IM 05P01C31-15EN   page 11/12

(SH)

Maximum value of RSP 

remote input scale

-19999 to 30000, (SL<SH),

 

| SH - SL | ≤ 30000

Depends 

on the 

input type

EASY

(SL)

Minimum value of RSP 

remote input scale

(BSL)

RSP remote input burn-

out action

OFF: Disable

UP: Upscale

DOWN: Downscale

Depends 

on the 

input type

STD

(RTD.S)

RTD wiring system

3-W: 3-wire system

4-W: 4-wire system

(The LL50A Parameter Setting Soft-

ware is required to use RSP terminals 

input as PV.)

3-W

 AIN2/AIN4 Aux. Analog Input Setting Parameter  

(E2/E4-terminal Area)

Menu symbol: 

 (AIN2)

 

 (AIN4)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(IN)

AIN2/AIN4 aux. analog 

input type

0.4-2 V: 0.400 to 2.000 V

1-5 V: 1.000 to 5.000 V

0-2 V: 0.000 to 2.000 V

0-10 V: 0.00 to 10.00 V

0-125: 0.000 to 1.250 V

1-5 V

EASY

(UNIT)

AIN2/AIN4 aux. analog 

input unit

-: No unit

C: Degree Celsius

-: No unit

- -: No unit

- - -: No unit

F: Degree Fahrenheit

C

(RH)

Maximum value of AIN2/

AIN4 aux. analog input 

range

Depends on the input type.

Set the range of a voltage signal that 

is applied.

The scale across which the voltage 

signal is actually controlled should be 

set using the maximum value of input 

scale (SH) and minimum value of 

input scale (SL).

(Input is always 0% when RL = RH.)

Depends 

on the 

input type

(RL)

Minimum value of AIN2/

AIN4 aux. analog input 

range

Depends 

on the 

input type

(SDP)

AIN2/AIN4 aux. analog 

input scale decimal point 

position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(SH)

Maximum value of AIN2/

AIN4 aux. analog input 

scale

-19999 to 30000, (SL<SH),

| SH - SL | ≤ 30000

Depends 

on the 

input type

(SL)

Minimum value of AIN2/

AIN4 aux. analog input 

scale

Depends 

on the 

input type

(BSL)

AIN2/AIN4 aux. analog 

input burnout action

OFF: Disable

UP: Upscale

DOWN: Downscale

Depends 

on the 

input type

STD

 Input Range, SP Limiter Setting Parameter

Menu symbol: 

 (MPV)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(P.UNI)

Control PV input unit

-: No unit

C: Degree Celsius

-: No unit

- -: No unit

- - -: No unit

F: Degree Fahrenheit

Same 

as PV 

input 

unit

STD

(P.DP)

Control PV input decimal 

point position

0: No decimal place

1: One decimal place

2: Two decimal places

3: Three decimal places

4: Four decimal places

Depends 

on the 

input type

(P.RH)

Maximum value of 

control PV input range

-19999 to 30000, (P.RL<P.RH),

| P.RH - P.RL | ≤ 30000

Depends 

on the 

input type

(P.RL)

Minimum value of control 

PV input range

Depends 

on the 

input type

(SPH)

SP high limit

0.0 to 100.0% of PV input range (EU), 

(SPL<SPH)

100.0 % 

of PV 

input 

range

(SPL)

SP low limit

0.0 % 

of PV 

input 

range

 

Output Setting Parameter

Menu symbol: 

 (OUT)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(OT)

Output type selection

Upper two 

digits

Lower two 

digits

Control output or Heating-side control 

output (Lower two digits)

00: OFF

01: OUT terminals (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay/triac)

04: OUT2 terminals (voltage pulse)

05: OUT2 terminals (current)

06: OUT2 terminals (relay/triac)

Cooling-side control output (Upper 

two digits)

00: OFF

01: OUT terminals (voltage pulse)

02: OUT terminals (current)

03: OUT terminals (relay/triac)

04: OUT2 terminals (voltage pulse)

05: OUT2 terminals (current)

06: OUT2 terminals (relay/triac)

Standard 

type: 

00.03

 

Heating/

cooling 

type: 

06.03

EASY

(CT)

Control output cycle time

 

Heating-side control 

output cycle time (in 

Heating/cooling control)

0.5 to 1000.0 s

30.0 s

EASY

(CTc)

Cooling-side control 

output cycle time

(V.AT)

Automatic valve position 

adjustment

OFF: Stop automatic adjustment

ON: Start automatic adjustment

OFF

(V.RS)

Valve position setting 

reset

Setting V.RS to ON resets the valve 

adjustment settings and causes the 

indication “V.RS” to blink.

OFF

(V.L)

Fully-closed valve posi-

tion setting

Pressing the SET/ENTER key with valve 

position set to the fully-closed position 

by Down arrow key causes the adjusted 

value to be stored. When V.L adjustment 

is complete, V.L stops blinking.

-

(V.H)

Fully-opened valve posi-

tion setting

Pressing the SET/ENTER key with valve 

position set to the fully-opened position by 

Up arrow key causes the adjusted value 

to be stored. When V.H adjustment is 

complete, V.H stops blinking

-

(TR.T)

Valve traveling time

5 to 300 s

60 s

STD

(V.MOD)

Valve adjusting mode

0: Valve position feedback type

1: Valve position feedback type

 

(moves to the estimating type if a 

feedback input error or break occurs.)

2: Valve position estimating type 

0

(RTS)

Retransmission output 

type of RET

OFF: Disable

PV1: PV

SP1: SP

OUT1: OUT (Valve opening: 0 to 100 

% in Position proportional control)

LPS: 15 V DC loop power supply

PV2: Loop-2 PV

SP2: Loop-2 SP

OUT2: Loop-2 OUT

TSP1: Target SP

HOUT1: Heating-side OUT

COUT1: Cooling-side OUT

MV1: Position proportional output 

(internal computed value)

TSP2: Loop-2 target SP

HOUT2: Loop-2 heating-side OUT

COUT2: Loop-2 cooling-side OUT

MV2: Loop-2 position proportional 

output (internal computed value)

PV: PV terminals analog input

RSP: RSP terminals analog input

AIN2: AIN2 terminals analog input

AIN4: AIN4 terminals analog input

* Loop-2 setting values are unavailable

 

in Single-loop control.

PV1

EASY

(RTH)

Maximum value of 

retransmission output 

scale of RET

When RTS = PV1, SP1, PV2, SP2, TSP1, 

TSP2, PV, RSP, AIN2, or AIN4, RTL + 1 

digit to 30000 -19999 to RTH - 1 digit 

Decimal point position:

When RTS=PV1, SP1, or TSP1, decimal 

point position is same as that of PV input.

When RTS=PV2, SP2, or TSP2, decimal 

point position is same as that of RSP input.

When RTS=PV, decimal point position  is 

same as that of PV input scale.

When RTS=RSP, decimal point position 

is same as that of RSP input scale.

When RTS=AIN2, decimal point position 

is same as that of AIN2 scale.

When RTS=AIN4, decimal point position 

is same as that of AIN4 scale.

100 % 

of PV 

input 

range

STD

(RTL)

Minimum value of 

retransmission output 

scale of RET 

0 % 

of PV 

input 

range

(O1RS)

Retransmission output 

type of OUT current output Same as RTS

OFF

STD

(O1RH)

Maximum value of 

retransmission output 

scale of OUT current 

output

When O1RS = PV1, SP1, PV2, SP2, 

TSP1, TSP2, PV, RSP, AIN2, or AIN4, O1RL 

+ 1 digit to 30000 -19999 to O1RH - 1 digit

Decimal point position:

When O1RS=PV1, SP1, or TSP1, decimal 

point position is same as that of PV input.

When O1RS =PV2, SP2, or TSP2, decimal 

point position is same as that of RSP input.

When O1RS =PV, decimal point position is 

same as that of PV input scale.

When O1RS =RSP, decimal point position 

is same as that of RSP input scale.

When O1RS =AIN2, decimal point position 

is same as that of AIN2 scale.

When O1RS =AIN4, decimal point position 

is same as that of AIN4 scale

-

STD

(O1RL)

Minimum value of 

retransmission output 

scale of OUT current 

output

-

(O2RS)

Retransmission output type 

of OUT2 current output

Same as RTS

OFF

STD

(O2RH)

Maximum value of 

retransmission output 

scale of OUT2 current 

output

When O2RS = PV1, SP1, PV2, SP2, 

TSP1, TSP2, PV, RSP, AIN2, or AIN4, O2RL 

+ 1 digit to 30000 -19999 to O2RH - 1 digit

Decimal point position:

When O2RS=PV1, SP1, or TSP1, decimal 

point position is same as that of PV input.

When O2RS =PV2, SP2, or TSP2, decimal 

point position is same as that of RSP input.

When O2RS =PV, decimal point position is 

same as that of PV input scale.

When O2RS =RSP, decimal point position 

is same as that of RSP input scale.

When O2RS =AIN2, decimal point position 

is same as that of AIN2 scale.

When O2RS =AIN4, decimal point position 

is same as that of AIN4 scale.

-

(O2RL)

Minimum value of 

retransmission output 

scale of OUT2 current 

output

-

(OU.A)

OUT current output 

range

4-20: 4 to 20 mA

0-20: 0 to 20 mA

20-4: 20 to 4 mA

20-0: 20 to 0 mA

4-20

STD

(OU2.A)

OUT2 current output 

range

4-20

(RET.A)

RET current output 

range

4-20

 Heater Break Alarm Setting Parameter

Menu symbol: 

 (HBA)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(HB1.S)

Heater break alarm-1 

function selection

0: Heater current measurement 

1: Heater break alarm

1

EASY

(HB2.S)

Heater break alarm-2 

function selection

1

(HB1)

Heater break alarm-1 

current setpoint

OFF, 0.1 to 300.0 Arms

OFF

(HB2)

Heater break alarm-2 

current setpoint

OFF

(CT1.T)

CT1 

coil winding number ratio

1 to 3300

800

(CT2.T)

CT2 

coil winding number ratio

800

(HDN1)

Heater break alarm-1 

On-delay timer

0.00 to 99.59 (m.s)

0.00

STD

(HDN2)

Heater break alarm-2 

On-delay timer

0.00

In cases where the current transformers manufactured by U.R.D. Co., Ltd are used, set 

the following value for the coil winding number ratio.

CTL-6-S-H: 800

CTL-12L-30: 3000

 RS-485 Communication Setting Parameter (E1/E3/E4-terminal Area)

Menu symbol: 

 (R485)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(PSL)

Protocol selection

PCL: PC link communication

PCLSM: PC link communication (with        

checksum)

LADR: Ladder communication

CO-M: Coordinated master station

CO-S: Coordinated slave station

MBASC: Modbus (ASCII)

MBRTU: Modbus (RTU)

CO-S1: Coordinated slave station

 

 

(Loop-1 mode)

CO-S2: Coordinated slave station

 

 

(Loop-2 mode)

P-P: Peer-to-peer communication

MBRTU

EASY

(BPS)

Baud rate

600: 600 bps

1200: 1200 bps

2400: 2400 bps

4800: 4800 bps

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

* The baud rate for RS-485 is up to 

19.2 k bps in E4-terminal area.

19200

(PRI)

Parity

NONE: None

EVEN: Even

ODD: Odd

EVEN

(STP)

Stop bit

1: 1 bit, 2: 2 bits

1

(DLN)

Data length

7: 7 bits, 8: 8 bits

8

(ADR)

Address

1 to 99

1

■ 

Ethernet Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (ETHR)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(HSR)

High-speed response mode OFF, 1 to 8

1

EASY

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(PRI)

Parity

NONE: None

 

EVEN: Even

 

ODD: Odd

EVEN

EASY

 to 

(IP1 to IP4)

IP address 1 to 4

0 to 255

Initial value: (IP1).(IP2).(IP3).(IP4)=

 

(192).(168).(1).(1)

See left

Table 

below

 to 

(SM1 to SM4)

Subnet mask 1 to 4

0 to 255

Initial value: (SM1).(SM2).(SM3).(SM4)

=(255).(255).(255).(0)

See left

Table 

below

EASY

 to 

(DG1 to DG4)

Default gateway 1 to 4

0 to 255

Initial value: (DG1).(DG2).(DG3).(DG4)=

(0).(0).(0).(0)

See left

Table 

below

(PRT)

Port number

502, 1024 to 65535

502

(IPAR)

IP access restriction

OFF: Disable, ON: Enable

OFF

 to 

,

 to 

(1.IP1 to 1.IP4,

2.IP1 to 2.IP4)

Permitted IP address 1-1 

to 1-4

Permitted IP address 2-1 

to 2-4

0 to 255

Initial value: 

 

(1.IP1).(1.IP2).(1.IP3).(1.IP4)=

 

(255).(255).(255).(255)

(2.IP1).(2.IP2).(2.IP3).(2.IP4)=

 

(255).(255).(255).(255)

See left

Table 

below

(ESW)

Ethernet setting switch

Setting this parameter to “ON” 

enables the Ethernet communication 

parameter settings. OFF, ON 

OFF

Use the following table to record Ethernet communication setting value.

Parameter

n=1

n=2

n=3

n=4

IPn

SMn

DGn

1.IPn
2.IPn

 PROFIBUS-DP Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (PROF)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

9.6K: 9.6k bps

19.2K: 19.2k bps

93.75K: 93.75k bps

187.5K: 187.5k bps

0.5M: 0.5M bps

1.5M: 1.5M bps

3M: 3M bps

6M: 6M bps

12M: 12M bps

AUTO

45.45K: 45.45k bps

AUTO

EASY

(ADR)

Address

0 to 125

3

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0 to 5

0

 DeviceNet  Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (DNET)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

125K: 125k bps

250K: 250k bps

500K: 500k bps

125K

EASY

(ADR)

Address

0 to 63

63

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

0 to 5

0

 CC-Link Communication Setting Parameter (E3-terminal Area)

Menu symbol: 

 (CC-L)

Parameter 

symbol

Name of Parameter

Setting Range

Initial 

value

User 

setting

Display 

level

(BR)

Baud rate

156K: 156k bps

625K: 625k bps

2.5K: 2.5k bps

5M: 5M bps

10M: 10M bps

10M

EASY

(ADR)

Address

1 to 64

3

(BPS)

Baud rate

9600: 9600 bps

19200: 19.2k bps

38400: 38.4k bps

38400

(FILE)

Profile number

UT55A: 0 to 7

(0, 1 and 6: Ver.1.10) (2 to 5 and 7: 

Ver.2.00)

UT52A: 0 to 3 and 6

(0, 1 and 6: Ver.1.10) (2 and 3: 

Ver.2.00)

0

Setup Parameters (Continued from page 10)

 

RSP Input Setting Parameter (E1-terminal Area) (Continued)

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: