IM 05P01C31-15EN   page 10/12

If you are using two or more groups of PID parameters, use the following table to record their setting values.

Parameter

n=2

n=3

n=4

n=5

n=6

n=7

n=8

R

P

I

D

OH

OL

MR

HYS

SU.HY

HY.UP
HY.LO

DR

SU.DR

Pc

Ic

Dc

OHc

OLc

HYSc

DB
PO

SU.PO

POc

n: group number

 Tuning Parameter 

Menu symbol: 

 

(TUNE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(SC)

Super function

OFF: Disable

1: Overshoot suppressing function 

(normal mode)

2: Hunting suppressing function 

(stable mode)

Enables to answer the wider 

characteristic changes compared 

with response mode.

3: Hunting suppressing function 

(response mode)

 

Enables quick follow-up and short 

converging time of PV for the 

changed SP.

4: Overshoot suppressing function 

(strong suppressing mode)

Note: Setpoints 2 and 3 must be 

used in PID control or PI control.

Disabled in the following controls: 

 

1) ON/OFF control, 2) PD control, 3) 

P control, 4) Heating/cooling control.

Do not use the function for the con-

trol processes with response such as 

flow or pressure control.

OFF

EASY

(AT.TY)

Auto-tuning type

0: Normal

1: Stability

0

STD

(STM)

Sample PI sampled time

0 to 9999 s

60 s

EASY

(SWD)

Sample PI control time 

span

0 to 9999 s

30 s

(AR)

Anti-reset windup 

(excess integration 

prevention)

AUTO, 50.0 to 200.0%

AUTO

STD

(OPR)

Output velocity limiter

OFF: Disable

0.1 to 100.0%/s

OFF

(MPON)

Manual preset output 

number selection

Select the output used in MAN mode 

when switched from AUTO to MAN 

mode.

OFF: Hold the control output in AUTO          

mode (bumpless)

1: Use manual preset output 1 (output 

bump)

2: Use manual preset output 2 (output 

bump)

3: Use manual preset output 3 (output 

bump)

4: Use manual preset output 4 (output 

bump)

5: Use manual preset output 5 (output 

bump)

OFF

 to

(MPO1 to MPO5)

Manual preset output 1 

to 5

-5.0 to 105.0% 

However, output is limited to the 

output high limit and low limit.

0.0%

Table 

below

Use the following table to record the manual preset output setting value.

Parameter

n=1

n=2

n=3

n=4

n=5

MPOn

 Zone Control Parameter

Menu symbol: 

 (ZONE)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to

(RP1 to RP7)

Reference point 1 to 7

Set reference points at which switch

-

ing is carried out between groups of 

PID constants according to the given 

temperature zone.

0.0 to 100.0% of PV input range (EU) 

 

(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5 ≤ 

RP6 ≤ RP7)

100.0% 

of PV 

input 

range

Table 

below

STD

(RHY)

Zone PID switching 

hysteresis

Hysteresis can be set for switching at 

a reference point.

0.0 to 10.0% of PV input range span 

(EUS)

0.5 % 

of PV 

input 

range 

span

(RDV)

Reference deviation

Set a deviation from SP. The PID for 

reference deviation is used if there 

is a larger deviation than the preset 

reference deviation.

OFF: Disable

0.0 + 1 digit to 100.0% of PV input 

range span (EUS)

OFF

For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se-

lection.

Use the following table to record the reference point setting value. 

Parameter

n=1

n=2

n=3

n=4

n=5

n=6

n=7

RPn

 P Parameter (for Ladder Program) 

Menu symbol: 

 (PPAR)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

 to 

(P01 to P10)

P01 to P10 parameter

-19999 to 30000 (Set a decimal point 

position using LL50A Parameter Set-

ting Software.)

0

Table 

below

STD

Parameter

n=01

n=02

n=03

n=04

n=05

n=06

n=07

n=08

n=09

n=10

Pn

 10-segment Linearizer-1, -2 Setting Parameter

Menu symbol: 

 (PYS1)

 

 (PYS2)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PYS)

10-segment linearizer 

selection 

OFF: Disable

PV: PV analog input

RSP: RSP analog input

AIN2: AIN2 analog input

AIN4: AIN4 analog input

PVIN: PV input

OUT: OUT analog output

OUT2: OUT2 analog output

RET: RET analog output

PV

 

(CTLM: 

SGL)

STD

(A1)

10-segment linearizer 

input 1

-66.7 to 105.0% of input range (EU)

Output linearizer: -5.0 to 105.0%

0.0%

(B1)

10-segment linearizer 

output 1

10-segment linearizer bias: -66.7 to 

105.0% of input range span (EUS)

10-segment linearizer approximation: 

-66.7 to 105.0% of input range (EU)

Output linearizer: -5.0 to 105.0%

0.0%

 to 

 to 

(A2 to A11,

B2 to B11)

10-segment linearizer 

input 2 to 11 

10-segment linearizer 

output 2 to 11

Same as A1 and B1

Same 

as

A1

and

B1

(PMD)

10-segment linearizer 

mode

0: 10-segment linearizer bias

1: 10-segment linearizer approxima-

tion

0

Use the following table to record the 10-segment linearizer input and output setting values.

Parameter

n=2

n=3

n=4

n=5

n=6

n=7

n=8

n=9

n=10

n=11

An

Bn

Setup Parameters

Hold down the PARAMETER key or PARA key and Left arrow key simultaneously for 3 

seconds to move from the Operation Display or Operation Parameter Setting Display to 

the Setup Parameter Setting Display.

Press the DISPLAY key or DISP key once to return to the Operation Display.

Menu

DISPLAY key

or DISP key

SET/ENTER key

PARAMETER key

or PARA key

key

key

key

key

key

Operation Dsipaly

Parameter

Parameter

Parameter

Parameter

Parameter

Parameter

END

Menu

END

Menu

END

END

Menu Display and 

Parameter Setting 

Display are changed 

in a circular pattern.

Move to the Operation Parameter Setting Display: 

          Hold down the PARAMETER key or PARA key for 3 sec.

Hold down PARAMETER key or PARA key and 

Left arrow key simultaneously for 3 sec.

Operation for Setting

·  To select the parameter setting displayed as the initial value, press the Down arrow 

key to move to the next parameter.

·  To change and set the parameter setting, press the SET/ENTER key to start the set-

point blinking. The blinking state allows you to make changes (setting mode). Use the 

Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to 

register the setting.

Note that there are some parameters which are not displayed depending on the Model 

and Suffix codes, control mode (CTLM), control type (CNT), etc. The parameters for pro-

fessional setting mode (LEVL: PRO) are not described in this manual. See User’s Manual 

(IM 05P01C31-01EN).

 Control Function Setting Parameter

Menu symbol: 

 (CTL)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(CTLM)

Control mode

When using the controls other than 

Single-loop control, see User's Manu-

al (IM 05P01C31-01EN). 

SGL

STD

SGL: Single-loop control

CAS1: Cascade primary-loop control

CAS2: Cascade secondary-loop control

CAS: Cascade control

BUM: Loop control for backup

PVSW: Loop control with PV switching

PVSEL: Loop control with PV auto-selector

PVHD: Loop control with PV-hold function

(CNT)

Control type

PID: PID control

ONOF: ON/OFF control (1 point of hysteresis)

ONOF2: ON/OFF control (2 points of hysteresis)

2P2L: Two-position two-level control

H/C: Heating/cooling control

S-PI: Sample PI control

BATCH: Batch PID control

FFPID: Feedforward control

PID or 

H/C (for 

Heat

-

ing/

Coo-

ling-

type)

EASY

(SPGR.)

Number of SP groups

Set a number of SP groups to use.

1 to 8

8

STD

(ZON)

Zone PID selection

If set to “SP group number selection,” allows 

PID constants to be selected for each SP 

group.

 

If set to “Zone PID selection,” automatically 

selects PID constants according to the range 

set in the Reference point. 

0: SP group number selection 1

1: Zone PID selection (selection by PV)

2: Zone PID selection (selection by target SP)

3: SP group number selection 2

4: Zone PID selection (selection by SP) 

0

(PIDG.)

Number of PID groups

Set a number of PID groups to use.

1 to 8

8

(SMP)

Input sampling period 

(control period)

50: 50 ms, 100: 100 ms, 200: 200 ms

100

 PV Input Setting Parameter 

Menu symbol: 

 (PV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

PV input type

OFF: Disable

K1: -270.0 to 1370.0 

0

C / -450.0 to 2500.0

 

0

F

K2: -270.0 to 1000.0 

0

C / -450.0 to 2300.0

 

0

F

K3: -200.0 to 500.0 

0

C / -200.0 to 1000.0

 

0

F

J: -200.0 to 1200.0 

0

C / -300.0 to 2300.0

 

0

F

T1: -270.0 to 400.0 

0

C / -450.0 to 750.0

 

0

F

T2: 0.0 to 400.0 

0

C / -200.0 to 750.0

 

0

F

B: 0.0 to 1800.0 

0

C / 32 to 3300

 

0

F

S: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

R: 0.0 to 1700.0 

0

C / 32 to 3100

 

0

F

N: -200.0 to 1300.0 

0

C / -300.0 to 2400.0

 

0

F

E: -270.0 to 1000.0 

0

C / -450.0 to 1800.0

 

0

F

L: -200.0 to 900.0 

0

C / -300.0 to 1600.0

 

0

F

U1: -200.0 to 400.0 

0

C / -300.0 to 750.0

 

0

F

U2: 0.0 to 400.0 

0

C / -200.0 to 1000.0

 

0

F

W: 0.0 to 2300.0 

0

C / 32 to 4200

 

0

F

PL2: 0.0 to 1390.0 

0

C / 32.0 to 2500.0

 

0

F

P2040: 0.0 to 1900.0 

0

C / 32 to 3400

 

0

F

WRE: 0.0 to 2000.0 

0

C / 32 to 3600

 

0

F

JPT1: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

JPT2: -150.0 to 150.0 

0

C / -200.0 to 300.0

 

0

F

PT1: -200.0 to 850.0 

0

C / -300.0 to 1560.0

 

0

F

PT2: -200.0 to 500.0 

0

C / -300.0 to 1000.0

 

0

F

PT3: -150.00 to 150.00 

0

C / -200.0 to 300.0

 

0

F

0.4-2V: 0.400 to 2.000 V

1-5V: 1.000 to 5.000 V

4-20: 4.00 to 20.00 mA

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-20 : 0.00 to 20.00 mA

-1020: -10.00 to 20.00 mV

0-100: 0.0 to 100.0 mV

OFF

EASY

(UNIT)

PV input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit, 

F: Degree Fahrenheit

C

(RH)

Maximum value of PV 

input range

Depends on the input type.

-For temperature input-

Set the temperature range that is 

actually controlled. (RL<RH)

-For voltage/current input-

Set the range of a voltage/current 

signal that is applied.

The scale across which the voltage/

current signal is actually controlled 

should be set using the maximum 

value of input scale (SH) and mini-

mum value of input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

(RL)

Minimum value of PV 

input range

Depends 

on the 

input type

(SDP)

PV input scale decimal 

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(SH)

Maximum value of PV 

input scale

-19999 to 30000, (SL<SH),

| SH - SL | ≤ 30000

Depends 

on the 

input type

(SL)

Minimum value of PV 

input scale

(BSL)

PV input burnout action

OFF: Disable

UP: Upscale

DOWN: Downscale

Depends 

on the 

input type

STD

(A.BS)

PV analog input bias

-100.0 to 100.0% of PV input range 

span (EUS)

0.0 % of 

PV input 

range 

span

(A.FL)

PV analog input filter

OFF, 1 to 120 s

OFF

W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25

 RSP Input Setting Parameter (E1-terminal Area)

Menu symbol: 

 (RSP)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

RSP remote input type

0.4-2V: 0.400 to 2.000 V

-5V: 1.000 to 5.000 V

0-2V: 0.000 to 2.000 V

0-10V: 0.00 to 10.00 V

0-125: 0.000 to 1.250 V

For option /U1, RSP remote input 

type is same as PV input type

1-5V

EASY

(UNIT)

RSP remote input unit

-: No unit, C: Degree Celsius

-: No unit, - -: No unit, - - -: No unit,

F: Degree Fahrenheit

C

(RH)

Maximum value of RSP 

remote input range

Depends on the input type.

-For temperature (/U1 option) input-

Set the temperature range that is 

actually controlled. (RL<RH)

-For voltage / current (/U1 option) input

Set the range of a voltage / current 

signal that is applied.

The scale across which the voltage/

current signal is actually controlled 

should be set using the maximum 

value of input scale (SH) and 

minimum value of input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

(RL)

Minimum value of RSP 

remote input range

Depends 

on the 

input type

(SDP)

RSP remote input scale 

decimal point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: