UTAdvanced UT35A/UT32A
List of Parameters
Operation Parameters
Operation Mode
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
MODE
S.R
STOP/RUN switch
EASY
STOP: Stop mode
RUN: Run mode
Preset output (PO) is generated in STOP mode.
Default: Not displayed. STOP/RUN switch is assigned to contact input.
RUN
R.L
REMOTE/LOCAL switch
EASY
LCL: Local mode
REM: Remote mode
(Displayed only in cases where the communication is specified.)
LCL
AT
Auto-tuning switch
EASY
OFF: Disable
1 to 4: Perform auto-tuning. Tuning result is stored in the specified numbered
PID.
R: Tuning result is stored in the PID for reference deviation.
OFF
SPNO.
SP number selection
EASY
1 to 4 (Depends on the setup parameter SPGR. setting.)
1
PID
PID number
EASY
The PID group number being selected is displayed.
1 to 4, R: PID group for reference deviation
1
SELECT Parameter
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
CS
CS10
SELECT parameter 10
EASY
-
CS11
SELECT parameter 11
EASY
-
CS12
SELECT parameter 12
EASY
-
CS13
SELECT parameter 13
EASY
-
CS14
SELECT parameter 14
EASY
-
CS15
SELECT parameter 15
EASY
-
CS16
SELECT parameter 16
EASY
-
CS17
SELECT parameter 17
EASY
-
CS18
SELECT parameter 18
EASY
-
CS19
SELECT parameter 19
EASY
-
SP and Alarm Setpoint Setting
Group 1
(SPNO.=1)
Group 2
(SPNO.=2)
Group 3
(SPNO.=3)
Group 4
(SPNO.=4)
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
User setting
User setting
User setting
SP
SP
Target setpoint
EASY
0.0 to 100.0% of PV input range (EU) (Setting range: SPL to SPH)
SPL
SUB
Sub-target setpoint
(in Two-position two-level control)
EASY
Set the offset from SP.
-100.0 to 100.0% of PV input range span (EUS)
0.0 % of PV input range
span
PIDN
PID number selection
EASY
1 to 4 (Depends on the PIDG. setting.)
Same as SP number.
A1
Alarm-1 setpoint
EASY
0
A2
Alarm-2 setpoint
EASY
0
A3
Alarm-3 setpoint
EASY
0
A4
Alarm-4 setpoint
EASY
0
SP-related Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
SPS
RT
Remote input ratio
STD
0.001 to 9.999
(Displayed only in cases where the communication is specified.)
1.000
RBS
Remote input bias
STD
-100.0 to 100.0% of PV input range span (EUS)
(Displayed only in cases where the communication is specified.)
0.0 % of PV input range
span
UPR
SP ramp-up rate
EASY
OFF
DNR
SP ramp-down rate
EASY
OFF
TMU
SP ramp-rate time unit
EASY
HOUR: Ramp-up rate or rampdown rate per hour
MIN: Ramp-up rate or ramp-down rate per minute
HOUR
SPT
SP tracking selection
STD
OFF, ON
ON
PVT
PV tracking selection
STD
OFF, ON
OFF
Alarm Function Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
ALRM
AL1
Alarm-1 type
EASY
PV high limit (01)
Without Standby action (0)
Energized (0)
Latch action (0)
AL2
Alarm-2 type
EASY
PV low limit (02)
Without Standby action (0)
Energized (0)
Latch action (0)
AL3
Alarm-3 type
EASY
PV high limit (01)
Without Standby action (0)
Energized (0)
Latch action (0)
AL4
Alarm-4 type
EASY
PV low limit (02)
Without Standby action (0)
Energized (0)
Latch action (0)
VT1
PV velocity alarm time setpoint 1
EASY
1.00
VT2
PV velocity alarm time setpoint 2
EASY
1.00
VT3
PV velocity alarm time setpoint 3
EASY
1.00
VT4
PV velocity alarm time setpoint 4
EASY
1.00
HY1
Alarm-1 hysteresis
EASY
10
HY2
Alarm-2 hysteresis
EASY
10
HY3
Alarm-3 hysteresis
EASY
10
HY4
Alarm-4 hysteresis
EASY
10
DYN1
Alarm-1 On-delay timer
STD
0.00
DYN2
Alarm-2 On-delay timer
STD
0.00
DYN3
Alarm-3 On-delay timer
STD
0.00
DYN4
Alarm-4 On-delay timer
STD
0.00
DYF1
Alarm-1 Off-delay timer
PRO
0.00
DYF2
Alarm-2 Off-delay timer
PRO
0.00
DYF3
Alarm-3 Off-delay timer
PRO
0.00
DYF4
Alarm-4 Off-delay timer
PRO
0.00
AMD
Alarm mode
STD
0: Always active
1: Not active in STOP mode
2: Not active in STOP or MAN mode
0
PV-related Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
PVS
BS
PV input bias
EASY
-100.0 to 100.0% of PV input range span (EUS)
0.0 % of PV input range
span
FL
PV input filter
EASY
OFF, 1 to 120 s
OFF
0.00 to 99.59 (minute.second)
Set a 5-digit value in the following order.
[Alarm type: 2 digits (see below)] + [Without (0) or With (1) Stand-by action]
+ [Energized (0) or De-energized (1)] + [Latch action (0/1/2/3/4)]
Alarm type: 2 digits
00: Disable
01: PV high limit
02: PV low limit
03: SP high limit
04: SP low limit
05: Deviation high limit
06: Deviation low limit
07: Deviation high and low limits
08: Deviation within high and low limits
09: Target SP high limit
10: Target SP low limit
11: Target SP deviation high limit
12: Target SP deviation low limit
13: Target SP deviation high and low limits
14: Target SP deviation within high and low limits
15: OUT high limit
16: OUT low limit
17: Cooling-side OUT high limit
18: Cooling-side OUT low limit
19: Analog input PV high limit
20: Analog input PV low limit
27: Feedback input high limit
28: Feedback input low limit
29: PV velocity
30: Fault diagnosis
31: FAIL
0.01 to 99.59 (minute.second)
Set a display value of setpoint of hysteresis.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
When the decimal point position for the input type is set to "1", the initial
value of the hysteresis is "1.0".
0.00 to 99.59 (minute.second)
* Some parameters are not displayed according to the model and suffix codes or the setting of CNT parameter. For
details, refer to the User's Manual.
Setting range of a registered parameter.
See User's Manual.
Set a display value of setpoint of PV alarm, SP alarm, deviation alarm, output
alarm, or velocity alarm.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
OFF, 0.0 + 1 digit to 100.0% of PV input range span (EUS)
Page 11 / 18