Model YPP6060 Dual-Input Process Meter
Instruction Manual
19
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all
connectors available with requested configuration.
Warning!
Do not connect any equipment other than Yokogawa
Corporation of America’s expansion modules, cables, or
meters to the RJ45 M-LINK connector. Otherwise damage
will occur to the equipment and the meter.
Figure 5. Connector Labeling for Fully Loaded YPP6060
Power Connections
Power connections are made to a two-terminal connector labeled
POWER on Figure 5. The meter will operate regardless of DC polarity
connection. The + and - symbols are only a suggested wiring convention.
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+ -
Figure 6. Power Connections