PID Setting

Group 1

(PIDN=1)

Group 2

(PIDN=2)

Group 3

(PIDN=3)

Group 4

(PIDN=4)

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

User setting

User setting

User setting

PID

P

Proportional band
Heating-side proportional band (in
Heating/cooling control)

EASY

0.0 to 999.9%
When 0.0% is set, it operates as 0.1%.
Heating-side ON/OFF control applies when 0.0% in Heating/cooling control

5.0%

I

Integral time
Heating-side integral time (in Heating/cooling
control)

EASY

OFF: Disable
1 to 6000 s

240 s

D

Derivative time
Heating-side derivative time (in Heating/cooling
control)

EASY

OFF: Disable
1 to 6000 s

60 s

OH

Control output high limit
Heating-side control output high limit (in
Heating/cooling control)

EASY

-4.9 to 105.0%, (OL<OH)
In Heating/cooling control: 0.1 to 105.0% (OL<OH)

100.0%

OL

Control output low limit
Heating-side control output low limit (in
Heating/cooling control)

EASY

-5.0 to 104.9%, (OL<OH), SD:Tight shut
In Heating/cooling control: 0.0 to 104.9% (OL<OH)

0.0%

MR

Manual reset

EASY

Enabled when integral time is OFF.
The manual reset value equals the output value when PV = SP.
-5.0 to 105.0%

50.0%

HYS

Hysteresis (in ON/OFF control, Position
proportional control, or Two-position two-level
control)
Heating-side ON/OFF control hysteresis (in
Heating/cooling control)

EASY

In ON/OFF control or Two-position two-level control: 0.0 to 100.0% of PV input
range span (EUS)
In Heating/cooling control or Position proportional control: 0.0 to 100.0%

In ON/OFF control or Two-
position two-level
control: 0.5 % of PV input
range span
In Heating/cooling control
or Position proportional
control: 0.5 %

SU.HY

Sub-hysteresis (in Two-position two-level
control)

EASY

0.0 to 100.0% of PV input range span (EUS)

0.5 % of PV input range
span

HY.UP

Upper-side hysteresis (in ON/OFF control)

EASY

0.5 % of PV input range
span

HY.LO

Lower-side hysteresis (in ON/OFF control)

EASY

0.5 % of PV input range
span

DR

Direct/reverse action switch

STD

RVS

SU.DR

Sub-direct/reverse action switch (in
Two-position two-level control)

STD

DIR

Pc

Cooling-side proportional band

EASY

0.0 to 999.9%
(Cooling-side ON/OFF control applies when 0.0% in Heating/cooling control)

5.0%

Ic

Cooling-side integral time

EASY

OFF: Disable
1 to 6000 s

240 s

Dc

Cooling-side derivative time

EASY

OFF: Disable
1 to 6000 s

60 s

OHc

Cooling-side control output high limit

EASY

0.1 to 105.0%, (OLc<OHc)

100.0%

OLc

Cooling-side control output low limit

EASY

0.0 to 104.9%, (OLc<OHc)

0.0%

HYSc

Cooling-side ON/OFF control hysteresis

EASY

0.0 to 100.0%

0.5%

DB

Output dead band (in Heating/cooling control
or Position proportional control)

EASY

In Heating/cooling control: -100.0 to 50.0%
In Position proportional control: 1.0 to 10.0%

3.0%

PO

Preset output
Heating-side preset output (in Heating/cooling
control)

EASY

-5.0 to 105.0%

0.0%

SU.PO

Sub-preset output (in Two-position two-level
control)

EASY

0%, 100%

0%

POc

Cooling-side preset output

EASY

-5.0 to 105.0%

0.0%

Tuning

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

TUNE

SC

Super function

EASY

OFF: Disable
1: Overshoot suppressing function (normal mode)
2: Hunting suppressing function (stable mode)
Enables to answer the wider characteristic changes compared with response
mode.
3: Hunting suppressing function (response mode)
Enables quick follow-up and short converging time of PV for the changed SP.
4: Overshoot suppressing function (strong suppressing mode)

OFF

AT.TY

Auto-tuning type

STD

0: Normal
1: Stability

0

AT.OH

Output high limit in auto-tuning

PRO

100.0%

AT.OL

Output low limit in auto-tuning

PRO

0.0%

AT.BS

SP bias in autotuning

PRO

-100.0 to 100.0% of PV input range span (EUS)

0.0 % of PV input range
span

AR

Anti-reset windup (excess integration
prevention)

STD

AUTO, 50.0 to 200.0%

AUTO

OPR

Output velocity limiter

STD

OFF: Disable
0.1 to 100.0%/s

OFF

OLMT

Output limiter switch

PRO

OFF: Disable output limiter in MAN mode
ON: Enable output limiter in MAN mode

ON

MPON

Manual preset output number selection

STD

OFF: Hold the control output in AUTO mode (bumpless)
1: Use manual preset output 1 (output bump)
2: Use manual preset output 2 (output bump)
3: Use manual preset output 3 (output bump)
4: Use manual preset output 4 (output bump)
5: Use manual preset output 5 (output bump)

OFF

MPO1

Manual preset output 1

STD

0.0%

MPO2

Manual preset output 2

STD

0.0%

MPO3

Manual preset output 3

STD

0.0%

MPO4

Manual preset output 4

STD

0.0%

MPO5

Manual preset output 5

STD

0.0%

Zone Control

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

ZONE

RP1

Reference point 1

STD

100.0 % of PV input range

RP2

Reference point 2

STD

100.0 % of PV input range

RP3

Reference point 3

STD

100.0 % of PV input range

RHY

Zone PID switching hysteresis

STD

0.0 to 10.0% of PV input range span (EUS)

0.5 % of PV input range
span

RDV

Reference deviation

STD

OFF: Disable
0.0 + 1 digit to 100.0% of PV input range span (EUS)

OFF

P Parameter

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

PPAR

P01

P01 Parameter

STD

0

P02

P02 Parameter

STD

0

P03

P03 Parameter

STD

0

P04

P04 Parameter

STD

0

P05

P05 Parameter

STD

0

P06

P06 Parameter

STD

0

P07

P07 Parameter

STD

0

P08

P08 Parameter

STD

0

P09

P09 Parameter

STD

0

P10

P10 Parameter

STD

0

-5.0 to 105.0%

0.0 to 100.0% of PV input range (EU)
(RP1 

 RP2 

 RP3)

-19999 to 30000 (Set a decimal point position using LL50A Parameter Setting
Software.)

0.0 to 100.0% of PV input range span (EUS)

RVS: Reverse action, DIR: Direct action

-5.0 to 105.0% (Disabled in Heating/cooling control)

Page 12 / 18

Содержание UTAdvanced UT35A

Страница 1: ...UTAdvanced UT35A UT32A Digital Indicating Controller Parameter Maps and Lists TI 05P01D31 01EN Copyright July 2011 1st Edition July 2011 Page 1 18...

Страница 2: ...Map PRO This sheet describes the setup parameter map which can be used as an operation guide List of Parameters PRO This sheet describes the setting range and initial value of operation parameters an...

Страница 3: ...l output value OUT and measured input value PV The data to be displayed can be set by the parameter Initial value deviation in Heating cooling control heatingside control output Lit when the alarms 1...

Страница 4: ...nu Display Press the key once to cancel the parameter setting setpoint is blinking SET ENTER key Press the key in the Menu Display to move to the Parameter Setting Display of the Menu Press the key in...

Страница 5: ...ion and Setup Operation To move to the Operation Parameter Setting Display To move to the Setup Parameter Setting Display To move to the Operation Display Operation for Setting Parameter Display Level...

Страница 6: ...ET ENTER key to blink the setpoint 6 Press the Up or Down arrow key to change the setpoint 7 Press the SET ENTER key to register the setpoint the setpoint stops blinking 8 Press the PARAMETER key once...

Страница 7: ...How to Set Parameter Setpoint Numeric Value Setting Selection Data Setting Time minute second Setting Page 7 18...

Страница 8: ...segments Alphabet Symbol display and Data display 11 segments Alphabet Group display 7 segments Alphabet PV display 14 segments Symbol The following shows the parameter symbols menu symbols alphanumer...

Страница 9: ...N2 1 Ic 4 Ic R Ic MPO5 DYN3 1 Dc 4 Dc R Dc END DYN4 1 OHc 4 OHc R OHc Symbol Corresponding parameters are displayedin all modes DYF1 1 OLc 4 OLc R OLc DYF2 1 HYSc 4 HYSc R HYSc DYF3 1 DB 4 DB R DB Sym...

Страница 10: ...l Key Lock Setting Menu Lock Setting DI Function Registration DI Function Numbering DI1 DI2 Contact Type Setting DI Setting E1 terminal area DI Setting E4 terminal area AL1 AL3 Function Registration D...

Страница 11: ...tch action 0 AL2 Alarm 2 type EASY PV low limit 02 Without Standby action 0 Energized 0 Latch action 0 AL3 Alarm 3 type EASY PV high limit 01 Without Standby action 0 Energized 0 Latch action 0 AL4 Al...

Страница 12: ...0 0 In Position proportional control 1 0 to 10 0 3 0 PO Preset output Heating side preset output in Heating cooling control EASY 5 0 to 105 0 0 0 SU PO Sub preset output in Two position two level cont...

Страница 13: ...ins Mfg Co ASTM E988 WRE W97Re3 W75Re25 OFF UNIT PV input unit EASY No unit C Degree Celsius No unit No unit No unit F Degree Fahrenheit C RH Maximum value of PV input range EASY Depends on the input...

Страница 14: ...PRO 0 00 HDF2 Heater break alarm 2 Offdelay timer PRO 0 00 HB1 D Heater break alarm 1 contact type PRO CLS HB2 D Heater break alarm 2 contact type PRO CLS RS 485 Communication Setting E1 terminal are...

Страница 15: ...isplay CC Link Communication Setting Menu Symbol Name Display level Setting range Initial value User setting CC L BR Baud rate EASY 156K 156k bps 625K 625k bps 2 5M 2 5M bps 5M 5M bps 10M 10M bps 10M...

Страница 16: ...ELECT Display 5 registration STD OFF CS10 SELECT parameter 10 registration PRO OFF CS11 SELECT parameter 11 registration PRO OFF CS12 SELECT parameter 12 registration PRO OFF CS13 SELECT parameter 13...

Страница 17: ...DIn5 contact type PRO 0 n Terminal area number 1 to 4 AL1 AL3 Function Registration Menu Symbol Name Display level Setting range Initial value User setting ALM AL1 S AL1 function selection STD 4353 AL...

Страница 18: ...r setting INIT U DEF Initialization to user default value PRO 12345 Initialization automatically returned to 0 after initialization 0 F DEF Initialization to factory default value PRO 12345 Initializa...

Отзывы: