Output Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

OUT

OT

Output type selection

EASY

Control output or Heating-side
control output (Lower two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage pulse)
08: RET/OUT2 terminals (current)
Cooling-side control output (Upper two digits)
00: OFF
01: OUT terminals (voltage pulse)
02: OUT terminals (current)
03: OUT terminals (relay/triac)
06: OUT2 terminals (relay)
07: RET/OUT2 terminals (voltage pulse)
08: RET/OUT2 terminals (current)

Standard type: 00.03
Heating/cooling type: 06.03

CT

Control output cycle time
Heating-side control output cycle time (in
Heating/cooling control)

EASY

30.0 s

CTc

Cooling-side control output cycle time

EASY

30.0 s

V.AT

Automatic valve position adjustment

EASY

OFF: Stop automatic adjustment
ON: Start automatic adjustment

OFF

V.RS

Valve position setting reset

EASY

Setting V.RS to ON resets the valve adjustment settings and causes the
indication “V.RS” to blink.

OFF

V.L

Fully-closed valve position setting

EASY

Pressing the SET/ENTER key with valve position set to the fullyclosed position
by Down arrow key causes the adjusted value to be stored. When V.L
adjustment is complete, V.L stops blinking.

-

V.H

Fully-open valve position setting

EASY

Pressing the SET/ENTER key with valve position set to the fullyopened position
by Up arrow key causes the adjusted value to be stored. When V.H adjustment
is complete, V.H stops blinking.

-

TR.T

Valve traveling time

STD

5 to 300 s

60 s

V.MOD

Valve adjusting mode

STD

0: Valve position feedback type
1: Valve position feedback type
(moves to the estimating type if a feedback input error or break occurs.)
2: Valve position estimating type

0

RTS

Retransmission output type of RET

EASY

OFF: Disable
PV1: PV
SP1: SP
OUT1: OUT (Valve opening: 0 to 100 % in Position proportional control)
LPS: 15 V DC loop power supply
TSP1: Target SP
HOUT1: Heating-side OUT
COUT1: Cooling-side OUT
MV1: Position proportional output internal computed value)
PV: PV terminals analog input

PV1

RTH

Maximum value of retransmission output scale
of RET

STD

100 % of PV input range

RTL

Minimum value of retransmission output scale
of RET

STD

0 % of PV input range

O1RS

Retransmission output type of OUT current
output

STD

Same as RTS

OFF

O1RH

Maximum value of retransmission output scale
of OUT current output

STD

-

O1RL

Minimum value of retransmission output scale
of OUT current output

STD

-

OU.A

OUT current output range

STD

4-20

RET.A

RET current output range

STD

4-20

Heater Break Alarm Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

HBA

HB1.S

Heater break alarm-1 function selection

EASY

1

HB2.S

Heater break alarm-2 function selection

EASY

1

HB1

Heater break alarm-1 current setpoint

EASY

OFF

HB2

Heater break alarm-2 current setpoint

EASY

OFF

CT1.T

CT1 coil winding number ratio

EASY

800

CT2.T

CT2 coil winding number ratio

EASY

800

HDN1

Heater break alarm-1 Ondelay timer

STD

0.00

HDN2

Heater break alarm-2 Ondelay timer

STD

0.00

HDF1

Heater break alarm-1 Offdelay timer

PRO

0.00

HDF2

Heater break alarm-2 Offdelay timer

PRO

0.00

HB1.D

Heater break alarm-1 contact type

PRO

CLS

HB2.D

Heater break alarm-2 contact type

PRO

CLS

RS-485 Communication Setting

(E1 terminal

area)

(E3 terminal

area)

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

User setting

R485

PSL

Protocol selection

EASY

PCL: PC link communication
PCLSM: PC link communication (with checksum)
LADR: Ladder communication
CO-M: Coordinated master station
CO-S: Coordinated slave station
MBASC: Modbus (ASCII)
MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station (Loop-1 mode)
CO-S2: Coordinated slave station (Loop-2 mode)
P-P: Peer-to-peer communication

MBRTU

BPS

Baud rate

EASY

600: 600 bps
1200: 1200 bps
2400: 2400 bps
4800: 4800 bps
9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps

19200

PRI

Parity

EASY

NONE: None
EVEN: Even
ODD: Odd

EVEN

STP

Stop bit

EASY

1: 1 bit, 2: 2 bits

1

DLN

Data length

EASY

7: 7 bits, 8: 8 bits

8

ADR

Address

EASY

1 to 99

1

RP.T

Minimum response time

PRO

0 to 10 (x10ms)

0

Ethernet Communication Setting

Menu

Symbol

Name

Display level

Setting range

Initial value

User setting

ETHR

HSR

High-speed response mode

EASY

OFF, 1 to 8

1

BPS

Baud rate

EASY

9600: 9600 bps
19200: 19.2k bps
38400: 38.4k bps

38400

PRI

Parity

EASY

NONE: None
EVEN: Even
ODD: Odd

EVEN

IP1

IP address 1

EASY

0 to 255

192

IP2

IP address 2

EASY

0 to 255

168

IP3

IP address 3

EASY

0 to 255

1

IP4

IP address 4

EASY

0 to 255

1

SM1

Subnet mask 1

EASY

0 to 255

255

SM2

Subnet mask 2

EASY

0 to 255

255

SM3

Subnet mask 3

EASY

0 to 255

255

SM4

Subnet mask 4

EASY

0 to 255

0

DG1

Default gateway 1

EASY

0 to 255

0

DG2

Default gateway 2

EASY

0 to 255

0

DG3

Default gateway 3

EASY

0 to 255

0

DG4

Default gateway 4

EASY

0 to 255

0

PRT

Port number

EASY

502, 1024 to 65535

502

IPAR

IP access restriction

EASY

OFF: Disable, ON: Enable

OFF

1.IP1

Permitted IP address 1-1

EASY

0 to 255

255

1.IP2

Permitted IP address 1-2

EASY

0 to 255

255

1.IP3

Permitted IP address 1-3

EASY

0 to 255

255

1.IP4

Permitted IP address 1-4

EASY

0 to 255

255

2.IP1

Permitted IP address 2-1

EASY

0 to 255

255

2.IP2

Permitted IP address 2-2

EASY

0 to 255

255

2.IP3

Permitted IP address 2-3

EASY

0 to 255

255

2.IP4

Permitted IP address 2-4

EASY

0 to 255

255

ESW

Ethernet setting switch

EASY

OFF, ON
Setting this parameter to “ON” enables the Ethernet communication parameter
settings.
* The parameter ESW automatically returns to “OFF” after “ON” is set.

OFF

When each parameter is displayed, the terminal area (E3) is displayed on Group display.

OFF, 0.1 to 300.0 Arms

1 to 3300

0.00 to 99.59 (minute.second)

CLS: When the event occurs, the contact is closed.
OPN: When the event occurs, the contact is opened.

When RTS = PV1, SP1, TSP1, or PV
RTL + 1 digit to 30000
-19999 to RTH - 1 digit
Decimal point position:
When RTS=PV1, SP1, or TSP1, decimal point position is same as that of PV
input.
When RTS=PV, decimal point position is same as that of PV input scale.

When O1RS = PV1, SP1, TSP1, or PV
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit
Decimal point position:
When O1RS=PV1, SP1, or TSP1, decimal point position is same as that of PV
input.
When O1RS =PV, decimal point position is same as that of PV input scale.

4-20: 4 to 20 mA
0-20: 0 to 20 mA
20-4: 20 to 4 mA
20-0: 20 to 0 mA

0: Heater current measurement
1: Heater break alarm (Heatingside)
2: Cooling-side heater break alarm

0.5 to 1000.0 s

Page 14 / 18

Содержание UTAdvanced UT35A

Страница 1: ...UTAdvanced UT35A UT32A Digital Indicating Controller Parameter Maps and Lists TI 05P01D31 01EN Copyright July 2011 1st Edition July 2011 Page 1 18...

Страница 2: ...Map PRO This sheet describes the setup parameter map which can be used as an operation guide List of Parameters PRO This sheet describes the setting range and initial value of operation parameters an...

Страница 3: ...l output value OUT and measured input value PV The data to be displayed can be set by the parameter Initial value deviation in Heating cooling control heatingside control output Lit when the alarms 1...

Страница 4: ...nu Display Press the key once to cancel the parameter setting setpoint is blinking SET ENTER key Press the key in the Menu Display to move to the Parameter Setting Display of the Menu Press the key in...

Страница 5: ...ion and Setup Operation To move to the Operation Parameter Setting Display To move to the Setup Parameter Setting Display To move to the Operation Display Operation for Setting Parameter Display Level...

Страница 6: ...ET ENTER key to blink the setpoint 6 Press the Up or Down arrow key to change the setpoint 7 Press the SET ENTER key to register the setpoint the setpoint stops blinking 8 Press the PARAMETER key once...

Страница 7: ...How to Set Parameter Setpoint Numeric Value Setting Selection Data Setting Time minute second Setting Page 7 18...

Страница 8: ...segments Alphabet Symbol display and Data display 11 segments Alphabet Group display 7 segments Alphabet PV display 14 segments Symbol The following shows the parameter symbols menu symbols alphanumer...

Страница 9: ...N2 1 Ic 4 Ic R Ic MPO5 DYN3 1 Dc 4 Dc R Dc END DYN4 1 OHc 4 OHc R OHc Symbol Corresponding parameters are displayedin all modes DYF1 1 OLc 4 OLc R OLc DYF2 1 HYSc 4 HYSc R HYSc DYF3 1 DB 4 DB R DB Sym...

Страница 10: ...l Key Lock Setting Menu Lock Setting DI Function Registration DI Function Numbering DI1 DI2 Contact Type Setting DI Setting E1 terminal area DI Setting E4 terminal area AL1 AL3 Function Registration D...

Страница 11: ...tch action 0 AL2 Alarm 2 type EASY PV low limit 02 Without Standby action 0 Energized 0 Latch action 0 AL3 Alarm 3 type EASY PV high limit 01 Without Standby action 0 Energized 0 Latch action 0 AL4 Al...

Страница 12: ...0 0 In Position proportional control 1 0 to 10 0 3 0 PO Preset output Heating side preset output in Heating cooling control EASY 5 0 to 105 0 0 0 SU PO Sub preset output in Two position two level cont...

Страница 13: ...ins Mfg Co ASTM E988 WRE W97Re3 W75Re25 OFF UNIT PV input unit EASY No unit C Degree Celsius No unit No unit No unit F Degree Fahrenheit C RH Maximum value of PV input range EASY Depends on the input...

Страница 14: ...PRO 0 00 HDF2 Heater break alarm 2 Offdelay timer PRO 0 00 HB1 D Heater break alarm 1 contact type PRO CLS HB2 D Heater break alarm 2 contact type PRO CLS RS 485 Communication Setting E1 terminal are...

Страница 15: ...isplay CC Link Communication Setting Menu Symbol Name Display level Setting range Initial value User setting CC L BR Baud rate EASY 156K 156k bps 625K 625k bps 2 5M 2 5M bps 5M 5M bps 10M 10M bps 10M...

Страница 16: ...ELECT Display 5 registration STD OFF CS10 SELECT parameter 10 registration PRO OFF CS11 SELECT parameter 11 registration PRO OFF CS12 SELECT parameter 12 registration PRO OFF CS13 SELECT parameter 13...

Страница 17: ...DIn5 contact type PRO 0 n Terminal area number 1 to 4 AL1 AL3 Function Registration Menu Symbol Name Display level Setting range Initial value User setting ALM AL1 S AL1 function selection STD 4353 AL...

Страница 18: ...r setting INIT U DEF Initialization to user default value PRO 12345 Initialization automatically returned to 0 after initialization 0 F DEF Initialization to factory default value PRO 12345 Initializa...

Отзывы: