5-22
IM CW500-01EN
Interruption (Instantaneous power interruption)
Set the interruption threshold (rms voltage in one cycle) as a percentage
of the nominal voltage. The selectable range varies depending on the
VT ratio. Hysteresis is applied to this threshold. To detect events at rms
voltages of 10 V or less, be sure to enable the interruption event. Proper
detection may not be possible by setting a similar threshold for dip.
Settings
0 to 100 % (10 %*) of the nominal voltage
* Default value
<Procedure>
Use the up and down arrow keys to move to INT.
→
Press ENTER to
show a value entry window.*
→
Use the arrow keys to enter a percentage
of the nominal voltage.
* The input range is shown in a pop-up.
Example of Dip and Interruption Detection
For details, see “Displaying Recorded Events” on page 6-27.
Rms value (1)
Rms value (2)
Rms value (3)
Rms value (5)
Rms value (7)
Rms value (9)
Rms value (4)
Rms value (6)
Rms value (8)
Voltage
waveform
Rms waveform
Hysteresis
Threshold
(4)
(5)
(6)
(7)
(8)
(9)
(1)
(2) (3)
5.3 Measurement Setup