![YOKOGAWA CENTUM CS Скачать руководство пользователя страница 160](http://html1.mh-extra.com/html/yokogawa/centum-cs/centum-cs_technical-information_910927160.webp)
3. Cabling
3-62
TI 33J01J10-01EN
Table Signal Cables for Connection with FIO (2/3)
Module
Name
I/O channels
per Module
Connection Signal
Pressure
Clamp
Terminal
Yokogawa-
specific
Cable (*1)
MIL
Cable
Digital I/O Modules
ADV151 Digital Input Module (24 V DC, 4.1 mA)
32
x
x
x
ADV551 Digital Output Module (24 V DC, 100 mA)
32
x
x
x
ADV161 Digital Input Module (24 V DC, 2.5 mA)
64
–
x (*2)
x
ADV561 Digital Output Module (24 V DC, 100 mA)
64
–
x (*2)
x
ADV859
Digital I/O Module for Compatible ST2
(Isolated Channels)
16 input
/16 output
–
x (*2)
–
ADV159 Digital Input Module for Compatible ST3
(Isolated Channels)
32
–
x (*2)
–
ADV559 Digital Output Module for Compatible ST4
(Isolated Channels)
32
–
x (*2)
–
ADV869
Digital I/O Module for Compatible ST5
(Common Minus Side Every 16-Channel)
32 input
/32 output
–
x (*2)
–
ADV169 Digital Input Module for Compatible ST6
(Common Minus Side Every 16-Channel)
64
–
x (*2)
–
ADV569 Digital Output Module for Compatible ST7
(Common Minus Side Every 16-Channel)
64
–
x (*2)
–
Communication Modules
ALR111 RS-232C Communication Module
(1200 bps to 115.2 kbps)
2 port
–
x (D-SUB9
pin) (*2)
–
ALR121
RS-422/RS-485 Communication Module
(1200 bps to 115.2 kbps)
2 port
–
x (M4
terminal
block
5-pole) (*2)
–
ALE111
Ethernet Communication Module (10 Mbps)
1 port
–
x (RJ-45)
(*2)
–
ALF111
Foundation Fieldbus (FF-H1) Communication Module
(31.25 kbps)
4 port
x
x (*2)
–
ALP111
PROFIBUS-DP Communication Module
1 port
–
x (*2)
–
ALP121
PROFIBUS-DP Communication Module (for FIO)
1 port
–
x (*2)
–
x :
Can be connected.
– :
Cannot be connected.
*1:
Yokogawa-specific cable for connecting I/O Module and a terminal board, etc.
*2:
Can be connected directly with a Yokogawa-specific cable, without a terminal block.