Model YPP6060 Dual-Input Process Meter
Instruction Manual
63
Scaling the 4-20 mA Analog Output (
Aout
)
The 4-20 mA analog output can be scaled to provide a 4-20 mA signal
for any display range selected.
No equipment is needed to scale the analog output; simply program the
display values to the corresponding mA output signal.
The
Analog Output
menu is used to program the 4-20 mA output based
on display values.
Aout
setup
dis 1
Aout
0
04.000
d i s 1
dis 2
Aout
0
20.000
d i s 2
Out 1
Aout
0
4.000
O u t 1
Out 2
Aout
2
0.000
O u t 2
For instructions on how to program
numeric values see
Setting Numeric
Values
, page 34.