IM 05P01C31-15EN   page 7/12

Contents

1.  Monitoring-purpose Operation Displays Available during Operation

2.  Setting Target Setpoint (SP)

3.  Performing/Canceling Auto-tuning

4.  Selecting Target Setpoint Numbers (SPNO.)

5.  Switching between AUTO and MAN

6.  Switching between RUN and STOP

7.  Switching between REM (Remote) and LCL (Local)

8.  Manipulating Control Output in Manual Mode

9.  Troubleshooting

1.  Monitoring-purpose Operation Displays Available during Operation

■ 

Operation Display Switching Diagram for Standard and Posi-

tion Proportional Types

•  SP Display

  Displays the measured input value on PV display. 

  Displays the target setpoint (SP) on Setpoint display (SP can be changed).

•  OUT Display

  Displays the measured input value on PV display.

  Displays the control output value (OUT) on Setpoint display (OUT can be changed 

in manual mode).

  Displays the valve’s feedback input value (at 0 to 100% valve opening) in Position 

proportional control.

SP Display

(SP can be changed.)

OUT Display

(OUT can be changed.)

 

■ 

Operation Display Switching Diagram for Heating/Cooling Type

•  SP Display

  Displays the measured input value on PV display.

  Displays the target setpoint (SP) on Setpoint display (SP can be changed).

•  OUT Display

  Displays the measured input value on PV display.

  Displays the control output values (C.H.) of heating and cooling sides on Setpoint 

display (C.H. can be changed in manual mode).

SP Display

(SP can be changed.)

Heating/cooling OUT Display

(OUT can be changed.)

After showing the OUT Display, press the DISPLAY key or DISP key to show the fol-

lowing displays conditionally. For details, see User’s Manual (IM 05P01C31-01EN).

Standard, Position Proportional, and Heating/Cooling Types

•  SELECT Displays 1 to 5 (which appear when registered)

•  Analog Input Display (display only) (factory default: non-display)

• 

Position Proportional Computation Output Display (display only) (factory default: non-display)

•  PID Number Display (display only) (factory default: non-display)

• 

Heater Break Alarm-1 Current Display (display only) (for heater break alarm option only)

• 

Heater Break Alarm-2 Current Display (display only) (for heater break alarm option only)

2.  Setting Target Setpoint (SP)

When the required value is displayed, 

press the SET/ENTER key to register 

the setpoint.

Show the SP Display (Operation Display).

(This is an example of setting the target      

 setpoint to 150.0).

Press the SET/ENTER key to start the 

last digit of the setpoint blinking.

Blinking allows you to change the value.

To set the setpoint, use the 

Left/Right arrow keys to move 

between digits and the Up/Down 

arrow keys to increase and 

decrease the value.

1.

2.

3.

4.

3.  Performing/Canceling Auto-tuning

Auto-tuning should be performed after setting a target setpoint.

Make sure that the controller is in automatic mode (AUTO) and in run mode (RUN) 

before auto-tuning. For setting to AUTO, see “5. Switching between AUTO and 

MAN,” and for setting to RUN, see “6. Switching between RUN and STOP.” 

If the setpoint is known in advance or auto-tuning does not find any appropriate PID 

constants, set the PID manually. For setting the PID manually, see User’s Manual (IM 

05P01C31-01EN).

CAUTION

Do not perform auto-tuning for the following processes.

Tune PID manually.

•  Processes with fast response such as flow rate control and pres-

sure control.

•  Processes which do not allow the output to be turned on and off 

even temporarily.

•  Processes which prohibit severe output changes at control 

valves (or other actuators).

•  Processes in which product quality can be adversely affected if 

PV values fluctuate beyond their allowable ranges.

Show the Operation Display.

Hold down the PARAMETER key or PARA key for 

3 seconds to display MODE menu. 

Press the SET/ENTER key.

Press the SET/ENTER key.

Press the Down arrow key until the parameter AT appears.

The parameter AT (auto-tuning switch) is displayed.

1.

2.

3.

4.

The parameter R.L (REMOTE/LOCAL switch) 

is displayed.

Press the SET/ENTER key.

During auto-tuning,

• The MAN lamp blinks.

• The OUT symbol appears.

• The output values at 100.0% and 

0% appear alternately. 

OFF blinks.

Press the Up/Down arrow keys to display the required setpoint.

Blinks during the change.

The setpoint has been registered. 

This starts auto-tuning.

The limiter can be set to the output during auto-tuning. 

For details, see User’s Manual (IM 05P01C31-01EN). 

The MAN lamp goes off, which means that 

the auto-tuning completed normally.

5.

6.

7.

8.

The setting range is 1 to 8 (represent group numbers) or R.

To perform auto-tuning for the PID of group 1, set the parameter AT to 1.

To quit the auto-tuning, set the parameter to OFF.

4.  Selecting Target Setpoint Numbers (SPNO.)

The following operating procedure shows an example of changing the target setpoint 

number (SPNO.) from 1 to 2. Each SP has its PID group. The PID group set for the 

parameter PIDN (PID number selection) is used.

Show the Operation Display.

Hold down the PARAMETER key or PARA key for 

3 seconds to display MODE menu.

Press the SET/ENTER key.

SPNO. has been changed to 2.

Blinks during the change.

The setpoint has been registered.

Press the DISPLAY key or DISP key once 

to return to the Operation Display.

Change the setpoint using 

the Up/Down arrow keys.

Press the Down arrow key until the parameter SPNO. 

appears.

Press the SET/ENTER key.

Press the SET/ENTER key.

1.
2.

3.

4.

5.

6.

7.

The parameter R.L (REMOTE/LOCAL switch) is 

displayed. 

The parameter SPNO. (SP number selection) 

is displayed.

Operation

Guide

UT55A, UT52A

Digital Indicating Controller 

(Panel Mounting Type)

Operation Guide for Single-loop Control

This operation guide describes key entries for operating the UT55A and UT52A.

Although the display of UT55A is used in this guide, UT52A can be operated similarly. 

For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” 

in “Installation and Wiring.” 

If you cannot remember how to carry out an operation during setting, press the 

DISPLAY key or DISP key once. This brings you to the display (Operation Display) that 

appears at power-on. 

The scrolling guide is displayed on PV display in the Parameter Setting Display. 

This guide can be turned on/off with the Fn key.

Operations

For details of the each function, refer to the electronic manual. Manuals can be 

downloaded or viewed at the following URL.

Functional

Enhancement

http://www.yokogawa.com/ns/ut/im/

«Detailed Code Model»

5.  Switching between AUTO and MAN

AUTO and MAN switching can be performed using any of the following: (1) A/M key, 

(2) Contact input, (3) Communication, and (4) User function key.

The figure below shows a direct operation using the A/M key. 

When AUTO and MAN switching function is assigned to the contact input, and the 

contact input is ON, the switching by key operation cannot be performed.

For details, see User’s Manual (IM 05P01C31-01EN).

MAN lamp is lit in MAN mode.

Each time you press the               key,
AUTO and MAN is switched alternately.

When AUTO is switched into MAN, the control output value in AUTO mode is held. 

The controller can be operated manually from the hold value.

If the manual preset output is set (MPON parameter ≠ OFF), the controller can be 

operated manually from the arbitrary output value (MPO1 to MPO5 parameters).

6.  Switching between RUN and STOP

RUN and STOP switching can be performed using any of the following: (1) Contact 

input, (2) Parameter, (3) Communication, and (4) User function key.

The following shows an example of switching using the contact input.

(The switching function is assigned to DI2 contact for the factory default.)

For details of other switching methods and the display appearing when the operation 

is started, see User’s Manual (IM 05P01C31-01EN).

When the controller is stopped, input and outputs are as follows:

PV input

Displays the PV value.

Control output

Displays the preset output value.

The preset output value is set for each PID group. 

Alarm output

Turns the output on in case of an alarm.

Display in STOP mode

“STOP” is displayed on Symbol display and "preset output value" is displayed on 

Data display.

OFF: Operation RUN

Display in STOP mode

210

212

ON: Operation STOP

210

212

Preset output (PO)

Valve opening (0-100%) for 

Position proportional type

STOP lamp is lit.

DI2

DI2

Display in STOP mode in Heating/cooling control

“Cooling-side preset output value” is displayed on the left side of the “ST” symbol, 

and “Heating-side preset output value” is on the right side.

OFF: Operation RUN

Display in STOP mode

210

212

ON: Operation STOP

210

212

Heating-side preset output (PO)

STOP lamp is lit

Cooling-side preset output (POc)

.

DI2

DI2

Содержание UTAdvanced UT52A

Страница 1: ...ish are available for the guide display 2 For heating cooling output both Output 1 and Output 2 should be specified Not available when Output 2 is N For position proportional output specify P for Outp...

Страница 2: ...o 5 000 V 0 1 of instrument range 1 digit DC voltage 0 000 to 2 000 V 0 2 of instrument range 1 digit 0 00 to 10 00 V 0 1 of instrument range 1 digit DC voltage for high input impedance 0 000 to 1 250...

Страница 3: ...208 Can be used for retransmission output or 15 V DC loop power supply when current voltage pulse output is not used for control output Current output range can be changed In Position proportional ty...

Страница 4: ...nal contact output Transistor contact rating 24 V DC 50 mA DO22 DO21 DO23 DO24 DO25 COM Alarm 4 PV low limit Common UT Option code Y2 307 308 309 310 311 312 Function can be assigned to the terminals...

Страница 5: ...ting Software is on the top of the unit 2 Setup Procedure The following flowchart shows the setup procedure for UT55A and UT52A Install and wire a controller Monitoring and control of regular operatio...

Страница 6: ...type is displayed Press the SET ENTER key 5 6 Energized De energized Latch action Stand by action The alarm 1 type setpoint 02 PV low limit is registered After the setup is completed press the DISPLAY...

Страница 7: ...int has been registered This starts auto tuning The limiter can be set to the output during auto tuning For details see User s Manual IM 05P01C31 01EN The MAN lamp goes off which means that the auto t...

Страница 8: ...function E1 to E4 terminal areas Faulty Contact us for repair Normal indication Normal indication Rightmost decimal point on PV display blinks Setup parameter PA ER Calibration value error Initialized...

Страница 9: ...4 SP low limit 05 Deviation high limit 06 Deviation low limit 07 Deviation high and low limits 08 Deviation within high and low limits 09 Target SP high limit 10 Target SP low limit 11 Target SP devia...

Страница 10: ...king state allows you to make changes setting mode Use the Up Down Left Right arrow keys to change the setpoint Press the SET ENTER key to register the setting Note that there are some parameters whic...

Страница 11: ...ge O1RS Retransmission output type of OUT current output Same as RTS OFF STD O1RH Maximum value of retransmission output scale of OUT current output When O1RS PV1 SP1 PV2 SP2 TSP1 TSP2 PV RSP AIN2 or...

Страница 12: ...ion Set an I relay number For the items other than below see Communication User s Manual Ex Set the number 4353 for AL1 S to use the alarm 1 Set OFF to disable the function No function OFF Alarm 1 435...

Отзывы: