App-1
IM CW500-01EN
When Using 96030, 96033, or 96036
To use a YOKOGAWA’s 96030, 96033, or 96036 current clamp-on probe
with the CW500, you need a 99073 banana-DIN adapter.
The sensor identification function cannot be used.
Configure the clamp-on probe settings manually.
The clamp-on probe settings and specifications are as follows.
Probe
96030
96033
96036
Current-Clamp
setting of CW500
96063
96061
96060
Accuracy
Band
width
±0.5%rdg±0.1mV
(45Hz to 66Hz)
±0.8%rdg±0.2mV
(66Hz to 1kHz)
±2.0%rdg±0.4mV
(1kHz to 3.5kHz)
±0.5%rdg±0.1mV
(45Hz to 66Hz)
±0.8%rdg±0.2mV
(66Hz to 1kHz)
±1.0%rdg±0.3mV
(1kHz to 3.5kHz)
±0.5%rdg±0.01mV
(45Hz to 66Hz)
±0.8%rdg±0.02mV
(66Hz to 1kHz)
±2.0%rdg±0.04mV
(1kHz to 3.5kHz)
Phase ±0.5° or less
(45Hz to 3.5kHz)
±1.0° or less
(45Hz to 3.5kHz)
-
Maximum allowable
input
5% to 110% of each measuring range
Safety standard
Do not comply with safety standard.
Appendix