IM 05P01C31-15EN page 12/12
■ Key Action Setting Parameter
Menu symbol:
(KEY)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(F1)
User function key-1 ac-
tion setting
OFF: Disable
A/M: AUTO/MAN switch
C/A/M: CAS/AUTO/MAN switch
R/L1: REM/LCL switch
R/L2: Loop-2 REM/LCL switch
S/R: STOP/RUN switch
CAS: Switch to CAS
AUTO: Switch to AUTO
MAN: Switch to MAN
REM1: Switch to REM
LCL1: Switch to LCL
REM2: Switch to Loop-2 REM
LCL2: Switch to Loop-2 LCL
STOP: Switch to STOP
RUN: Switch to RUN
AT: Auto-tuning
LTUP: LCD brightness UP
LTDN: LCD brightness DOWN
BRI: Adjust LCD brightness
LCD: LCD backlight ON/OFF switch
LAT: Latch release
PID: PID tuning switch
* Loop-2 setting values are
unavailable in Single-loop control.
OFF
EASY
(F2)
User function key-2 ac-
tion setting
OFF
(Fn)
User function key-n ac-
tion setting
PID
■ Display Function Setting Parameter
Menu symbol:
(DISP)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(DVB)
Deviation display band
Permits a change in the span of
deviation shown on the front-panel
deviation monitor.
Displayed only for UT55A.
0.0 to 100.0% of PV input range span (EUS).
1.0 %
of PV
input
range
span
STD
(PCMD)
Active color PV display
switch
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white,
Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF:
white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF:
red, Alarm ON: white)
6: PV limit (Within range: white, Out
of range: red)
7: PV limit (Within range: red, Out of
range: white)
8: SP deviation (Within deviation:
white, Out of deviation: red)
9: SP deviation (Within deviation: red,
Out of deviation: white)
10: Link to DI (ON: red, OFF: white)
0
EASY
(PCH)
PV color change high
limit
Set a display value when in PV limit
or SP deviation.
-19999 to 30000 (Set a value within
the input range.)
Decimal point position depends on
the input type.
0
(PCL)
PV color change low limit
0
(BAR1)
Upper bar-graph display
registration
0: Disable
1:OUT, Heating-side OUT, Internal value
in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6: Loop-2 OUT, Loop-2 heating-side OUT
7: Loop-2 cooling-side OUT
8: Loop-2 PV
9: Loop-2 SP
10: Loop-2 deviation
11 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
19: RSP terminals analog input
20: AIN2 terminals analog input
21: AIN4 terminals analog input
27: TSP
28: TSP deviation
29: Loop-2 TSP
30: Loop-2 TSP deviation
5
(Heating
/cooling
type: 1)
STD
(BAR2)
Lower bar-graph display
registration
1
(Heating
/cooling
type: 2)
(Posi-
tion
propor
-
tional
type:
17)
(BDV)
Bar-graph deviation
display band
0.0 to 100.0% of PV input range span
(EUS)
1.0 %
of PV
input
range
span
STD
(GUID)
Guide display ON/OFF
OFF: Nondisplay, ON: Display
ON
(ECO)
Economy mode
OFF: Disable
1: Economy mode ON (All indications
except PV display OFF)
2: Economy mode ON (All indications OFF)
3: Brightness 10 % (whole indication)
OFF
(BRI)
Brightness
(Dark) 1 to 5 (Bright)
3
EASY
(MLSD)
Least significant digital
mask of PV display
OFF: With least significant digit
ON: Without least significant digit
OFF
STD
(MKTP)
Method for least signifi-
cant digital mask of PV
display
0: Rounding, 1: Rounding-off
0
STD
■ SELECT Display Setting Parameter
Menu symbol:
(CSEL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
to
(CS1 to CS5)
SELECT Display-1 to -5
registration
Register the operation parameter
(except the Operation Mode) that is
frequently modified to display it in the
Operation Display.
OFF, 2301 to 5000, 6701 to 6710
For the setting range, see User’s Manual.
OFF
STD
Use the following table to record SELECT Display setting value.
Parameter
n=1
n=2
n=3
n=4
n=5
CSn
■ Key Lock Setting Parameter
Menu symbol:
(KLOC)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(COM.W)
Communication write
enable/disable
OFF: Enable, ON: Disable
OFF
STD
(DATA)
Front panel parameter
data (▼,▲) key lock
OFF: Unlock, ON: Lock
OFF
(A/M)
Front panel A/M key lock
OFF
■ DI Function Registration Parameter
Menu symbol:
(DI.SL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(A/M)
AUTO/MAN switch
Set an I relay number of contact
input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area
DI21: 5057, DI22: 5058, DI23: 5059,
DI24: 5060, DI25: 5061, DI26: 5062
E3-terminal area
DI31: 5073, DI32: 5074, DI33: 5075,
DI34: 5076, DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093, DI46: 5094
5025
STD
(R/L)
REMOTE/LOCAL switch
5046
(S/R)
STOP/RUN switch
5026
(CAS)
Switch to CAS
OFF
(AUTO)
Switch to AUTO
OFF
(MAN)
Switch to MAN
OFF
(REM)
Switch to REMOTE
OFF
(LCL)
Switch to LOCAL
OFF
(AT)
Auto-tuning START/STOP
switch
OFF
(LAT)
Latch release
OFF
(LCD)
LCD backlight ON/OFF
switch
OFF
(PVRW)
PV red/white switch
OFF
■ DI Function Numbering Parameter
Menu symbol:
(DI.NU)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(SP.B0)
Bit-0 of SP number
Set an I relay number of contact input.
Set “OFF” to disable the function.
Standard terminals
DI1: 5025, DI2: 5026, DI3: 5027
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
DI14: 5044, DI15: 5045, DI16: 5046
E2 -terminal area
DI21: 5057, DI22: 5058, DI23: 5059,
DI24: 5060, DI25: 5061, DI26: 5062
E3-terminal area
DI31: 5073, DI32: 5074, DI33: 5075,
DI34: 5076, DI35: 5077
E4-terminal area
DI41: 5089, DI42: 5090, DI43: 5091,
DI44: 5092, DI45: 5093, DI46: 5094
OFF
EASY
(SP.B1)
Bit-1 of SP number
OFF
(SP.B2)
Bit-2 of SP number
OFF
(SP.B3)
Bit-3 of SP number
OFF
(PN.B0)
Bit-0 of PID number
OFF
STD
(PN.B1)
Bit-1 of PID number
OFF
(PN.B2)
Bit-2 of PID number
OFF
(PN.B3)
Bit-3 of PID number
OFF
(MP.B0)
Bit-0 of manual preset
output number
OFF
(MP.B1)
Bit-1 of manual preset
output number
OFF
(MP.B2)
Bit-2 of manual preset
output number
OFF
(SP.BC)
Bit changing method of
SP number
0: Status switch 1
1: Status switch 2
0
STD
■ AL1-AL3 Function Registration Parameter
Menu symbol:
(ALM)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(AL1.S)
AL1 function selection
Set an I relay number. For the items
other than below, see Communication
User's Manual.
Ex.) Set the number 4353 for AL1.S
to use the alarm 1.
Set “OFF” to disable the function.
No function: OFF
Alarm 1: 4353, Alarm 2: 4354
Alarm 3: 4355, Alarm 4: 4357
Alarm 5: 4358, Alarm 6: 4359
Alarm 7: 4361, Alarm 8: 4362
AUTO (OFF) / MAN (ON) status: 4193
REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195
Output tracking (ON) switching signal: 4201
FAIL (Normally ON) output: 4256
4353
STD
(AL2.S)
AL2 function selection
4354
(AL3.S)
AL3 function selection
4355
(OR.S)
OUT relay function
selection
OFF
(OR2.S)
OUT2 relay function
selection
OFF
■ DO Setting Parameter (E1/E2/E3/E4-terminal Area)
Menu symbol:
(DO)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(DO1.S)
DO11/DO21/DO31/
DO41 function selection Same as AL1.S
Set “OFF” to disable the function.
Initial value:
DO11, DO12, DO13, DO14, DO15,
DO31, DO32, DO33, DO34, DO35,
DO41, DO42, DO43, DO44, DO45 =
OFF
DO21 = 4357, DO22 = 4358,
DO23 = 4359, DO24 = 4361,
DO25 = 4362
See left
Table
below
STD
(DO2.S)
DO12/DO22/DO32/
DO42 function selection
See left
(DO3.S)
DO13/DO23/DO33/
DO43 function selection
See left
(DO4.S)
DO14/DO24/DO34/
DO44 function selection
See left
(DO5.S)
DO15/DO25/DO35/
DO45 function selection
See left
Use the following table to record DO setting value.
Parameter
E1-terminal Area
E2-terminal Area
E3-terminal Area
E4-terminal Area
DO1.S
DO2.S
DO3.S
DO4.S
DO5.S
■ System Setting Parameter
Menu symbol:
(SYS)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(R.MD)
Restart mode
Set how the controller should recover from
a power failure of 5 seconds or more.
CONT: Continue action set before
power failure.
MAN: Start from MAN.
AUTO: Start from AUTO.
CONT
STD
(R.TM)
Restart timer
Set time between power on and the
instant where controller starts computa
-
tion. 0 to 10 s
0
(EPO)
Input error preset output
Set preset output value when the
input burnout or ADC error occurs.
Manual output is prioritized when
the input burnout occurs in MAN.
0: Preset output, 1: 0% output
2: 100% output
0
STD
(FREQ)
Power frequency
AUTO, 60: 60 Hz, 50: 50 Hz
AUTO
EASY
(QSM)
Quick setting mode
OFF: Disable
ON: Enable
ON
(LANG)
Guide display language
ENG: English
FRA: French
GER: German
SPA: Spanish
Depe-nds on
the model
and suffix
codes
(PASS)
Password setting
0 (No password) to 65535
0
■ Error and Version Confirmation Parameter (for display only)
Menu symbol:
(VER)
Parameter
symbol
Name of Parameter
Status record
Display
level
(PA.ER)
Parameter error status
EASY
(OP.ER)
Option error status
(AD1.E)
A/D converter error status 1
(AD2.E)
A/D converter error status 2
(PV1.E)
Loop-1 PV input error status
(PV2.E)
Loop-2 PV input error status
(LA.ER)
Ladder error status
(MCU)
MCU version
EASY
(DCU)
DCU version
(ECU1)
ECU-1 version (E1-terminal area)
(ECU2)
ECU-2 version (E2-terminal area)
(ECU3)
ECU-3 version (E3-terminal area)
(ECU4)
ECU-4 version (E4-terminal area)
(PARA)
Parameter version
(H.VER)
Product version
(
SER1
)
Serial number 1
(SER2)
Serial number 2
(MAC1)
MAC address 1 (E3-terminal area)
(MAC2)
MAC address 2 (E3-terminal area)
(MAC3)
MAC address 3 (E3-terminal area)
*
The parameters for Loop-2 are unavailable in Single-loop control.
■ Parameter Display Level Parameter
Menu symbol:
(LVL)
Parameter
symbol
Name of Parameter
Setting Range
Initial
value
User
setting
Display
level
(LEVL)
Parameter display level
EASY: Easy setting mode
STD: Standard setting mode
PRO: Professional setting mode
STD
EASY
*
For Professional setting mode, see User’s Manual.
Trademarks
● Our product names or brand names mentioned in this manual are
the trademarks or registered trademarks of Yokogawa Electric Corporation.
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
of Adobe Systems Incorporated.
● Ethernet is a registered trademark of XEROX Corporation in the United States.
● Modbus is a registered trademark of Schneider Electric.
● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
● CC-Link is a registered trademark of CC-Link Partner Association.
● We do not use the TM or ® mark to indicate these trademarks or
registered trademarks in this manual.
● All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.
• Authorised Representative in the EEA
Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The Netherlands) is the
Authorised Representative of Yokogawa Electric Corporation for this Product in the EEA.
• Printed Manuals
Model
Description
UT55A, UT52A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01C31-11EN
UT55A, UT52A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Detailed Code Model
»
IM 05P01C31-15EN
UT55A/MDL, UT52A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P01C81-11EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
• Electronic Manuals
You can download the latest manuals from the following website:
URL: http://www.yokogawa.com/ns/ut/im/
Model
Description
UT55A, UT52A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Standard Code Model
»
IM 05P01C31-11EN
UT55A, UT52A Digital Indicating Controller (Panel Mounting Type) Operation Guide
«
Detailed Code Model
»
IM 05P01C31-15EN
UT55A/MDL, UT52A/MDL Digital Indicating Controller (DIN Rail Mounting Type)
Operation Guide
«
Standard Code Model
»
IM 05P01C81-11EN
UT55A/UT52A Digital Indicating Controller User’s Manual
IM 05P01C31-01EN
UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
UTAdvanced Series Communication Interface (Open Network) User’s Manual
IM 05P07A01-02EN
LL50A Parameter Setting Software Installation Manual
IM 05P05A01-01EN
LL50A Parameter Setting Software User’s Manual
IM 05P05A01-02EN
Precautions on the Use of the UTAdvanced Series
IM 05P01A01-11EN
• General Specification
Model
Description
UT55A, UT52A Digital Indicating Controller (Panel Mounting Type)
GS 05P01C31-01EN
UT55A/MDL, UT52A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01C81-01EN
LL50A Parameter Setting Software
GS 05P05A01-01EN
*
The last two characters of the manual number and general specification number indicate the
language in which the manual is written.