1. System Installation Requirements
1-9
TI 33J01J10-01EN
n
Applied Standards
The CENTUM VP system complies with the standards shown below.
IMPORTANT
Different standards are applied according to the types of equipment. For details, refer to
Integrated Production Control System CENTUM VP System Overview (GS 33J01A10-01EN).
l
Safety Standards (*1) (*2) (*3) (*4)
[CSA]
CAN/CSA-C22.2 No.61010-1, No.61010-2-030
CAN/CSA-IEC 61010-2-201
[CE Marking] Low Voltage Directive
EN 61010-1, EN 61010-2-201, EN 61010-2-030
EN 60825-1
[EAC Marking]
CU TR 004
l
EMC Conformity Standards (*3) (*5) (*6)
[CE Marking] EMC Directive
EN 55011 Class A Group 1 (*7)
EN 61000-6-2
EN 61000-3-2 (*8)
EN 61000-3-3
EN 61326-1 (*9)
[RCM]
EN 55011 Class A Group 1 (*7)
[KC Marking]
Korea Electromagnetic Conformity Standard
[EAC Marking]
CU TR 020
Note: In relation to the CE Marking, the manufacturer and the authorized representative for CENTUM in the EEA are indicated below:
Manufacturer: YOKOGAWA Electric Corporation
(2-9-32 Nakacho, Musashino-shi, Tokyo 180-8750, Japan.)
Authorised representative in the EEA: Yokogawa Europe B.V.
(Euroweg 2, 3825 HD Amersfoort, The Netherlands.)
*1:
For ensuring all the hardware devices to satisfy the safety standards, the dedicated breakers in the power supply distribution board must
conform to the following specifications.
[CSA] CSA C22.2 No.5 or UL 489
[CE Marking] EN 60947-1 and EN 60947-3
[EAC Marking] EN 60947-1 and EN 60947-3
*2: The ground suitable for the power distribution system in the country or region has to be used for protective grounding system.
*3:
For the rack mountable devices, DIN rail mountable devices, and wall mountable devices to meet the Safety Standards and EMC Standards,
the devices must be installed in a lockable metal cabinet. The cabinet must conform to IEC/EN/CSA 61010-2-201 or provide degrees of
protection IP3X or above and IK09 or above.
*4: CENTUM measurement input corresponds to the measurement category O (Other) based on IEC/EN 61010-2-030 and CAN/CSA-C 22.2
No. 61010-2-030. The measurement category I defined in IEC/EN 61010-1: 2001 and CAN/CSA-C 22.2 No. 61010-1-04 has been changed
to O (Other).
*5:
A lightening arrester or the like is required to meet this surge immunity standard except for A2ZN3D, A2ZN4DC, and A2ZN5DC.
The length of the cable to feed the external power supply for AGS813 AO channels should not exceed 30 meters.
*6:
To the field power supply input connector of the base plate for adaptor A2BN3D and the barrier power supply input connector of the base
plates for barrier A2BN4D and A2BN5D, power must not be supplied directly from a DC distribution network.
*7:
A Class A hardware device is designed for use in the industrial environment. Please use this device in the industrial environment only.
*8:
An external device such as a power unit with harmonic current neutralizer and an active harmonics conditioner must be connected to meet
this harmonic current emission standard. See Section 1.3 “Power Supply System”.
*9:
The base plate for barrier A2BN5D conforms to EN 61326-1. If A2BN5D is used with intrinsic safety barriers for analog input, analog output,
or temperature input mounted, the accuracy under the electromagnetic immunity conditions (acceptance criteria A) is within ±1 % of the
span.
Mar. 29, 2019-00