Display Function Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
DISP
PCMD
Active color PV display switch
EASY
0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF: red, Alarm ON: white)
6: PV limit (Within range: white, Out of range: red)
7: PV limit (Within range: red, Out of range: white)
8: SP deviation (Within deviation: white, Out of deviation: red)
9: SP deviation (Within deviation: red, Out of deviation: white)
10: Link to DI (ON: red, OFF: white)
0
PCH
PV color change high limit
EASY
0
PCL
PV color change low limit
EASY
0
BAR1
Bar-graph display registration
STD
0: Disable
1:OUT, Heating-side OUT, Internal value in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input
5
(Heating/cooling type: 1)
BDV
Bar-graph deviation display band
STD
0.0 to 100.0% of PV input range span (EUS)
10.0 % of PV input range
span
EV1
EV1 display condition registration
PRO
4321
EV2
EV2 display condition registration
PRO
4322
EV3
EV3 display condition registration
PRO
4323
EV4
EV4 display condition registration
PRO
4325
PV.D
PV display area ON/OFF
PRO
ON
SP.D
Setpoint display area ON/OFF
PRO
ON
STS.D
Status display area ON/OFF
PRO
ON
SPD
Scroll speed
PRO
(Slow) 1 to 8 (Quick)
4
GUID
Guide display ON/OFF
STD
OFF: Nondisplay
ON: Display
ON
HOME
Home Operation Display setting
PRO
SP1: SP Display
OUT1: OUT Display
HCO: Heating/cooling OUT Display
VP: Valve Position Display
MV: Position Proportional Computation Output Display
PID1: PID Number Display
HC1: Heater Break Alarm-1 Current Display
HC2: Heater Break Alarm-2 Current Display
PV: PV Analog Input Display
CS1 to CS5: SELECT Display 1 to 5
SP1
ECO
Economy mode
STD
OFF: Disable
1: Economy mode ON (All indications except PV display OFF)
2: Economy mode ON (All indications OFF)
3: Brightness 10 % (All indications)
OFF
BRI
Brightness
EASY
(Dark) 1 to 5 (Bright)
3
B.PVW
White brightness adjustment of PV display
PRO
Adjusts the white brightness of PV display.
(Dark) -4 to 4 (Bright)
0
B.PVR
Red brightness adjustment of PV display
PRO
Adjusts the red brightness of PV display.
(Dark) -4 to 4 (Bright)
0
B.SP
Brightness adjustment of Setpoint display
PRO
Adjusts the brightness of SP display.
(Dark) -4 to 4 (Bright)
0
B.BAR
Brightness adjustment of Bargraph display
PRO
Adjusts the brightness of Bargraph display.
(Dark) -4 to 4 (Bright)
0
B.STS
Brightness adjustment of Status indicator
PRO
Adjusts the brightness of Status indicator.
(Dark) -4 to 4 (Bright)
0
D.CYC
Display update cycle
PRO
1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s
2
OP.JP
Autoreturn to operation display
PRO
Automatically returned to the Operation Display when there has been no
keystroke operation for 5 minutes.
OFF, ON
ON
MLSD
Least significant digital mask of PV display
STD
OFF: With least significant digit
ON: Without least significant digit
OFF
SELECT Display Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
CSEL
CS1
SELECT Display-1 registration
STD
OFF
CS2
SELECT Display-2 registration
STD
OFF
CS3
SELECT Display-3 registration
STD
OFF
CS4
SELECT Display-4 registration
STD
OFF
CS5
SELECT Display-5 registration
STD
OFF
CS10
SELECT parameter-10 registration
PRO
OFF
CS11
SELECT parameter-11 registration
PRO
OFF
CS12
SELECT parameter-12 registration
PRO
OFF
CS13
SELECT parameter-13 registration
PRO
OFF
CS14
SELECT parameter-14 registration
PRO
OFF
CS15
SELECT parameter-15 registration
PRO
OFF
CS16
SELECT parameter-16 registration
PRO
OFF
CS17
SELECT parameter-17 registration
PRO
OFF
CS18
SELECT parameter-18 registration
PRO
OFF
CS19
SELECT parameter-19 registration
PRO
OFF
Key Lock Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
KLOC
U.SP
SP Display lock
PRO
OFF
U.OUT
OUT Display lock
PRO
OFF
U.HCO
Heating/cooling OUT Display lock
PRO
OFF
U.VP
Valve Position Display lock
PRO
OFF
U.MV
Position Proportional Computation Output
Display lock
PRO
ON
U.PID
PID Number Display lock
PRO
ON
U.HC
Heater Break Alarm Current Value Display lock
PRO
OFF
U.PV
PV Analog Input Display lock
PRO
ON
COM.W
Communication write enable/disable
STD
OFF: Enable, ON: Disable
OFF
DATA
Front panel parameter data key lock
STD
OFF
A/M
Front panel A/M key lock
STD
OFF
OFF, 2301 to 5000
For the D register number, see the UTAdvanced Series Communication
Interface User’s Manual
Main registration parameters
- Group 1 (SPNO.=1)
Alarm-1 setpoint (A1): 2504, Alarm-2 setpoint (A2): 2505,
Alarm-3 setpoint (A3): 2506, Alarm-4 setpoint (A4): 2507,
Control output high limit (OH): 3004, Control output low limit (OL): 3005,
Cooling-side control output high limit (OHc):
3016, Cooling-side control output low limit (OLc): 3017
- Group 2 (SPNO.=2)
Alarm-1 setpoint (A1): 2524, Alarm-2 setpoint (A2): 2525,
Alarm-3 setpoint (A3): 2526, Alarm-4 setpoint (A4): 2527,
Control output high limit (OH): 3054, Control output low limit (OL): 3055,
Cooling-side control output high limit (OHc): 3066,
Cooling-side control output low limit (OLc): 3067
- Group 3 (SPNO.=3)
Alarm-1 setpoint (A1): 2544, Alarm-2 setpoint (A2): 2545,
Alarm-3 setpoint (A3): 2546, Alarm-4 setpoint (A4): 2547,
Control output high limit (OH): 3104, Control output low limit (OL): 3105,
Cooling-side control output high limit (OHc): 3116,
Cooling-side control output low limit (OLc): 3117
- Group 4 (SPNO.=4)
Alarm-1 setpoint (A1): 2564, Alarm-2 setpoint (A2): 2565,
Alarm-3 setpoint (A3): 2566, Alarm-4 setpoint (A4): 2567,
Control output high limit (OH): 3154, Control output low limit (OL): 3155,
Cooling-side control output high limit (OHc):
3166, Cooling-side control output low limit (OLc): 3167
SP ramp-up rate (UPR): 2705, SP ramp-down rate (DNR): 2706
Remote input ratio (RT): 2703
OFF: Display
ON: Nondisplay
OFF: Unlock
ON: Lock
Set a display value when in PV limit or SP deviation.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.
Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm occurs)
4530: Heater break alarm 2 (Lit when the alarm occurs)
5025 to 5026: Link to DI1-DI2 (Lit when the contact is closed)
5041 to 5045: Link to DI11-DI15 (E1-terminal area)
(Lit when the contact is closed)
5153 to 5155: Link to AL1-AL3 (Lit when the contact is closed)
5169 to 5170: Link to DO11-DO12 (E1-terminal area)
(Lit when the contact is closed)
5217 to 5221: Link to DO41-DO45 (E4-terminal area)
(Lit when the contact is closed)
For other functions, see the UTAdvanced Series Communication Interface User’
s Manual.
OFF: Nondisplay, ON: Display
Page 16 / 18