
Model YPP6060 Dual-Input Process Meter
Instruction Manual
83
Meter Copy Function (
Copy
)
The
Copy
function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and
programming (
i.e
. type of input, scaling, decimal point, filter, bypass,
etc.).
Warning!
Only the YPPA1200 meter copy cable must be used for
meter-to-meter interfacing. The YPPA1200 is a special
eight-conductor flat cable with two wires swapped.
Using standard CAT5 or other cable will cause damage to
both meters.
Figure 20. Meter Copy Connection
Copy Function Requirements
To successfully copy settings from one
meter to another, both meters must have:
1. Same software version
2. Same baud rate setting
See
Determining Software Version
,
page 87 for instructions.
Meter Copy or Cloning Instructions
!
Caution!
Do not connect the two meters to
the same signal source while
cloning. Internal calibration may
be affected.
YPPA1200 Meter Copy Cable
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...
Страница 104: ...Model YPP6060 Dual Input Process Meter Instruction Manual LIM6060YK_B SFT065 Ver 2 200 up 11 11 ...