![YOKOGAWA CENTUM CS Скачать руководство пользователя страница 186](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927186.webp)
3. Cabling
3-88
TI 33J01J10-01EN
n
A2SAT105 mV/TC/RTD input adaptor
The following figure shows the signal wiring when using the mV/TC/RTD input adaptor
A2SAT105 is unavailable for A2BN3D-
9
.
When connnecting a TC input or mV input
When connnectinga an RTD input
When connnecting a potentiometer input
F030721.ai
A
B
C
D
‒
+
A
B
C
D
A
B
C
D
0%
100%
Figure When using the mv/TC/RTD input adaptor
For thermocouple signalinput,mountthemV/TC/RTD input adaptor on the base plate for adaptor
with RJC.
SEE
ALSO
For more information about the types of TC and RTD that can be connected to the mV/TC/RTD input adaptor and
the standards they must conform to, refer to:
"I/O Adaptors (for N-IO)" (GS 33J62F30-01EN).
n
A2SDV105 Digital input adaptor
The following figure shows the signal wiring for the base plate when you use the digital input
adaptor. The dry contact input is not supported for A2BN3D-
9
. For the dry contact input,
it is necessary to change the adaptor to A2SMX801 and set the DI mode by software for the
connection between terminal-A and B. In that case, it becomes non-isolated from an I/O module.
If you connect a dry contact input, connect the field power supply to the base plate.
F030713.ai
+
‒
+
‒
A
B
C
D
A
B
C
D
Connect voltage input
Connect no-voltage contact input
:
1 to 16
Figure When Using the digital Input Adaptor
n
A2SDV505 Digital output adaptor
The following figure shows the signal wiring to the base plate when you use the digital output
adaptor.
When you use the digital output adaptor, connect the field power supply to the base plate.
F030714.ai
A
B
C
D
‒
+
: Load
:
1 to 16
Figure When Using the digital output adaptor
Oct. 5, 2018-00
Содержание CENTUM CS
Страница 2: ...Blank Page...
Страница 246: ...Blank Page...