5-20
IM CW500-01EN
Swell (Instantaneous voltage rise)
Set the swell threshold (rms voltage in one cycle) as a percentage of the
nominal voltage. The selectable range varies depending on the VT ratio.
Hysteresis is applied to this threshold.
Settings
100 to 200% (110%*) of the nominal voltage
* Default value
<Procedure>
Use the up and down arrow keys to move to SWELL.
→
Press ENTER to
show a value entry window.*
→
Use the arrow keys to enter a percentage
of the nominal voltage.
* The input range is shown in a pop-up.
Inrush current (Instantaneous current rise)
Set the inrush current threshold (rms current in one cycle) as a
percentage of the maximum value of the current range. The selectable
range varies depending on the CT ratio. Hysteresis is applied to this
threshold.
Settings
0 to 110% (100%*) of the current range
* Default value
<Procedure>
Use the up and down arrow keys to move to InrushCurrent.
→
Press
ENTER to show a value entry window.*
→
Use the arrow keys to enter a
percentage of the maximum value of the current range.
* The input range is shown in a pop-up.
5.3 Measurement Setup