background image

Display Function Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

DISP

PCMD

Active color PV display switch

EASY

0: Fixed in white
1: Fixed in red
2: Link to alarm 1 (Alarm OFF: white, Alarm ON: red)
3: Link to alarm 1 (Alarm OFF: red, Alarm ON: white)
4: Link to alarm 1 or 2 (Alarm OFF: white, Alarm ON: red)
5: Link to alarm 1 or 2 (Alarm OFF: red, Alarm ON: white)
6: PV limit (Within range: white, Out of range: red)
7: PV limit (Within range: red, Out of range: white)
8: SP deviation (Within deviation: white, Out of deviation: red)
9: SP deviation (Within deviation: red, Out of deviation: white)
10: Link to DI (ON: red, OFF: white)

0

PCH

PV color change high limit

EASY

0

PCL

PV color change low limit

EASY

0

BAR1

Bar-graph display registration

STD

0: Disable
1:OUT, Heating-side OUT, Internal value in Position proportional control
2: Cooling-side OUT
3: PV
4: SP
5: Deviation
6 to 16: Disable
17: Feedback input (valve opening)
18: PV terminals analog input

5
(Heating/cooling type: 1)

BDV

Bar-graph deviation display band

STD

0.0 to 100.0% of PV input range span (EUS)

10.0 % of PV input range
span

EV1

EV1 display condition registration

PRO

4321

EV2

EV2 display condition registration

PRO

4322

EV3

EV3 display condition registration

PRO

4323

EV4

EV4 display condition registration

PRO

4325

PV.D

PV display area ON/OFF

PRO

ON

SP.D

Setpoint display area ON/OFF

PRO

ON

STS.D

Status display area ON/OFF

PRO

ON

SPD

Scroll speed

PRO

(Slow) 1 to 8 (Quick)

4

GUID

Guide display ON/OFF

STD

OFF: Nondisplay
ON: Display

ON

HOME

Home Operation Display setting

PRO

SP1: SP Display
OUT1: OUT Display
HCO: Heating/cooling OUT Display
VP: Valve Position Display
MV: Position Proportional Computation Output Display
PID1: PID Number Display
HC1: Heater Break Alarm-1 Current Display
HC2: Heater Break Alarm-2 Current Display
PV: PV Analog Input Display
CS1 to CS5: SELECT Display 1 to 5

SP1

ECO

Economy mode

STD

OFF: Disable
1: Economy mode ON (All indications except PV display OFF)
2: Economy mode ON (All indications OFF)
3: Brightness 10 % (All indications)

OFF

BRI

Brightness

EASY

(Dark) 1 to 5 (Bright)

3

B.PVW

White brightness adjustment of PV display

PRO

Adjusts the white brightness of PV display.
(Dark) -4 to 4 (Bright)

0

B.PVR

Red brightness adjustment of PV display

PRO

Adjusts the red brightness of PV display.
(Dark) -4 to 4 (Bright)

0

B.SP

Brightness adjustment of Setpoint display

PRO

Adjusts the brightness of SP display.
(Dark) -4 to 4 (Bright)

0

B.BAR

Brightness adjustment of Bargraph display

PRO

Adjusts the brightness of Bargraph display.
(Dark) -4 to 4 (Bright)

0

B.STS

Brightness adjustment of Status indicator

PRO

Adjusts the brightness of Status indicator.
(Dark) -4 to 4 (Bright)

0

D.CYC

Display update cycle

PRO

1: 100 ms
2: 200 ms
3: 500 ms
4: 1 s
5: 2 s

2

OP.JP

Autoreturn to operation display

PRO

Automatically returned to the Operation Display when there has been no
keystroke operation for 5 minutes.
OFF, ON

ON

MLSD

Least significant digital mask of PV display

STD

OFF: With least significant digit
ON: Without least significant digit

OFF

SELECT Display Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

CSEL

CS1

SELECT Display-1 registration

STD

OFF

CS2

SELECT Display-2 registration

STD

OFF

CS3

SELECT Display-3 registration

STD

OFF

CS4

SELECT Display-4 registration

STD

OFF

CS5

SELECT Display-5 registration

STD

OFF

CS10

SELECT parameter-10 registration

PRO

OFF

CS11

SELECT parameter-11 registration

PRO

OFF

CS12

SELECT parameter-12 registration

PRO

OFF

CS13

SELECT parameter-13 registration

PRO

OFF

CS14

SELECT parameter-14 registration

PRO

OFF

CS15

SELECT parameter-15 registration

PRO

OFF

CS16

SELECT parameter-16 registration

PRO

OFF

CS17

SELECT parameter-17 registration

PRO

OFF

CS18

SELECT parameter-18 registration

PRO

OFF

CS19

SELECT parameter-19 registration

PRO

OFF

Key Lock Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

KLOC

U.SP

SP Display lock

PRO

OFF

U.OUT

OUT Display lock

PRO

OFF

U.HCO

Heating/cooling OUT Display lock

PRO

OFF

U.VP

Valve Position Display lock

PRO

OFF

U.MV

Position Proportional Computation Output
Display lock

PRO

ON

U.PID

PID Number Display lock

PRO

ON

U.HC

Heater Break Alarm Current Value Display lock

PRO

OFF

U.PV

PV Analog Input Display lock

PRO

ON

COM.W

Communication write enable/disable

STD

OFF: Enable, ON: Disable

OFF

DATA

Front panel parameter data key lock

STD

OFF

A/M

Front panel A/M key lock

STD

OFF

OFF, 2301 to 5000
For the D register number, see the UTAdvanced Series Communication
Interface User’s Manual

Main registration parameters
- Group 1 (SPNO.=1)
Alarm-1 setpoint (A1): 2504, Alarm-2 setpoint (A2): 2505,
Alarm-3 setpoint (A3): 2506, Alarm-4 setpoint (A4): 2507,
Control output high limit (OH): 3004, Control output low limit (OL): 3005,
Cooling-side control output high limit (OHc):
3016, Cooling-side control output low limit (OLc): 3017
- Group 2 (SPNO.=2)
Alarm-1 setpoint (A1): 2524, Alarm-2 setpoint (A2): 2525,
Alarm-3 setpoint (A3): 2526, Alarm-4 setpoint (A4): 2527,
Control output high limit (OH): 3054, Control output low limit (OL): 3055,
Cooling-side control output high limit (OHc): 3066,
Cooling-side control output low limit (OLc): 3067
- Group 3 (SPNO.=3)
Alarm-1 setpoint (A1): 2544, Alarm-2 setpoint (A2): 2545,
Alarm-3 setpoint (A3): 2546, Alarm-4 setpoint (A4): 2547,
Control output high limit (OH): 3104, Control output low limit (OL): 3105,
Cooling-side control output high limit (OHc): 3116,
Cooling-side control output low limit (OLc): 3117
- Group 4 (SPNO.=4)
Alarm-1 setpoint (A1): 2564, Alarm-2 setpoint (A2): 2565,
Alarm-3 setpoint (A3): 2566, Alarm-4 setpoint (A4): 2567,
Control output high limit (OH): 3154, Control output low limit (OL): 3155,
Cooling-side control output high limit (OHc):
3166, Cooling-side control output low limit (OLc): 3167

SP ramp-up rate (UPR): 2705, SP ramp-down rate (DNR): 2706
Remote input ratio (RT): 2703

OFF: Display
ON: Nondisplay

OFF: Unlock
ON: Lock

Set a display value when in PV limit or SP deviation.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type.

Setting range: 4001 to 6304
OFF: Disable
4321: Link to alarm 1 (Lit when the alarm occurs)
4322: Link to alarm 2 (Lit when the alarm occurs)
4323: Link to alarm 3 (Lit when the alarm occurs)
4325: Link to alarm 4 (Lit when the alarm occurs)
4529: Heater break alarm 1 (Lit when the alarm occurs)
4530: Heater break alarm 2 (Lit when the alarm occurs)
5025 to 5026: Link to DI1-DI2 (Lit when the contact is closed)
5041 to 5045: Link to DI11-DI15 (E1-terminal area)
                   (Lit when the contact is closed)
5153 to 5155: Link to AL1-AL3 (Lit when the contact is closed)
5169 to 5170: Link to DO11-DO12 (E1-terminal area)
                   (Lit when the contact is closed)
5217 to 5221: Link to DO41-DO45 (E4-terminal area)
                   (Lit when the contact is closed)
For other functions, see the UTAdvanced Series Communication Interface User’
s Manual.

OFF: Nondisplay, ON: Display

Page 16 / 18

Содержание UTAdvanced UT35A

Страница 1: ...UTAdvanced UT35A UT32A Digital Indicating Controller Parameter Maps and Lists TI 05P01D31 01EN Copyright July 2011 1st Edition July 2011 Page 1 18...

Страница 2: ...Map PRO This sheet describes the setup parameter map which can be used as an operation guide List of Parameters PRO This sheet describes the setting range and initial value of operation parameters an...

Страница 3: ...l output value OUT and measured input value PV The data to be displayed can be set by the parameter Initial value deviation in Heating cooling control heatingside control output Lit when the alarms 1...

Страница 4: ...nu Display Press the key once to cancel the parameter setting setpoint is blinking SET ENTER key Press the key in the Menu Display to move to the Parameter Setting Display of the Menu Press the key in...

Страница 5: ...ion and Setup Operation To move to the Operation Parameter Setting Display To move to the Setup Parameter Setting Display To move to the Operation Display Operation for Setting Parameter Display Level...

Страница 6: ...ET ENTER key to blink the setpoint 6 Press the Up or Down arrow key to change the setpoint 7 Press the SET ENTER key to register the setpoint the setpoint stops blinking 8 Press the PARAMETER key once...

Страница 7: ...How to Set Parameter Setpoint Numeric Value Setting Selection Data Setting Time minute second Setting Page 7 18...

Страница 8: ...segments Alphabet Symbol display and Data display 11 segments Alphabet Group display 7 segments Alphabet PV display 14 segments Symbol The following shows the parameter symbols menu symbols alphanumer...

Страница 9: ...N2 1 Ic 4 Ic R Ic MPO5 DYN3 1 Dc 4 Dc R Dc END DYN4 1 OHc 4 OHc R OHc Symbol Corresponding parameters are displayedin all modes DYF1 1 OLc 4 OLc R OLc DYF2 1 HYSc 4 HYSc R HYSc DYF3 1 DB 4 DB R DB Sym...

Страница 10: ...l Key Lock Setting Menu Lock Setting DI Function Registration DI Function Numbering DI1 DI2 Contact Type Setting DI Setting E1 terminal area DI Setting E4 terminal area AL1 AL3 Function Registration D...

Страница 11: ...tch action 0 AL2 Alarm 2 type EASY PV low limit 02 Without Standby action 0 Energized 0 Latch action 0 AL3 Alarm 3 type EASY PV high limit 01 Without Standby action 0 Energized 0 Latch action 0 AL4 Al...

Страница 12: ...0 0 In Position proportional control 1 0 to 10 0 3 0 PO Preset output Heating side preset output in Heating cooling control EASY 5 0 to 105 0 0 0 SU PO Sub preset output in Two position two level cont...

Страница 13: ...ins Mfg Co ASTM E988 WRE W97Re3 W75Re25 OFF UNIT PV input unit EASY No unit C Degree Celsius No unit No unit No unit F Degree Fahrenheit C RH Maximum value of PV input range EASY Depends on the input...

Страница 14: ...PRO 0 00 HDF2 Heater break alarm 2 Offdelay timer PRO 0 00 HB1 D Heater break alarm 1 contact type PRO CLS HB2 D Heater break alarm 2 contact type PRO CLS RS 485 Communication Setting E1 terminal are...

Страница 15: ...isplay CC Link Communication Setting Menu Symbol Name Display level Setting range Initial value User setting CC L BR Baud rate EASY 156K 156k bps 625K 625k bps 2 5M 2 5M bps 5M 5M bps 10M 10M bps 10M...

Страница 16: ...ELECT Display 5 registration STD OFF CS10 SELECT parameter 10 registration PRO OFF CS11 SELECT parameter 11 registration PRO OFF CS12 SELECT parameter 12 registration PRO OFF CS13 SELECT parameter 13...

Страница 17: ...DIn5 contact type PRO 0 n Terminal area number 1 to 4 AL1 AL3 Function Registration Menu Symbol Name Display level Setting range Initial value User setting ALM AL1 S AL1 function selection STD 4353 AL...

Страница 18: ...r setting INIT U DEF Initialization to user default value PRO 12345 Initialization automatically returned to 0 after initialization 0 F DEF Initialization to factory default value PRO 12345 Initializa...

Отзывы: