Model YPP6060 Dual-Input Process Meter
Instruction Manual
45
Setting the Relay Operation (
relay
)
This menu is used to set up the assignment and operation of the relays.
CAUTION! During setup, the relays do not follow the input and they will
remain in the state found prior to entering the Relay menu.
1. Relay
assignment
a. Channel
A
b. Channel
B
c. Channel C (Math channel)
d. Modbus
2. Relay
action
a. Automatic reset only (non-latching)
b. Aut manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
condition has cleared)
e. Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
3. Set
point
4. Reset
point
5. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
6. Time
delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
7. Relay action for loss (break) of 4-20 mA input (ignore, on, off)
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...
Страница 104: ...Model YPP6060 Dual Input Process Meter Instruction Manual LIM6060YK_B SFT065 Ver 2 200 up 11 11 ...