Model YPP6060 Dual-Input Process Meter
Instruction Manual
36
Setting the Input Signal (
Input
)
Enter the
Input
menu to set up the meter to display current (
mA
) or
voltage (
volt
) inputs for channel A and channel B.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or
±
10 VDC signals.
Channel C is the Math Function calculation, which is set up in the
Advanced Features menu.
Setting the Decimal Point (
dEc pt
)
The decimal point may be set with up to five decimal places or with no
decimal point at all.
Pressing the Right arrow moves the decimal point one place to the right
until no decimal point is displayed, and then it moves to the leftmost
position.
There are three decimal points to set up for three channels: Ch-A, Ch-B,
and Ch-C.
After the decimal points are set up, the meter moves to the
Program
menu.
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...
Страница 104: ...Model YPP6060 Dual Input Process Meter Instruction Manual LIM6060YK_B SFT065 Ver 2 200 up 11 11 ...