background image

IM 05P01C31-15EN  page 1/12

Contents

1.  Safety Precautions

2.  Model and Suffix Codes

3.  How to Install

4.  Hardware Specifications

5.  How to Connect Wires

6.  Terminal Wiring Diagrams

Introduction

Thank you for purchasing the UT55A, UT52A Digital Indicating Controller.

This operation guide describes the basic operations related to the single-loop control 

function of the UT55A and UT52A. The guide should be provided to the end user of 

this product.

Be sure to read this operation guide before using the product in order to ensure 

correct operation. For details of each function, refer to User’s manual.

Before using the product, refer to the table of Model and Suffix Codes to make sure 

that the delivered product is consistent with the model and suffix codes you ordered. 

Also make sure that the following items are included in the package.

• Digital Indicating Controller (the model you ordered)

 ..............................

x1

• Set of Brackets ........................................................................................

x1

• Terminal Cover (L4502XP for UT55A /L4502XQ for UT52A)

 ..................

x1

• Unit Label (L4502VZ)

 ..............................................................................

x1

• Tag Label (L4502VE) (Only when ordered.)

 ............................................

x1

Target Readers

This guide is intended for the following personnel;

•  Engineers responsible for installation, wiring, and maintenance of the equipment.

•  Personnel responsible for normal daily operation of the equipment.

1.  Safety Precautions

The following symbol is used on the instrument. It indicates the possibility of injury 

to the user or damage to the instrument, and signifies that the user must refer to the 

operation guide or user’s manual for special instructions. The same symbol is used 

in the operation guide and user’s manual on pages that the user needs to refer to, 

together with the term “WARNING” or “CAUTION.”

WARNING 

Calls attention to actions or conditions that could cause serious 

or fatal injury to the user, and indicates precautions that should be 

taken to prevent such occurrences.

CAUTION

Calls attention to actions or conditions that could cause injury to 

the user or damage to the instrument or property and indicates pre-

cautions that should be taken to prevent such occurrences.

AC

AC/DC

 

The equipment wholly protected by double insulation or reinforced insulation.

  

Functional grounding terminals 

   

(Do not use this terminal as a protective grounding terminal).

Note

Identifies important information required to operate the instrument.

  Warning and Disclaimer

(1) YOKOGAWA makes no warranties regarding the product except those stated in 

the WARRANTY that is provided separately.

(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 

any person or entity for any loss or damage, direct or indirect, arising from the 

use of the product or from any unpredictable defect of the product.

  Safety, Protection, and Modification of the Product

(1) In order to protect the system controlled by this product and the product itself, 

and to ensure safe operation, observe the safety precautions described in the 

operation guide. Use of the instrument in a manner not prescribed herein may 

compromise the product's functions and the protection features inherent in the 

device. We assume no liability for safety, or responsibility for the product's quality, 

performance or functionality should users fail to observe these instructions when 

operating the product.

(2) Installation  of  protection  and/or  safety  circuits  with  respect  to  a  lightning 

protector; protective equipment for the system controlled by the product and the 

product itself; foolproof or fail-safe design of a process or line using the system 

controlled by the product or the product itself; and/or the design and installation 

of other protective and safety circuits are to be appropriately implemented as the 

customer deems necessary.

(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts 

or consumables.

(4) This product is not designed or manufactured to be used in critical applications 

that directly affect or threaten human lives. Such applications include nuclear 

power  equipment,  devices  using  radioactivity,  railway  facilities,  aviation 

equipment, air navigation facilities, aviation facilities, and medical equipment. 

If so used, it is the user’s responsibility to include in the system additional 

equipment and devices that ensure personnel safety.

(5) Modification of the product is strictly prohibited.

(6) This product is intended to be handled by skilled/trained personnel for electric devices.

(7) This product is UL Recognized Component. In order to comply with UL standards, 

end-products are necessary to be designed by those who have knowledge of the 

requirements.

WARNING 

Power Supply

  Ensure that the instrument’s supply voltage matches the voltage 

of the power supply before turning ON the power.

l

  Do Not Use in an Explosive Atmosphere

  Do not operate the instrument in locations with combustible 

or explosive gases or steam. Operation in such environments 

constitutes an extreme safety hazard. Use of the instrument in 

environments with high concentrations of corrosive gas (H

2

S, 

SO

X

, etc.) for extended periods of time may cause a failure.

l

  Do Not Remove Internal Unit

  The internal unit should not be removed by anyone other than 

YOKOGAWA's service personnel. There are dangerous high voltage 

parts inside. Additionally, do not replace the fuse by yourself.

l

  Damage to the Protective Construction

  Operation of the instrument in a manner not specified in the 

operation guide may damage its protective construction.

CAUTION

This instrument is an EMC class A product. In a domestic environ-

ment this product may cause radio interference in which case the 

user needs to take adequate measures.

2.  Model and Suffix Codes

 UT55A «Detailed Code Model»

Model

Suffix code

Option

code

Description

UT55A

Digital Indicating Controller (Power supply: 100-240 V 

AC) (provided with 3 DIs and 3 DOs)

Fixed code

-NNN

Always "-NNN” (for detailed code model)

Display language (*1)

-1

English (Default. Can be switched to other language by the setting.)

-2

German (Default. Can be switched to other language by the setting.)

-3

French (Default. Can be switched to other language by the setting.)

-4

Spanish (Default. Can be switched to other language by the setting.)

Case color

0

White (Light gray)

1

Black (Light charcoal gray)

Output 1 (*2) (*3)

-A

Analog output (current/voltage pulse)

-R

Relay output (c-contact)

-U

Universal output (current/voltage pulse/relay)

-T

Triac output

-P

Position proportional output

Output 2 (*2) (*3)

A

Analog output (current/voltage pulse)

R

Relay output (c-contact)

U

Universal output (current/voltage pulse/relay)

T

Triac output

N

None

Retransmission output

/RT

Retransmission output or 15 V DC power supply

Heater break alarm (*3)

/HA

Heater break alarm

E1 terminal area (*4)

/R1

Remote (1 additional aux. analog) input and 1 additional DI

/U1

1 additional universal input (TC/RTD/DCV/mA)

/X1

5 additional DIs

/Y1

5 additional DOs

/W1

2 additional DIs and 2 additional DOs

E2 terminal area (*4)

/A2

1 additional aux. analog input and 1 additional DI

/X2

5 additional DIs

/Y2

5 additional DOs

/W2

2 additional DIs and 2 additional DOs

E3 terminal area (*4) (*5)

/CH3

RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)

/CC3

CC-Link communication (with Modbus master function)

/PD3

PROFIBUS-DP communication (with Modbus master function)

/DN3

DeviceNet communication (with Modbus master function)

/ET3

Ethernet communication (with serial gateway function)

/X3

5 additional DIs

/Y3

5 additional DOs

/W3

2 additional DIs and 2 additional DOs

E4 terminal area (*4) (*5)

/A4

1 additional aux. analog input and 1 additional DI

/C4

RS485 communication (Max. 19.2 kbps, 2-wire/4-wire)

/L4

24 V DC loop power supply

/AC4

1 additional aux. analog input, 1 additional DI, and 

RS485 communication (Max.19.2 kbps, 2-wire)

/LC4

24 V DC loop power supply and RS485 communication 

(Max.19.2 kbps, 2-wire)

/X4

5 additional DIs

/Y4

5 additional DOs

/W4

2 additional DIs and 2 additional DOs

Power supply

/DC

Power supply 24 V AC/DC

Additional treatment (*6)

/CT

Coating

*1: 

English, German, French, and Spanish are available for the guide display.

*2: 

For heating/cooling output, both Output 1 and Output 2 should be specified. Not available 

when Output 2 is “N”. For position proportional output, specify “-P” for Output 1 and “N” for Output 2. 

*3: 

The /HA option can be specified only when the code for Output 1 and 2 is “-AN”, “-RN”, “-UN” or “-TN.” 

*4: 

Only one option is available for each terminal area of E1 to E4.

*5: 

The /L4 and /LC4 options for E4 terminal area can be specified only when the E3 terminal 

area option is not specified or specified any of /CH3, /X3, /Y3 or /W3.

*6: 

When the /CT option is specified, the UT55A does not conform to the safety standards (UL 

and CSA) and CE marking (Products with /CT option are not intended for EEA-market).

 UT52A «Detailed Code Model»

Model

Suffix code

Option

code

Description

UT52A

Digital Indicating Controller (Power supply: 100-240 V 

AC) (provided with 3 DIs and 3 DOs)

Fixed code

-NNN

Always "-NNN” (for detailed code model)

Display language (*1)

-1

English (Default. Can be switched to other language by the setting.)

-2

German (Default. Can be switched to other language by the setting.)

-3

French (Default. Can be switched to other language by the setting.)

-4

Spanish (Default. Can be switched to other language by the setting.)

Case color

0

White (Light gray)

1

Black (Light charcoal gray)

Output 1 (*2) (*3) (*4)

-A

Analog output (current/voltage pulse)

-R

Relay output (c-contact)

-U

Universal output (current/voltage pulse/relay)

-T

Triac output

-P

Position proportional output

Output 2 (*2) (*3) (*4) (*5) 

A

Analog output (current/voltage pulse)

R

Relay output (a-contact)

U

Universal output (current/voltage pulse/relay)

N

None

Retransmission output

/RT

Retransmission output or 15 V DC power supply

Heater break alarm (*3)

/HA

Heater break alarm

E1 terminal area (*5) (*6)

/R1

Remote (1 additional aux. analog) input and 1 additional DI

/U1

1 additional universal input (TC/RTD/DCV/mA)

/L1

24 V DC loop power supply

/CH1

RS485 communication (Max. 38.4 kbps, 2-wire/4-wire)

/RCH1

Remote (1 additional aux. analog) input, 1 additional DI, 

and RS485 communication (Max.38.4 kbps, 2-wire)

/LCH1

24 V DC loop power supply and RS485 communication 

(Max. 38.4 kbps, 2-wire)

/X1

5 additional DIs

/Y1

5 additional DOs

/W1

2 additional DIs and 2 additional DOs

Power supply

/DC

Power supply 24 V AC/DC

Additional treatment (*7)

/CT

Coating

*1: 

English, German, French, and Spanish are available for the guide display.

*2: 

For heating/cooling output, both Output 1 and Output 2 should be specified. Not available 

when Output 2 is “N”. For position proportional output, specify “-P” for Output 1 and “N” for Output 2. 

*3: 

The /HA option can be specified only when the code for Output 1 and 2 is “-AN”, “-RN”, “-UN” or “-TN.

*4: 

When the code for Output 1 is "-R" or "-U" and Output 2 is "R" or "U", Output 1 is changed 

from the contact point c to the contact point a.

 

When the code for Output 1 is specified to "-T", only "A" or "N" is available for Output 2.

*5: 

The /L1 or /LCH option can be specified only when the code for Output 2 is “N.”

*6: 

Only one option is available for E1 terminal area.

*7: 

When the /CT option is specified, the UT52A does not conform to the safety standards (UL 

and CSA) and CE marking (Products with /CT option are not intended for EEA-market).

  Accessories (sold separately)

The following is an accessory sold separately.

•  LL50A Parameter Setting Software

Model

Suffix code

Description

LL50A

-00

Parameter Setting Software

•  External Precision Resistor 

Model

Suffix code

Description

X010

See the General Specifications (*)

Resistance Module

 

*: Necessary to input the current signal to the voltage input terminal.

•  Terminal Cover

  For UT55A: Model UTAP001; For UT52A: Model UTAP002

• Manuals

 

* Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/

• Brackets

 

Part number: L4502TP (2 pcs for upper and lower sides)

•  Operation Guide for Single-loop Control (this document) x6 (A3 size)

 

(Installation and Wiring, Initial Settings, Operations, and Parameters)

3.  How to Install

  Installation Location

The  instrument  should  be  installed  in  indoor  locations  meeting  the  following 

conditions:

•  Instrumented panel

  This instrument is designed to be mounted in an instrumented panel. Mount the 

instrument in a location where its terminals will not inadvertently be touched.

•  Well ventilated locations

  Mount the instrument in well ventilated locations to prevent the instrument’s 

internal temperature from rising. 

  However,  make  sure  that  the  terminal  portions  are  not  exposed  to  wind. 

Exposure to wind may cause the temperature sensor accuracy to deteriorate. To 

mount multiple indicating controllers, see the external dimensions/panel cutout 

dimensions which follow. If mounting other instruments adjacent to the instrument, 

comply with these panel cutout dimensions to provide sufficient clearance between 

the instruments.

•  Locations with little mechanical vibration

  Install the instrument in a location subject to little mechanical vibration.

•  Horizontal location

  Mount the instrument horizontally and ensure that it is level, with no inclination to 

the right or left.

Front panel

of controller

Keep this angle

within 30°

Rear of

controller

30°

Note

If the instrument is moved from a location with low temperature and low humidity 

to a place with high temperature and high humidity, or if the temperature changes 

rapidly, condensation will result. Moreover, in the case of thermocouple inputs, 

measurement errors will result. To avoid such a situation, leave the instrument in the 

new environment under ambient conditions for more than 1 hour prior to using it.

Do not mount the instrument in the following locations:

• Outdoors

•  Locations subject to direct sunlight or close to a heater

  Install the instrument in a location with stable temperatures that remain close to an 

average temperature of 23°C. Do not mount it in locations subject to direct sunlight 

or close to a heater. Doing so adversely affects the instrument.

• Locations with substantial amounts of oily fumes, steam, moisture, dust, or 

corrosive gases

  The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely 

affects the instrument. Do not mount the instrument in locations subject to any of 

these substances.

•  Areas near electromagnetic field generating sources

  Do not place magnets or tools that generate magnetism near the instrument. If the 

instrument is used in locations close to a strong electromagnetic field generating 

source, the magnetic field may cause measurement errors.

•  Locations where the display is difficult to see

  The instrument uses an LCD for the display unit, and this can be difficult to see 

from extremely oblique angles. Mount the instrument in a location where it can be 

seen as much as possible from the front.

•  Areas close to flammable articles

  Absolutely  do  not  place  the  instrument  directly 

on  flammable  surfaces.  If  such  a  circumstance  is 

unavoidable and the instrument must be placed close 

to a flammable item, provide a shield for it made of 1.43 

mm thick plated steel or 1.6 mm thick unplated steel 

with a space of at least 150 mm between it and the 

instrument on the top, bottom, and sides.

•  Areas subject to being splashed with water

WARNING 

Be sure to turn OFF the power supply to the controller before in-

stalling it on the panel to avoid an electric shock.

www.yokogawa.com/ns

YOKOGAWA ELECTRIC CORPORATION

Network Solutions Business Division

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN

YOKOGAWA CORPORATION OF AMERICA

Head office and for product sales

2 Dart Road, Newnan, Georgia 30265, USA

YOKOGAWA EUROPE B.V.

Headquarters

Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS

All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation

150 mm

150 mm

150 mm

150 mm

Operation

Guide

IM 05P01C31-15EN

UT55A, UT52A

Digital Indicating Controller 

(Panel Mounting Type)

Operation Guide for Single-loop Control

This operation guide describes installation, wiring, and other tasks required to make the 

controller ready for operation.

6th Edition : Mar. 2016

Installation and Wiring

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Detailed Code Model»

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: