectly.
Check transducer against a gauge.
Suction Temp. Sensor reads incorrectly.
Check sensor against a thermocouple.
Low flow.
Check flow.
Condenser Drain (Flash Tank Feed) Valve
NOT operating.
Check Feed and Drain Valve operation.
Check superheat.
Condenser or Drain (Flash Tank Feed) Valve
defective.
Check Feed and Drain Valve operation.
Check superheat.
SYSTEM FAULT:
DISCHARGE PRESSURE
LIMITING
Discharge Transducer is defective.
Check transducer against a gauge.
Ambient Temp. very high.
Normal operation.
Fans NOT operating.
Check fan operation.
Remote or local discharge pressure
load limiting is programmed.
Normal operation.
NOTE:
Always remove power to the chiller and assure the DC Bus voltage has bled off.
Содержание YVAA
Страница 4: ...JOHNSON CONTROLS 4 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 96: ...JOHNSON CONTROLS 96 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 126: ...JOHNSON CONTROLS 126 FORM 201 28 NM1 1 ISSUE DATE 10 12 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 174: ...JOHNSON CONTROLS 174 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 177: ...JOHNSON CONTROLS 177 FORM 201 28 NM1 1 ISSUE DATE 1 31 2018 NOTES...