Wiring PG Speed Control Card Terminal Blocks
Wiring PG Speed Control Card Terminal Blocks
Use no more than 100 meters of wiring for PG (encoder) signal lines, and keep them separate from power
lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield
to the shield connection terminal.
Wire Sizes (Same for All Models)
Wire Sizes (Same for All Models)
Terminal wire sizes are shown in Table 3.14.
Table 3.14 Wire Sizes
Terminal
Terminal
Screws
Wire Thickness
(mm2)
Wire Type
Pulse generator power supply
P u l s e i n p u t t e r m i n a l
Pulse monitor output terminal
Shield connection terminal
M3.5
Stranded wire: 0.5 to
1.25
Single wire: 0.5 to 1.25
0.5 to 2
Shielded, twisted-pair
wire
Shielded, polyethylene
-covered
vinyl sheath cable
Solderless Terminals for Control Circuit Terminals
Solderless Terminals for Control Circuit Terminals
The use of solderless terminals for the control circuit terminals is recommended because solderless
terminals
are easy to connect securely.
Straight Solderless Terminal Sizes
Wire Thickness
Model
Manufacturer
Phoenix Contact
Straight Solderless Terminal Sizes
IMPORTANT
Do not solder wires with the control circuit terminals if wires are used instead of solderless terminals.
Wires may not contact well with the control circuit terminals or the wires may be disconnected from
the control
circuit terminals due to oscillation if the wires are soldered
Is a registered trademark of yolico