Model YPP6060 Dual-Input Process Meter
Instruction Manual
12
RELAY RESET
User selectable via front panel buttons or digital inputs
1.
Automatic reset only (non-latching), when the input
passes the reset point.
2.
Aut manual reset at any time (non-latching)
3.
Manual reset only, at any time (latching)
4.
Manual reset only after alarm condition has cleared (L)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
TIME DELAY
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
FAIL-SAFE
OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
AUTO
INITIALIZATION
When power is applied to the meter, relays will reflect the
state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT
SOURCE
Process channel A, B, or C, max or min for channel A, B, or
highest or lowest max or min of A and B, set points 1-8,
Modbus input, or manual control mode
SCALING RANGE
1.000 to 23.000 mA for any display range
CALIBRATION
Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT
PROGRAMMING
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
ACCURACY
± 0.1% of span ± 0.004 mA
TEMPERATURE
DRIFT
0.4 µA/
°
C max from 0 to 65
°
C ambient,
0.8 µA/
°
C max from -40 to 0
°
C ambient
Note: Analog output drift is separate from input drift.
ISOLATED
TRANSMITTER
POWER SUPPLY
Terminals I+ & R: 24 VDC
±
5% @ 40 mA maximum; may
be used to power the 4-20 mA output or other devices.
Refer to Figure 5 on page 19 and Figure 14 on page 23.
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply
Minimum
Maximum
24 VDC
10
Ω
700
Ω
35 VDC (external)
100
Ω
1200
Ω
Содержание YPP6060
Страница 46: ...Model YPP6060 Dual Input Process Meter Instruction Manual 46 Setting the Relay Assignment asSign ...
Страница 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Страница 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Страница 101: ...Model YPP6060 Dual Input Process Meter Instruction Manual 101 Figure 23 1 8 DIN Panel Cutout Template ...
Страница 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Страница 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...
Страница 104: ...Model YPP6060 Dual Input Process Meter Instruction Manual LIM6060YK_B SFT065 Ver 2 200 up 11 11 ...