Model YPP6060 Dual-Input Process Meter
Instruction Manual
74
Signal Input Conditioning (
Functn
)
The
Function
menu is used to select the input-to-output transfer function
applied to the input signal: linear, square root, programmable exponent,
or round horizontal tank volume calculation. The multi-point linearization
is part of the linear function selection.
Meters are set up at the factory for linear function with 2-point
linearization. The linear function provides a display that is linear with
respect to the input signal.
Square Root Linearization (
Square
)
The square root function is used to calculate flow measured with a
differential pressure transmitter. The flow rate is proportional to the
square root of the differential pressure. Scale the meter so that the low
input signal (e.g. 4 mA) is equal to zero flow and the high input signal
(e.g. 20 mA) is equal to the maximum flow.
Programmable Exponent Linearization (
Prog E
)
The programmable exponent function is used to calculate open-channel
flow measured with a level transmitter in weirs and flumes. The flow rate
is proportional to the head height. Scale the meter so that the low input
signal (e.g. 4 mA) is equal to zero flow and the high input signal (e.g. 20
mA) is equal to the maximum flow. This method works well for all weirs
and flumes that have a simple exponent in the flow calculation formula.
For weirs and flumes with complex exponents it is necessary to use a
strapping table and the 32-point linearization of the meter.
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...
Страница 104: ...Model YPP6060 Dual Input Process Meter Instruction Manual LIM6060YK_B SFT065 Ver 2 200 up 11 11 ...