![YOKOGAWA CENTUM CS Скачать руководство пользователя страница 240](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927240.webp)
4. Installation Specifications
4-10
TI 33J01J10-01EN
June 30, 2016-00
l
A2FV70
Table Periodic Replacement Parts Having Defined Life Spans
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Power supply module
PW481
8 years
Yes
100 - 120 V AC:
Average ambient temperature 40 °C or less
PW482
8 years
Yes
220 - 240 V AC:
Average ambient temperature 40 °C or less
PW484
8 years
Yes
24 V DC:
Average ambient temperature 40 °C or less
Battery Pack
S9548FA
3 years
Yes
Average ambient temperature
30 °C or less
1.5 years
Yes
Average ambient temperature
40 °C or less
9 months
Yes
Average ambient temperature
50 °C or less
Aluminium Electrolytic
Capacitor
(in power supply
module)
(PW481)
8 years
No
100 V AC:
Average ambient temperature 40 °C or less
(PW482)
8 years
No
220 V AC:
Average ambient temperature 40 °C or less
(PW484)
8 years
No
24 V DC:
Average ambient temperature 40 °C or less
Built-in power fuse
—
8 years
No
For PW481, PW482, PW484
l
AVR10D, AW810D
Table Periodic Replacement Parts Having Defined Life Spans
Part names
Part
numbers
Recommended
replacement
cycle
Replacement
by user
Remarks
Power supply module
PW441
8 years
Yes
100 - 120 V AC:
Average ambient temperature 40 °C or less
PW442
8 years
Yes
220 - 240 V AC:
Average ambient temperature 40 °C or less
PW444
8 years
Yes
24 V DC:
Average ambient temperature 40 °C or less
Aluminium Electrolytic
Capacitor
(in power supply
module)
(PW441)
8 years
No
100 V AC:
Average ambient temperature 40 °C or less
(PW442)
8 years
No
220 V AC:
Average ambient temperature 40 °C or less
(PW444)
8 years
No
24 V DC:
Average ambient temperature 40 °C or less
Built-in power fuse
—
8 years
No
For PW441, PW442, PW444