Model YPP6060 Dual-Input Process Meter
Instruction Manual
76
Changing the Volume from Gallons to Liters
In the above graphic, entering the 48" for the diameter and 120" for the
length of the round horizontal tank, the meter automatically calculates
that the volume of the tank is 940.02 gallons.
1. Convert gallons to liters
1 US gallon = 3.7854 L
940.02 gal = 3558.4 L
2. Go to the
Setup
menu and change the decimal point to 1 decimal.
3. Go to the
Program
–
Scale
menu and press Enter until
dis 2
is
shown on the main display.
4. Press Enter and change the display 2 value to 3558.4.
5. The meter is now displaying the volume in liters.
Note: The display can be scaled to display the volume in any
engineering units.
Low-Flow Cutoff (
CutofF
)
The low-flow cutoff feature allows the meter to be programmed so that
the often-unsteady output from a differential pressure transmitter, at low
flow rates, always displays zero on the meter.
The cutoff value may be programmed from 0 to 999999. The meter will
display zero below the cutoff value. Programming the cutoff value to
zero disables the cutoff feature.
Analog Output Programming (
AoutPr
)
The
Analog Output Programming
menu is used to program the behavior
of the 4-20 mA output. The following parameters and functions are
programmed in this menu:
1. Source: Source for generating the 4-20 mA output (e.g. channel A)
2. Overrange: Analog output value with display in overrange condition
3. Underrange: Analog output value with display in underrange condition
4. Break: Analog output value when loop break is detected
5. Max: Maximum analog output value allowed regardless of input
6. Min: Minimum analog output value allowed regardless of input
7. Calibrate: Calibrate the internal 4-20 mA source reference used to
scale the 4-20 mA output
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...