3. Cabling
3-99
TI 33J01J10-01EN
Elements of the shunt resistor unit
The following figure shows the elements of the shunt resistor unit.
F030832.ai
Cables
Cover
Slots
Terminal block
(Corresponds to
channels 1 to 4
from the top)
Shunt resistor
module
Short plug
Figure Shunt resistor unit
The shunt resistor unit has terminal blocks for channel numbers 1 to 4. Each terminal block is
provided with two slots that are used to install a shunt resistor module or a short plug. Short plugs
are installed on these slots when the unit is shipped from the factory. The shunt resistor unit
comes with shunt resistor modules and cables for connecting the shunt resistor unit and the nest
for I/O adaptor as accessories.
Installation and wiring for the shunt resistor unit
CAUTION
Handle shunt resistor module in A2EXR001 with care as it may become high in temperature. Use
a cover to prevent from touching the resistor directly to avoid being burned.
Oct. 5, 2018-00