1. System Installation Requirements
1-10
TI 33J01J10-01EN
l
Standards for Hazardous Location Equipment
For more information about Standard for Hazardous Locations, please refer to TI 33Q01J30-01E.
[CSA Non-Incendive] (*1)
[FM Nonincendive] (*2)
[Type n] (*3)
[Type i (Intrinsic Safety)]
[ATEX Type i]
[IECEx Type i]
[FM Intrinsic Safety]
Note: In relation to the CE Marking, the manufacturer and the authorized representative for CENTUM in the EEA are indicated below:
Manufacturer: YOKOGAWA Electric Corporation
(2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan.)
Authorised representative in the EEA: Yokogawa Europe B.V.
(Euroweg 2, 3825 HD Amersfoort, The Netherlands.)
*1:
To meet a standard for hazardous location equipment, the 19-inch rack-mounted devices must be installed in a keyed metallic
cabinet approved by CSA or non-incendive regulator in your area.
Use a cabinet which is larger than the size of W600×H760×D350 (mm) to mount a FIO node unit on.
*2:
To meet a standard for hazardous location equipment, the 19-inch rack-mounted devices must be installed in a keyed metallic
cabinet approved by FM or Nonincendive regulator in your area.
*3:
To be compatible with Type n, for example the requirements of cabinet must be met. For details, refer to the Explosion Protection
(TI 33Q01J30-01E).
l
Marine Standards
For more infomation about the marine standards, refer to 1.8, “Compliance with Marine
Standards.”
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
LR (Lloyd’s Register)
DNV GL