![YOKOGAWA CENTUM CS Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927024.webp)
1. System Installation Requirements
1-12
TI 33J01J10-01EN
Item
Specifications (except
for ANB10
, ANB11
,
and ANT10U)
Specifications
(ANB10
, ANB11
and ANT10U)
Specifications
(N-IO node)
(*1)
Remarks
Power
source
Insulation
resistance
20 Mohms at 500 V DC
20 Mohms at 500 V DC
20 Mohms at 500 V DC
Between power
and grounding
terminals
Grounding
Apply the grounding
system which is
defined by the rules
and standards of the
country or the region.
Apply the grounding
system which is
defined by the rules
and standards of the
country or the region.
Apply the grounding
system which is
defined by the rules
and standards of the
country or the region.
–
Noise
Electric field
3 V/m or less
(26 MHz to 1.0 GHz)
3 V/m or less (1.4 to
2.0 GHz)
1 V/m or less (2.0 to
2.7 GHz)
3 V/m or less
(26 MHz to 1.0 GHz)
3 V/m or less (1.4 to
2.0 GHz)
1 V/m or less (2.0 to
2.7 GHz)
10 V/m or less
(80 MHz to 1.0 GHz)
3 V/m or less (1.4 to
2.0 GHz)
1 V/m or less (2.0 to
2.7 GHz)
–
Magnetic field
30 A/m or less (AC)
400 A/m or less (DC)
30 A/m or less (AC)
400 A/m or less (DC)
30 A/m or less (AC)
400 A/m or less (DC)
Earth magnetism
not included in DC
magnetic field
Static electricity
4 kV or less (direct
discharge)
8 kV or less (aerial
discharge)
4 kV or less (direct
discharge)
8 kV or less (aerial
discharge)
4 kV or less (direct
discharge)
8 kV or less (aerial
discharge)
In accordance with
IEC 61000-4-2
Vibration
Vibration
Displacement amplitude:
0.25 mm or less (1 to 14
Hz) Acceleration: 2.0 m/s
2
or less (14 to 100 Hz)
Displacement amplitude:
0.25 mm or less (1 to 14
Hz) Acceleration: 2.0 m/s
2
or less (14 to 100 Hz)
Continuous tremor
amplitude:
1.75 mm or less (5 to 8.4
Hz) Acceleration: 4.9 m/s
2
or less (8.4 to 150 Hz)
Discontinuous vibration
amplitude:
3.5 mm or less (5 to 8.4
Hz) Acceleration: 9.8 m/s
2
or less (8.4 to 150 Hz)
Quake resistance
4.9 m/s
2
or less
4.9 m/s
2
or less
4.9 m/s
2
or less
Vibration during
transportation
For cabinets:
Horizontal: 2.9 m/s
2
or
less
Vertical: 4.9 m/s
2
or less
For others:
Horizontal: 4.9 m/s
2
or
less Vertical: 9.8 m/s
2
or less
Horizontal: 4.9 m/s
2
or
less Vertical: 9.8 m/s
2
or less
Horizontal: 4.9 m/s
2
or
less Vertical: 9.8 m/s
2
or less
In packed condition
Impact
Transportation
impact
Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
147 m/s
2
or less,
11 ms
In packed condition
Dust
0.3 mg/m
3
or less
0.3 mg/m
3
or less
0.3 mg/m
3
or less
–
Corrosive gas
Ordinary office level
In case of AFF50
/
ISA S71.04.G2
(ISA G3 option: ISA
S71.04.G3)
ISA S71.04 G2
(ISA G3 option: ISA
S71.04 G3)
ISA S71.04 G2
(ISA G3 option: ISA
S71.04 G3)
–
Altitude
2000 m or less
2000 m or less
3000 m or less (*7)
*1: Except for equipment for RIO System Upgrade.
For specification of RIO System Upgrade, refer to the GS 33J64E10-01EN.
*7:
When the Node Interface Unit (A2NN30D) with the following optical ESB bus specifications is used at an altitude of 2000 m
or higher, the ambient temperature range is -40 to 60°C.
A2NN30D-
01
A2NN30D-
02
A2NN30D-
10
A2NN30D-
11
A2NN30D-
12
A2NN30D-
20
A2NN30D-
21
A2NN30D-
22
SEE
ALSO
For the level of corrosive gases permitted in an ordinary office, refer to “Guidelines for Installation Environment”
(TI 33Q01J20-01E).
Table Equipment Installation Specifications (2/2)
Oct. 5, 2018-00
Содержание CENTUM CS
Страница 2: ...Blank Page...