IM 05P01C31-15EN   page 8/12

7.  Switching between REM (Remote) and LCL (Local)

Remote and local switching can be performed using any of the following: 

(1) Contact input, (2) Parameter, (3) Communication, and (4) User function key.

LCL (Local)

Control is performed using the target setpoint set on the controller.

REM (Remote)

Control is performed using an external analog signal that is used as the target set-

point. The following shows an example of switching from local to remote using the 

parameter.

For details of other switching methods, see User’s Manual (IM 05P01C31-01EN).

• The PID group for the local SP number is used as PID in remote mode.

NOTE

When the contact input is ON, operation cannot be performed using the parameter, 

communication, or key. When the contact input is OFF and the setting is switched 

using the parameter, communication, or key, the last switching operation is per-

formed.

Show the Operation Display.

Hold down the PARAMETER key or PARA key 

for 3 seconds to display MODE menu.

Press the SET/ENTER key.

1.
2.

Press the SET/ENTER key.

The REM lamp is lit.

Change the operation mode using 

the Up/Down arrow keys.

Blinks during the change.

Press the SET/ENTER key.

3.

4.

5.

The parameter R.L (REMOTE/LOCAL switch)

is displayed.

8.  Manipulating Control Output in Manual Mode

NOTE

In manual mode, control output is manipulated by operating the keys (the value is 

changed using the Up/Down arrow keys, then outputted as it is).

Even if the SET/ENTER key is not pressed, the control output value changes ac-

cording to the displayed value.

In stop mode (when the STOP lamp is lit), control output cannot be manipulated.

MAN lamp is lit.

Up arrow key: increases control output.
Down arrow key: decreases control output.

In Position proportional control:

Up arrow key; opens the valve.

Down arrow key; closes the valve.

Output; only while pressing a key. 

OUT; valve opening (0-100%)

Output manipulation in Position proportional control 

is not restricted from output limiters (OH, OL).

Manual operation in Heating/cooling control

Symbol of cooling side

Target setpoint (SP) number

Symbol of heating side

Heating-side control output

Cooling-side control output

Up arrow key: concurrently decreases cooling-side control output and increases 

heating-side control output.

Down arrow key: concurrently increases cooling-side control output and decreases 

heating-side control output.

(Either none of the heating-side and cooling-side outputs are presented, or both of 

them are presented according to the dead band setting.)

Actual output (%)

DB=24.8

Dead band: Operation parameter DB

Control computation output

Control computation output

12.4

0

-12.4

Manipulated output change

when a dead band is positive (+)

Actual output (%)

100

DB= -24.8

12.4

0

-12.4

Manipulated output change

when a dead band is negative (-)

100

Cooling-side

manipulated output

Heating-side

manipulated output

Heating-side

manipulated output

Cooling-side

manipulated output

9. Troubleshooting

■ Troubleshooting Flow

If the Operation Display does not appear after turning on the controller’s power, check the procedures in the following flowchart.

If a problem appears to be complicated, contact our sales representatives.

Is the controller

defective?

Contact us for repair. Problem solved.

No communication

capability

Completely

inactive?

Yes

Yes

Yes

No

No

No

Key

operation

failure?

Yes

No

Yes

Check wiring of the

power terminals.

Check the key lock

setting.

Display

failure?

*

Yes

No

Turn off power, and

then turn it on again.

I/O signal

failure?

Yes

No

Check the 

supply voltage.

Check the 

specifications and polarity

 of connected devices .

Check the communication-

related parameters.

Check the specifications

of communication 

devices.

Check the

communication wiring.

Communication

failure?

No

With

communi-

cation?

Yes

Yes

Normal?

Is the 

key locked?

Check the specifications

of the controller.

Yes

No

Correct?

Correct the error(s).

Cancel the setting.

Check the I/O specifications

of the controller.

* The LCD (a liquid crystal display) is used for 

   a display portion of this product.

   The LCD has a characteristic that the display action 

   becomes late at the low temperature.

   Additionally, the luminance and contrast degradation

   are caused due to aged deterioration.

   However, the control function is not affected.

■ 

Remedies if Power Failure Occurs 

during Operations

•  Instantaneous power failure within 20 ms.

 

A power failure is not detected. Normal 

operation continues.

•  Power failure for less than about 5 seconds, 

or for about 5 seconds or more.

 

Affects the "settings" and "operation sta-

tus."

  For  details,  see  User's  Manual  (IM 

05P01C31-01EN).

NOTE

Write down the settings of parameters for a 

repair request.

n

 Errors at Power On

The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see User’s Manual (IM 05P01C31-01EN).

PV display 

(Operation 

Display)

Setpoint display

(Operation Display)

Status indicator

(Operation Display)

Parameter that displays error 

details

Error description

Cause and diagnosis

Remedy

Indication off Indication off

Faulty MCU RAM / MCU ROM

MCU RAM / MCU ROM are failed.

Faulty. Contact us for repair.

ERR

SYS - - - - -

System data error

System data is corrupted.

Faulty. Contact us for repair.

PAR 0004

 

(for user default value error only)

Setup parameter (PA.ER)

User (parameter) default value error User parameter is corrupted.

Initialized to factory default value.

Check and reconfigure the initialized 

setting parameters. Error indication is 

erased when the power is turned on 

again.

PAR 0010 

(for setup parameter error only)

Setup parameter error

Setup parameter data is corrupted.

Initialized to user default value.

PAR 0020 

(for operation parameter error 

only)

Operation parameter error

Operation parameter data is corrupted.

Initialized to user default value.

SLOT 0017 

(0017: Error occurs to all 

hardware of E1 to E4-terminal 

areas.)

Setup parameter (OP.ER)

Nonresponding hardware of 

extended function (E1 to E4-

terminal areas)

Inconsistence of system data and 

hardware of extended function.

Nonresponding communication between 

hardware of extended function (E1 to E4-

terminal areas).

Faulty.

Contact us for repair.

Normal 

indication

Normal indication

Rightmost decimal point 

on PV display blinks.

Setup parameter (PA.ER)

Calibration value error

Initialized to calibrated default value because 

of corrupted factory default value.

Faulty. Contact us for repair.

Rightmost decimal point 

on Symbol display blinks.

Faulty FRAM

Data writing (storing) to FRAM is 

impossible.

Normal 

indication

Normal indication

LADDER lamp blinks

Setup parameter (LA.ER)

Corrupted ladder program

Ladder program is corrupted. 

Operates without ladder program.

Download the ladder program again.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

User profile error 

User profile is corrupted.

Download the user profile again.

n

 Errors during Operation

The errors shown below may occur during operation. (For input/output action when each error occurs, see User’s Manual (IM 05P01C31-01EN).

PV display 

(Operation 

Display)

Setpoint display

(Operation Display)

Status indicator

(Operation Display)

Parameter that displays

error details

Error description

Cause and diagnosis

Remedy

AD.ERR

Normal indication (Note)

Setup parameter (AD1.E)

Analog input terminal ADC error

•PV input

•RSP input (E1-terminal area)

•AIN2 input (E2-terminal area)

•AIN4 input (E4-terminal area)

Analog input terminal AD value error

Faulty.

Contact us for repair.

RJC.E 

(Displays RJC.

E and PV 

alternately.)

Normal indication (Note)

Setup parameter (AD1.E)

Universal input terminal RJC error

•PV input

•RSP input (E1-terminal area)

Universal input terminal RJC error

Faulty.

Contact us for repair.

Set the parameter RJC to OFF to erase 

error indication.

B.OUT

Normal indication (Note)

Setup parameter (AD1.E)

Analog input terminal burnout error

•PV input

•RSP input (E1-terminal area)

•AIN2 input (E2-terminal area)

•AIN4 input (E4-terminal area)

Analog input terminal sensor burnout

Check wiring and sensor.

Error indication is erased in normal 

operation.

Setup parameter (PV1.E / PV2.E) PV input burnout error (Loop 1, 

Loop 2)

Burnout of analog input connected to PV

Check wiring and sensor of connected 

analog input terminals.

Error indication is erased in normal 

operation.

OVER

-OVER

Normal indication

Setup parameter (PV1.E / PV2.E)

PV input over-scale

PV input under-scale

(PV values out of -5 to 105%) (Loop 

1, Loop 2)

PV input is out of -5 to 105%. Also occurs 

when the data out of range which is the 

ladder calculation result is input.

Check analog input value or ladder 

program.

Normal 

indication

Normal indication

Setup parameter (PV1.E / PV2.E) RSP input burnout error (Loop 1, 

Loop 2)

Burnout of analog input connected to RSP Check wiring and sensor. Error 

indication is erased in normal operation.

Normal 

indication

RSP B.OUT

Setup parameter (PV1.E / PV2.E) Burnout error when RSP input is 

used for control (Loop 1, Loop 2)

Burnout of analog input connected to RSP 

when RSP is used for control computation

Check wiring and sensor. Error 

indication is erased in normal operation.

Normal 

indication

OUT - - - - -

Setup parameter (AD2.E)

Feedback input resistor/current 

burnout

Feedback input burnout

Check wiring of feedback input resistor/

current. Error indication is erased in 

normal operation.

Normal 

indication

Normal indication

LADDER lamp blinks

Setup parameter (LA.ER)

Ladder calculation overflow

Floating point computation for ladder 

calculation is infinite.

Check the ladder program.

Load factor over 100%

Computation does not end within the 

control period (load factor is 100% or 

more).

Change the control period or reduce 

the number of steps for the ladder 

program.

Load factor over 200%

(Forced end)

Computation does not end within the control 

period (load factor is 200% or more).

Change the control period or reduce the 

number of steps for the ladder program.

Ladder program error

Ladder program is corrupted.

Download the ladder program again. If 

the error indication is still not erased, 

there is a fault. Contact us for repair.

0.000 00000

(Decimal point on the left of 

the Symbol display blinks)

Setup parameter (OP.ER)

Peer-to-peer communication error Peer-to-peer communication error

Check that the target devices are 

connected correctly.

Recovery at normal receipt.

AT.E

Normal indication

Setup parameter (PV1.E/PV2.E) Auto-tuning time-out 

(Loop 1, Loop 2)

Auto-tuning does not end even when 24 

hours have elapsed after the start of tuning.

Check the process. Hold down any key to 

erase the error indication

VAT.E

Normal indication

Setup parameter (AD2.E)

Valve position automatic 

adjustment error

Fully-closed valve position is equal to or larger 

than the fully-open valve position after automatic 

valve position adjustment is performed.

Check wiring and valve. Hold down any 

key to erase the error indication.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks)

Setup parameter (OP.ER)

Communication error 

(RS-485 communication)

Framing parity error

Buffer overflow 

Inter-character time-out 

Checksum error (PC link communication with 

checksum) 

CRC check error (Modbus/RTU)

LRC check error (Modbus/ASCII)

Check the communication parameters.

Recovery at normal receipt.

Hold down any key to stop blinking.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

Communication error 

(coordinated operation)

Inconsistence of loop between coordinated 

master and slaves

Check the communication parameters.

Recovery at normal receipt.

Change from remote to local mode to stop 

blinking.

When the mode is changed from remote to 

local, SP tracking does not work even if it is 

set to ON.

Communication from coordinated master is 

interrupted for 2 seconds.

Normal 

indication

0.000 00000

(Decimal point on the left of 

the Symbol display blinks) 

Setup parameter (OP.ER)

User profile error 

User profile is corrupted.

Download the user profile again.

Normal 

indication

Normal indication

Rightmost decimal point on 

Symbol display blinks.

Setup parameter (PA.ER)

Faulty FRAM

Writing (storing) data to FRAM is impossible. Faulty. Contact us for repair.

Undefined

Undefined

Faulty MCU / DCU

(ROM / RAM error, corrupted)

MCU / DCU is corrupted.

Faulty. Contact us for repair.

Note: When an error occurs in input shown in Analog input display (Operation display), Setpoint display shows the same symbol as the PV display.

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: