background image

IM 05P01C31-15EN  page 2/12

  Mounting the Instrument Main Unit

Provide an instrumented panel steel sheet of 1 to 10 mm thickness.

After opening the mounting hole on the panel, follow the procedures below to install 

the controller:

1)  Insert the controller into the opening from the front of the panel so that the 

terminal board on the rear is at the far side.

2)  Set the brackets in place on the top and bottom of the controller as shown in the figure 

below, then tighten the screws of the brackets. Take care not to overtighten them.

 

Bracket

(top mounting hardware)

Terminal board

Bracket

(bottom mounting hardware)

Panel

Insert a screwdriver into the

brackets to tighten the screws.

Direction to insert the

controller

Appropriate

tightening torque:

0.25 N

m

Insert the controller

into the opening at

the front of the panel.

CAUTION

•  Tighten the screws with appropriate tightening torque within 0.25 N•m. 

Otherwise it may cause the case deformation or the bracket damage.

•  Make sure that foreign materials do not enter the inside of the 

instrument through the case’s slit holes.

  External Dimensions and Panel Cutout Dimensions

(25)

(53) (2.09)

[(N-1)×96+92]

117 (4.61) min.

145 (5.71)

min.

+0.8

0

+0.8

0

92

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N≥5.

65 (2.56)

20  (0.79)

11

(0.43)

UT55A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket

94.6 (3.72)

91.6 (3.61)

105.2 (4.14)

Unit: mm (approx. inch)

96 (3.78)

96 (3.78)

• General mounting

• Side-by-side close mounting

Terminal cover

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.8

0

92

+0.03

0

(3.62        )

(0.98)

+0.03

0

(3.62        )

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×3.78+3.62]         )

+0.03

0

[(N-1)×48+45]

+0.6

0

65 (2.56)

48 (1.89)

11 (0.43)

UT52A

1 to 10 mm (0.04 to 0.39 inch) (panel thickness)

Bracket

Bracket Terminal cover

94.6 (3.72)

96 (3.78)

105.2 (4.14)

Unit: mm (approx. inch)

70 (2.76)

min.

(25)

145 (5.71)

min.

+0.6

0

45

(53) (2.09)

+0.8

0

92

• General mounting

• Side-by-side close mounting

20  (0.79)

91.6 (3.61)

“N” stands for the number of controllers to be

installed.

However, the measured value applies if N

5.

Normal tolerance: 

±(value of JIS B 0401-1998 tolerance class IT18)/2

+0.03

0

(3.62        )

+0.02

0

(1.77         ) (0.98)

+0.8

0

92

+0.03

0

(3.62        )

([(N-1)×1.89+1.77]        )

+0.02

0

4.  Hardware Specifications

WARNING 

This instrument is for Measurement Category No.1.

Do not use it for measurements in locations falling under Measure-

ment Categories No.2, No.3, and No.4.

Internal Wiring

Outlet

Entrance IV

Cable

III

T

O( I )

II

Category

IEC/EN/CSA

/

UL 

61010-1

EN 61010-2-030

Remarks

No.1

Measurement 

Category I

O (Other)

For measurements performed on circuits not direct

-

ly connected to MAINS.

No.2

Measurement 

Category II

Measurement 

Category II

For measurements performed on circuits directly 

connected to the low-voltage installation.

No.3

Measurement 

Category III

Measurement 

Category III

For measurements performed in the building instal-

lation.

No.4

Measurement 

Category IV

Measurement 

Category IV

For measurements performed at the source of the 

low-voltage installation.

  Input Specifications

●Universal Input (Equipped as standard)

•  Number of inputs: 1

•  Input type, instrument range, and measurement accuracy: See the table below,

Input Type

 Instrument Range

Accuracy

ºC

ºF

Thermo-

couple

K

-270.0 to 1370.0ºC -450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C 

 

±2% of instrument range ±1 digit for 

less than -200.0°C of thermocouple K 

±1% of instrument range ±1 digit for 

less than -200.0°C of thermocouple T

-270.0 to  1000.0ºC -450.0 to 2300.0ºF

-200.0 to  500.0ºC -200.0 to 1000.0ºF

J

-200.0 to 1200.0ºC -300.0 to 2300.0ºF

T

-270.0 to 400.0ºC

-450.0 to 750.0ºF

0.0 to  400.0ºC

-200.0 to 750.0ºF

B

0.0 to 1800.0ºC

32 to 3300ºF

±0.15% of instrument range ±1 digit 

for 400°C or more

 

±5% of instrument range ±1 digit for 

less than 400°C

S

0.0 to 1700.0ºC

32 to 3100ºF

±0.15% of instrument range ±1 digit 

R

0.0 to 1700.0ºC

32 to 3100ºF

N

-200.0 to 1300.0ºC -300.0 to 2400.0ºF

±0.1% of instrument range ±1 digit

±0.25% of instrument range ±1 digit 

for less than 0°C

E

-270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for 

0°C or more

 

±0.2% of instrument range ±1 digit for 

less than 0°C

 

±1.5% of instrument range ±1 digit for 

less than -200.0°C of thermocouple E.

L

-200.0 to 900.0ºC

-300.0 to 1600.0ºF

U

-200.0 to 400.0ºC

-300.0 to 750.0ºF

0.0 to 400.0ºC

-200.0 to 1000.0ºF

W

0.0 to 2300.0ºC

32 to 4200ºF

±0.2% of instrument range ±1 digit 

(Note 2)  

Platinel 2

0.0 to 1390.0ºC

32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit  

PR20-40

0.0 to 1900.0ºC

32 to 3400ºF

±0.5% of instrument range ±1 digit for 

800°C or more 

 

Accuracy is not guaranteed for less 

than 800°C.  

W97Re3-

W75Re25

0.0 to 2000.0ºC

32 to 3600ºF

±0.2% of instrument range ±1 digit  

RTD

JPt100

-200.0 to 500.0ºC

-300.0 to 1000.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-150.00 to  150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Pt100

-200.0 to 850.0ºC

-300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit 

(Note 1) 

-200.0 to 500.0ºC

-300.0 to 1000.0ºF

-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit

Standard signal

0.400 to 2.000 V

±0.1% of instrument range ±1 digit

1.000 to 5.000 V

4.00 to 20.00 mA

DC voltage/current

0.000 to 2.000 V

0.00 to 10.00 V

0.00 to 20.00 mA

-10.00 to 20.00 mV

0.0 to 100.0 mV

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power frequency at 50/60 Hz.

Note 1: ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range between -100 and 200°C.

Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988

•  Input sampling (control) period: Select from 50, 100, and 200 ms

  Burnout detection:

Functions at TC, RTD, and standard signal.

Upscale, downscale, and off can be specified.

For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4

 

mA or less.

•  Input bias current: 0.05 µA (for TC or RTD)

•  Measured current (RTD): About 0.16 mA

•  Input resistance:

TC or mV input: 1 MΩ or more

V input: About 1 MΩ

mA input: About 250 Ω

•  Allowable signal source resistance:

TC or mV input: 250 Ω or less

Effects of signal source resistance: 0.1 µV/Ω or less

DC voltage input: 2 kΩ or less

Effects of signal source resistance: About 0.01%/100 Ω

•  Allowable wiring resistance:

RTD input: Max. 150 Ω/wire  (The conductor resistance between the three wires 

shall be equal.)

Wiring resistance effect: ±0.1ºC/10 Ω

•  Allowable input voltage/current:

TC, mV, mA and RTD input: ±10 V DC

V input: ±20 V DC

mA input: ±40 mA

•  Noise rejection ratio:

Normal mode: 40 dB or more (at 50/60 Hz)

Common mode: 120 dB or more (at 50/60 Hz) 

For 100-240 V AC, the power frequency can be set manually. Automatic detection 

is also available.

For 24 V AC/DC, the power frequency can be set manually.

•  Reference junction compensation error:

±1.0ºC (15 to 35ºC), ±1.5ºC (-10 to 15ºC and 35 to 50ºC)

•  Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD

● Auxiliary Analog Input

• 

Use: Remote setpoint setting, external compensating input, auxiliary input for computation, etc.

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type, instrument range, and measurement accuracy: See the table below.

Input Type

Instrument Range

Accuracy

Standard signal

0.400 to 2.000 V

±0.2% of instrument range ±1 digit

1.000 to 5.000 V

±0.1% of instrument range ±1 digit

DC voltage

0.000 to 2.000 V

±0.2% of instrument range ±1 digit

0.00 to 10.00 V

±0.1% of instrument range ±1 digit

DC voltage 

for high-input 

impedance

0.000 to 1.250 V

±0.1% of instrument range ±1 digit

•  Input sampling (control) period: Same as the standard-equipped universal input

•  Input resistance: About 1 MΩ

However, 10 MΩ or more for DC voltage for high-input impedance range.

•  Burnout detection: Functions at standard signal

Burnout is determined to have occurred if it is 0.1 V or less.

● Universal Input (Option code: /U1)

  Number of inputs: See the table of Model and Suffix Codes.

•  Input type, instrument range, and measurement accuracy: Same as the standard-

equipped universal input except the table below.

Input Type 

Instrument Range

Accuracy

°C

°F 

4-wire RTD

JPt100

-200.0 to 500.0°C

 -300.0 to 1000.0°F  ±0.5°C ±1 digit

-150.00 to 150.00°C  -200.0 to 300.0°F  ±0.2°C ±1 digit

Pt100

-200.0 to 850.0°C

 -300.0 to 1560.0°F  ±0.1% of instrument range ±1 

digit (Note 1)

-200.0 to 500.0°C

 -300.0 to 1000.0°F  ±0.5°C ±1 digit

-150.00 to 150.00°C  -200.0 to 300.0°F  ±0.2°C ±1 digit

Note 1

: ±0.5°C ±1 digit in the range between -200.0 and 500.0°C/-300.0 and 1000.0°F.

•  Input sampling (control) period: Same as the standard-equipped universal input.

•  Burnout detection: Same as the standard-equipped universal input.

  Contact Input Specifications

•  Number of inputs: See the table of Model and Suffix Codes.

•  Input type: No-voltage contact input or transistor contact input

•  Input contact rating: 12 V DC, 10 mA or more

Use a contact with a minimum on-current of 1 mA or less.

•  ON/OFF detection:

No-voltage contact input:

Contact resistance of 1 kΩ or less is determined as “ON” and contact

resistance of 50 kΩ or more as “OFF.”

Transistor contact input:

Input voltage of 2 V or less is determined as “ON” and leakage current must not 

exceed 100 µA when “OFF.”

•  Minimum status detection hold time: Control 50 ms

•  Use: SP switch, operation mode switch, and event input

  Analog Output Specifications

•  Number of outputs:

Control output: 1

Cooling-side control output of Heating/cooling type: 1

•  Output type: Current output or voltage pulse output

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less

•  Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)

The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

and power frequency at 50/60 Hz.

•  Voltage pulse output:

Use: Time proportional output

On-voltage: 12 V or more/load resistance of 600 Ω or more

Off-voltage: 0.1 V DC or less

Time resolution: 10 ms or 0.1% of output, whichever is larger

  Retransmission Output Specifications

•  Number of outputs: Retransmission output; 1, shared with 15 V DC loop power supply.

•  Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less

•  Current output accuracy (conversion accuracy from PV display on the set scale): 

±0.1% of span (±5% of span for 1 mA or less)

  The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 

  and power frequency at 50/60 Hz.

  This is not conversion accuracy through input and output but the performance of 

transmission output itself.

  15 V DC Loop Power Supply Specifications

(Shared with retransmission output)

•  Power supply: 14.5 to 18.0 V DC

•  Maximum supply current: About 21 mA (with short-circuit current limiting circuit)

  Step Response Time Specifications

Within 500 ms (when the control period is 50 ms or 100 ms)

Within 1 s (when the control period is 200 ms)

(63% of analog output response time when a step change of 10 to 90% of input span is applied)

  Relay Contact Output Specifications

•  Contact type and number of outputs:

Control output: contact point 1c; 1 point

Cooling-side control output of Heating/cooling type: contact point 1c; 1 point 

(forUT55A only)

For UT52A, contact point 1a; 2 points for both heating and cooling sides

Alarm output: contact point 1a; 3 points (common is independent)

•  Contact rating:

Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load)

Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load) 

(for UT52A only)

Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load)

•  Use: Time proportional output, alarm output, FAIL output, etc.

•  Time resolution of control output: 10 ms or 0.1% of output, whichever is larger

Note:  The control output should always be used with a load of 10 mA or more.

 

The alarm output should always be used with a load of 1 mA or more.

  Triac Output Specifications

•  Contact type and number of output: zero cross; 1 point

Load voltage: 75 to 250 VAC

Allowable load current: 0.8 A when the ambient temperature is 20°C, 0.3 A when the 

ambient temperature is 50°C.

•  Minimum load current: 20 mA (*)

*: If there is a risk of surge current, connect a current-limiting reactor, a current-limiting fuse or a 

breaker in series to the load power supply.

•  Use: Time proportional output, Alarm output

•  Time resolution of control output: 1/commercial frequency (s) or 0.1% of output, 

whichever is larger.

  Transistor Contact Output Specifications

•  Number of outputs: See the table of Model and Suffix Codes.

•  Output type: Open collector (SINK current)

•  Output contact rating: Max. 24 V DC, 50 mA

•  Output time resolution: Min. 50 ms

•  Use: Alarm output, FAIL output, etc.

  Position Proportional Output Specifications

•  Position signal input:

Slide resistance: 100 Ω to 2.5 kΩ of total resistance

100% side and slide line: with disconnection detection

0% side: without disconnection detection

Current input: 4 to 20 mA (with disconnection detection)

•  Sampling period: 50 ms

•  Measurement resolution: 0.1% of input span

•  Position proportional relay output:

UT55A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)

UT52A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)

Note: This should always be used with a load of 10 mA or more.

  Heater Break Alarm Specifications

•  Number of inputs: 2

•  Number of outputs: 2 (transistor contact output)

•  Use: Measures the heater current using an external current transformer (CT) and 

generates a heater break alarm when the measured value is less than the break 

detection value.

•  Current transformer input resistance: About 9.4 Ω

• 

Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)

•  Heater current setting range: OFF, 0.1 to 300.0 Arms

Heater current measured value display range: 0.0 to 360.0 Arms

Note: The CT ratio can be set. CT ratio setting range: 1 to 3300

•  Recommended CT: CT from U.R.D., Ltd.

CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms

CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms

•  Heater current measurement period: 200 ms

•  Heater current measurement accuracy: ±5% of current transformer input range 

span ± 1digit (CT error is not included.)

• 

Heater current detection resolution: Within 1/250 of current transformer input range span

•  Break detection On-time: Min. 0.2 second (for time proportional output)

  24 V DC Loop Power Supply Specifications

•  Use: Power is supplied to a 2-wire transmitter.

•  Power supply: 21.6 to 28.0 V DC

•  Rated current: 4 to 20 mA DC

•  Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)

■  Safety and EMC Standards

•  Safety: 

 

Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-2-201 (CE), IEC/EN 61010-2-030 

(CE), approved by CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL 61010-1.

  Installation category: II

  Pollution degree: 2

  Measurement category: I (CAT I) (UL, CSA)

  

 

    

O (Other) (CE)

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: