Output Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
OUT
OT
Output type selection
EASY
Control output or Heating-side
control output (Lower two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage pulse)
08: RET/OUT2 terminals (current)
Cooling-side control output (Upper two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage pulse)
08: RET/OUT2 terminals (current)
Standard type: 00.03
Heating/cooling type: 06.03
CT
Control output cycle time
Heating-side control output cycle time (in
Heating/cooling control)
EASY
30.0 s
CTc
Cooling-side control output cycle time
EASY
30.0 s
V.AT
Automatic valve position adjustment
EASY
OFF: Stop automatic adjustment
ON: Start automatic adjustment
OFF
V.RS
Valve position setting reset
EASY
Setting V.RS to ON resets the valve adjustment settings and causes the
indication “V.RS” to blink.
OFF
V.L
Fully-closed valve position setting
EASY
Pressing the SET/ENTER key with valve position set to the fullyclosed position
by Down arrow key causes the adjusted value to be stored. When V.L
adjustment is complete, V.L stops blinking.
-
V.H
Fully-open valve position setting
EASY
Pressing the SET/ENTER key with valve position set to the fullyopened position
by Up arrow key causes the adjusted value to be stored. When V.H adjustment
is complete, V.H stops blinking.
-
TR.T
Valve traveling time
STD
5 to 300 s
60 s
V.MOD
Valve adjusting mode
STD
0: Valve position feedback type
1: Valve position feedback type
(moves to the estimating type if a feedback input error or break occurs.)
2: Valve position estimating type
0
RTS
Retransmission output type of RET
EASY
OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to 100 % in Position proportional control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output internal computed value)
PV: PV terminals analog input
PV1
RTH
Maximum value of retransmission output scale
of RET
STD
100 % of PV input range
RTL
Minimum value of retransmission output scale
of RET
STD
0 % of PV input range
O1RS
Retransmission output type of OUT current
output
STD
Same as RTS
OFF
O1RH
Maximum value of retransmission output scale
of OUT current output
STD
-
O1RL
Minimum value of retransmission output scale
of OUT current output
STD
-
OU.A
OUT current output range
STD
4-20
RET.A
RET current output range
STD
4-20
Heater Break Alarm Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
HBA
HB1.S
Heater break alarm-1 function selection
EASY
1
HB2.S
Heater break alarm-2 function selection
EASY
1
HB1
Heater break alarm-1 current setpoint
EASY
OFF
HB2
Heater break alarm-2 current setpoint
EASY
OFF
CT1.T
CT1 coil winding number ratio
EASY
800
CT2.T
CT2 coil winding number ratio
EASY
800
HDN1
Heater break alarm-1 Ondelay timer
STD
0.00
HDN2
Heater break alarm-2 Ondelay timer
STD
0.00
HDF1
Heater break alarm-1 Offdelay timer
PRO
0.00
HDF2
Heater break alarm-2 Offdelay timer
PRO
0.00
HB1.D
Heater break alarm-1 contact type
PRO
CLS
HB2.D
Heater break alarm-2 contact type
PRO
CLS
RS-485 Communication Setting
(E1 terminal
area)
(E3 terminal
area)
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
User setting
R485
PSL
Protocol selection
EASY
PCL: PC link communication
PCLSM: PC link communication (with checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station (Loop-1 mode)
CO-S2: Coordinated slave station (Loop-2 mode)
P-P: Peer-to-peer communication
MBRTU
BPS
Baud rate
EASY
600: 600 bps
1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
19200
PRI
Parity
EASY
NONE: None
EVEN: Even
ODD: Odd
EVEN
STP
Stop bit
EASY
1: 1 bit, 2: 2 bits
1
DLN
Data length
EASY
7: 7 bits, 8: 8 bits
8
ADR
Address
EASY
1 to 99
1
RP.T
Minimum response time
PRO
0 to 10 (x10ms)
0
Ethernet Communication Setting
Menu
Symbol
Name
Display level
Setting range
Initial value
User setting
ETHR
HSR
High-speed response mode
EASY
OFF, 1 to 8
1
BPS
Baud rate
EASY
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps
38400
PRI
Parity
EASY
NONE: None
EVEN: Even
ODD: Odd
EVEN
IP1
IP address 1
EASY
0 to 255
192
IP2
IP address 2
EASY
0 to 255
168
IP3
IP address 3
EASY
0 to 255
1
IP4
IP address 4
EASY
0 to 255
1
SM1
Subnet mask 1
EASY
0 to 255
255
SM2
Subnet mask 2
EASY
0 to 255
255
SM3
Subnet mask 3
EASY
0 to 255
255
SM4
Subnet mask 4
EASY
0 to 255
0
DG1
Default gateway 1
EASY
0 to 255
0
DG2
Default gateway 2
EASY
0 to 255
0
DG3
Default gateway 3
EASY
0 to 255
0
DG4
Default gateway 4
EASY
0 to 255
0
PRT
Port number
EASY
502, 1024 to 65535
502
IPAR
IP access restriction
EASY
OFF: Disable, ON: Enable
OFF
1.IP1
Permitted IP address 1-1
EASY
0 to 255
255
1.IP2
Permitted IP address 1-2
EASY
0 to 255
255
1.IP3
Permitted IP address 1-3
EASY
0 to 255
255
1.IP4
Permitted IP address 1-4
EASY
0 to 255
255
2.IP1
Permitted IP address 2-1
EASY
0 to 255
255
2.IP2
Permitted IP address 2-2
EASY
0 to 255
255
2.IP3
Permitted IP address 2-3
EASY
0 to 255
255
2.IP4
Permitted IP address 2-4
EASY
0 to 255
255
ESW
Ethernet setting switch
EASY
OFF, ON
Setting this parameter to “ON” enables the Ethernet communication parameter
settings.
* The parameter ESW automatically returns to “OFF” after “ON” is set.
OFF
When each parameter is displayed, the terminal area (E3) is displayed on Group display.
OFF, 0.1 to 300.0 Arms
1 to 3300
0.00 to 99.59 (minute.second)
CLS: When the event occurs, the contact is closed.
OPN: When the event occurs, the contact is opened.
When RTS = PV1, SP1, TSP1, or PV
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1, decimal point position is same as that of PV
input.
When RTS=PV, decimal point position is same as that of PV input scale.
When O1RS = PV1, SP1, TSP1, or PV
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1, decimal point position is same as that of PV
input.
When O1RS =PV, decimal point position is same as that of PV input scale.
4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA
0: Heater current measurement
1: Heater break alarm (Heatingside)
2: Cooling-side heater break alarm
0.5 to 1000.0 s
Page 14 / 18