<6.  PARAMETER DESCRIPTION>

6-12

IM 01E30D01-01EN

(9)  Item J (Menu J): Auxiliary Function Setting items

Menu J contains setting items such as the flow direction, rate limits, and low cut.

Item 

Name 

R/W 

Data range 

Units 

Position 

of decimal 

point 

Default value 

(*): Indicated item 

Description

Display unit

(BRAIN) 

Display unit

/BRAIN 

J00  Aux 

(AUX) 

J10  4-20mA Low Cut 

(4-20 LOW CUT) 

0 to 20 

3% 

Sets the range in vicinity of 0% 

within which the current output 

will be 4 mA. 

J11  4-20mA Low Lmt 

(4-20 LOW LMT) 

-1.25 to 100.00 

-1.25% 

Sets the low limit for current 

output 

J12  4-20mA High Lmt 

(4-20 HI LMT) 

0.0 to 103.13 

103.13% 

Sets the high limit for current 

output 

J15  Pls Special Mode 

(PLS SPECIAL) 

Normal 

Pulse Only 

Normal 

Selects the pulse special mode 

J20  Flow Direction 

(FLOW DIRECT) 

Forward 

Reverse 

Forward 

Selects the flow direction. 

J21  Rate Limit 

(RATE LIMIT) 

0 to10 

5% 

Sets the level to reduce output 

fluctuation. 

J22  Dead Time 

(DEAD TIME) 

0 to 15 

0s 

Sets the dead time to reduce 

output fluctuation. When “0” 

is set, rate limit function is not 

available. 

J23  Pulsing Flow 

(PULSING FLOW) 

No 

Yes 

No 

Selects whether pulsing flow is 

to be supported. 

J25  T/P Damp Select 

(T/P DAMP SEL) 

Damping 

No Damping 

Damping 

Selects whether the flow 

rate value obtained through 

damping calculation for total/

pulse or the instantaneous flow 

rate value (no damping) for 

total/pulse is to be used. 

J30  Basic Frequency 

(BASIC FREQ) 

Freq(1) 

Freq(2) 

Freq(1) 

Selects the basic frequency 

J35  Memo 1 

(MEMO 1) 

ASCII 16 characters 

Memo field 

J36  Memo 2 

(MEMO 2) 

ASCII 16 characters 

Memo field 

J37  Memo 3 

(MEMO 3) 

ASCII 16 characters 

Memo field 

J40  MS Code 1 

(MS CODE 1) 

ASC II 16 characters 

Sets MS code 1 

J41  MS Code 2 

(MS CODE 2) 

ASCII 16 characters 

Sets MS code 2 

J42  MS Code 3 

(MS CODE 3) 

ASCII 16 characters 

Sets MS code 3 

J43  MS Code 4 

(MS CODE 4) 

ASCII 16 characters 

Sets MS code 4 

J44  MS Code 5 

(MS CODE 5) 

ASCII 16 characters 

Sets MS code 5 

J45  MS Code 6 

(MS CODE 6) 

ASCII 16 characters 

Sets MS code 6 

J50  Software Rev No 

(SOFTWARE REV) 

— 

Software revision number 

J60  — 

(SELF CHECK) 

Good 

Error 

Read Section 6.5 “Alarm 

Functions”. 

Содержание ADMAG AXR

Страница 1: ...User s Manual AXR Two wire Magnetic Flowmeter Integral Flowmeter Style S2 IM 01E30D01 01EN IM 01E30D01 01EN 8th Edition ...

Страница 2: ...andling Precautions 3 3 3 2 1 General Precautions 3 3 3 2 2 Flowmeter Piping 3 4 3 3 Mounting Procedures 3 5 3 3 1 Nominal Diameter 25 mm 1 0 in to 40 mm 1 5 in Wafer Type 3 5 3 3 2 Nominal Diameter 50 mm 2 0 in to 200 mm 8 0 in Wafer Type 3 7 3 3 3 Nominal Diameter 25 mm 1 0 in to 200 mm 8 0 in Flange Type 3 10 3 3 4 Gaskets Size 3 13 4 WIRING 4 1 4 1 Wiring Precautions 4 1 4 2 Terminal Configura...

Страница 3: ...n 7 3 7 2 2 The data update and upload download function of BT200 7 4 7 2 3 BT200 Screens Flow Rate Data Display 7 4 7 3 Parameter Setting Using a BT200 7 5 7 3 1 BT200 Setting of Selection Type Data Flow rate units 7 6 7 3 2 BT200 Setting of Numeric Type Data Flow rate span 7 7 7 3 3 BT200 Setting of Alphanumeric Type Data Tag number 7 8 8 OPERATION VIA HART CONFIGURATION TOOL HART 5 8 1 8 1 HART...

Страница 4: ... 5 9 8 3 Burst Mode 9 6 9 8 4 Multidrop Mode 9 10 9 8 5 Switching HART Protocol Revision 9 11 9 8 6 Other operations for the HART configuration tool 9 11 9 9 Menu Tree for DD and DTM HART 7 9 12 10 ACTUAL OPERATION 10 1 10 1 Pre operation Zero Adjustment 10 1 11 MAINTENANCE 11 1 11 1 Changing Direction of Electrical Connection 11 1 11 2 Components Replacement 11 2 11 2 1 Display Unit Replacement 1...

Страница 5: ...rumented Systems Installation A1 1 A1 1 Scope and Purpose A1 1 A1 2 Using the AXR for an SIS Application A1 1 A1 2 1 Safety Accuracy A1 1 A1 2 2 Diagnostic Response Time A1 1 A1 2 3 Setup A1 1 A1 2 4 Required Parameter Settings A1 1 A1 2 5 Proof Testing A1 1 A1 2 6 Repair and Replacement A1 2 A1 2 7 Startup Time A1 2 A1 2 8 Firmware Update A1 2 A1 2 9 Reliability Data A1 3 A1 2 10 Lifetime Limits ...

Страница 6: ...ure the accuracy of the contents of this manual However if any errors or omissions are found please inform Yokogawa Yokogawa assumes no responsibilities for this product except as stated in the warranty Please note that this user s manual may not be revised for any specification changes construction changes or operating part changes that are not considered to affect function or performance There i...

Страница 7: ...through accidentally dropping it or by exerting excessive force on the magnetic flowmeter When moving the magnetic flowmeter always use a trolley and have at least two people carry it When the magnetic flowmeter is processing hot fluids the instrument itself may become extremely hot Take sufficient care not to get burnt Where the fluid being processed is a toxic substance avoid contact with the fl...

Страница 8: ... up of dirt dust or other substances on the display panel glass or name plate If these surfaces do get dirty wipe them clean with a soft dry cloth 5 Explosion Proof Type Instrument WARNING Magnetic flowmeters with the model name AXR C are products which have been certified as explosion proof type instruments Strict limitations are applied to the structures installation locations external wiring wo...

Страница 9: ...es Damage due to negligence or insufficient maintenance on the part of the customer Problems or damage resulting from handling operation or storage that violates the intended use and specifications Problems that result from using or performing maintenance on the instrument in a location that does not comply with the installation location specified by Yokogawa Problems or damage resulting from repa...

Страница 10: ... 1 INTRODUCTION 1 5 IM 01E30D01 01EN 1 3 ATEX Documentation This is only applicable to the countries in European Union GB DK I E NL SF P F D S LT LV PL EST SLO H BG RO M CZ SK GR ...

Страница 11: ...ter Type 2 2 Accessories Check that the parts shown below are included in the package Centering device wafer type only 1 pc Plug 1 pc 2 3 Storage Precautions If the instrument is to be stored for a long period of time after delivery observe the following points The instrument should be stored in its original packing condition in the storage location Select a storage location that fulfils the follo...

Страница 12: ...ntilation Atmospheric Condition Avoid installing the instrument in a corrosive atmosphere In situations where this is unavoidable consider ways to improve ventilation and to prevent rainwater from entering and being retained in the conduit pipes Vibrations or Shocks Avoid installing the instrument in a place subject to shocks or vibrations Explosion proof type Explosion proof types can be installe...

Страница 13: ...f at least 5D between them Gate valve fully open Reducer pipe 5 D or more 2 D or more 2 D or more 2 D or more 10 D or more 10 D or more 5 D or more 5 D or more 0 is allowable 0 is allowable 0 is allowable 0 is allowable F0301 ai Tee 90 degree bent Various valves Expander pipe D Flowtube Size Figure 3 1 1 Required Lengths of Straight Runs 1 Do not install anything in the vicinity that may interfere...

Страница 14: ...fully filled with liquids IMPORTANT If the pipe is empty the output fluctuates or the Process Alarm Signal Overflow occurs The pipe must be fully filled with liquid Piping shall be designed so as to maintain the interior of the flowtube filled with fluids Vertical mounting is effective in such cases as when fluids tend to separate or solid matter may be precipitated When employing vertical mountin...

Страница 15: ...n application 3 2 Handling Precautions WARNING The magnetic flowmeter is a heavy instrument Be careful that no damage is caused to personnel through accidentally dropping it or by exerting excessive force on the magnetic flowmeter When moving the magnetic flowmeter always use a trolley and have at least two people carry it 3 2 1 General Precautions 1 Precaution during Transportation The magnetic f...

Страница 16: ...ons as mentioned above and the inside of the terminal box at least once a year Also due to rain etc when it is suspected that water may have penetrated into the inside flowmeter perform supplementary inspections 3 2 2 Flowmeter Piping CAUTION Misaligned or slanted piping can lead to leakage and damage to the flanges 1 Correct any misaligned or slanted piping and any gaps that may exist between mou...

Страница 17: ... flowmeter IMPORTANT If it is impossible to match the direction of the arrow mark the direction of the electrical connection can be changed Read Section 11 1 to do this properly In case the fluid being measured flows against the arrow direction read the parameter J20 Flow Direction in this user s manual 2 Mounting Centering Devices To maintain concentricity of the flowmeter with the pipes install ...

Страница 18: ...S 20K ANSI Class 300 and DIN PN16 DIN PN40 25 1 0 23 5 to 27 3 239 6 to 278 4 208 to 241 6 23 7 to 27 3 241 7 to 278 4 209 8 to 241 6 22 3 to 27 3 227 4 to 278 4 197 4 to 241 6 40 1 5 36 2 to 42 4 369 1 to 432 4 320 4 to 375 3 36 9 to 42 4 376 3 to 432 4 326 6 to 375 3 39 1 to 42 4 398 7 to 432 4 346 1 to 375 3 Table 3 3 2 Wafer Type Tightening Torque Values for PVC Piping Tightening torque values...

Страница 19: ...er so that the flow direction of the fluid to be measured is in line with the direction of the arrow mark on the flowmeter IMPORTANT If it is impossible to match the direction of the arrow mark the direction of the electrical connection can be changed Read Section 11 1 to do this properly In case the fluid being measured flows against the arrow direction read this parameter J20 Flow Direction in t...

Страница 20: ...e ratings Size mm inch JIS 10K ANSI Class 150 DIN PN10 JIS20K ANSI Class 300 DIN PN16 DIN PN40 JIS F12 JIS 75M 50 2 0 45 0 to 56 8 4 58 9 to 579 2 398 3 to 502 7 45 0 to 56 8 458 9 to 579 2 398 3 to 502 7 22 5 to 25 9 229 4 to 264 1 199 1 to 229 2 22 5 to 25 9 229 4 to 264 1 199 1 to 229 2 50 0 to 57 5 509 9 to 586 3 442 5 to 508 9 65 2 5 61 3 to 70 5 625 1 to 718 9 542 5 to 624 0 61 3 to 70 5 625...

Страница 21: ...e Tightening Torque Values for Metal Piping and Permeable Fluids Tightening torque values for PFA lining type Unit N m kgf cm in lbf Gasket types within flowtube No gasket standard Gasket types for user s flange PTFE sheathed non asbestos gasket optional code BSF or the equivalent in hardness Flange ratings Size mm inch JIS 10K ANSI Class 150 DIN PN10 JIS20K ANSI Class 300 DIN PN16 DIN PN40 JIS F1...

Страница 22: ...h the direction of the arrow mark on the flowmeter IMPORTANT If it is impossible to match the direction of the arrow mark the direction of the electrical connection can be changed Read Section 11 1 to do this properly In case the fluid being measured flows against the arrow direction read the parameter J20 Flow Direction in this user s manual 2 Tightening Nuts Tighten the bolts according to the to...

Страница 23: ... 3 246 0 to 283 2 27 8 to 32 0 283 5 to 326 3 246 0 to 283 2 23 2 to 26 7 236 6 to 272 3 205 3 to 236 3 65 2 5 41 6 to 47 8 424 2 to 487 4 368 2 to 423 0 41 6 to 47 8 424 2 to 487 4 368 2 to 423 0 19 5 to 28 5 198 8 to 290 6 172 6 to 252 2 19 5 to 28 5 198 8 to 290 6 172 6 to 252 2 41 4 to 47 6 422 2 to 485 4 366 4 to 421 3 28 8 to 33 1 293 7 to 337 5 254 9 to 293 0 80 3 0 23 2 to 26 7 236 6 to 27...

Страница 24: ... to 247 8 129 2 to 215 1 16 1 to 26 9 164 2 to 274 3 142 5 to 238 1 Table 3 3 11 Flange Type Tightening Torque Values for Metal Piping and Permeable Fluids Tightening torque values for PFA lining type Unit N m kgf cm in lbf Gasket types within flowtube No gasket standard Gasket types for user s flange Non asbestos gasket PTFE sheathed non asbestos gasket or the equivalent in hardness Flangeratings...

Страница 25: ...6 84 3 31 80 3 0 77 3 03 114 4 49 90 3 54 100 4 0 102 4 02 140 5 51 115 4 53 150 6 0 146 1 5 75 190 7 48 167 6 57 200 8 0 193 6 7 62 240 9 45 218 8 58 Lay length code 2 Unit mm in Size PFA lining Wafer Inner Diameter of Grounding Ring øA Outer Diameter for Effective Sealing øB Recommended Inner Diameter of Gasket Flat Gasket øC PTFE sheathed Non asbestos Gasket øD 25 1 0 28 1 10 53 2 09 35 1 38 40...

Страница 26: ... tube 16 JIS C 8305 or flexible conduit tubes 15 JIS C 8309 Keep the conduits or flexible tubes watertight using sealing tape When waterproof glands or union equipped waterproof glands are used avoid tightening the glands with an excessive torque A plug is provided Use this plug to cover the unused wiring port when wiring the instrument with only one Be sure to turn the power off before opening th...

Страница 27: ...ufacturer of the crimp terminal you want to use to connect the crimp terminal and cable Use crimp tools that are appropriate for the diameter of the cable to be connected 4 3 Wiring Ports This instrument is of watertight construction as stipulated in JIS C0920 It is shipped with a wiring bracket waterproof gland or waterproof gland with union or a plastic gland attached only in cases where an opti...

Страница 28: ... or flexible pipes G1 2 only Cable G1 2 Figure 4 3 2 Waterproof Gland with Union Joint Optional code EU Plastic gland Gasket F0405 ai Figure 4 3 3 Plastic Gland Optional code EP 3 Conduit Wiring When wiring the conduits pass the conduit through the wiring connection port and utilize the waterproof gland to prevent water from flowing in Place the conduit pipe on an angle as shown in Figure 4 3 4 In...

Страница 29: ...rounding can have an adverse effect on the flow measurement Ensure that the instrument is properly grounded The electromotive force of the magnetic flowmeter is minute and it is easily affected by noise and the reference electric potential is the same as that of the measuring fluid Therefore the reference electric potential terminal potential of the flowtube and converter also need to be the same ...

Страница 30: ... In case grounding rings are used Hazardrous area Grounding ring Non hazardrous area Class A grounding In case grounding rings are not used Available only for metal piping TIIS Explosion Proof Type TIIS Explosion Proof Type Grounding resistance of 10 Ω or less is necessary for class A grounding terminal Grounding resistance of 100 Ω or less is necessary for Functional grounding terminal When the o...

Страница 31: ...figuration General purpose Use Explosion Proof Type except TIIS When the cover is removed the connection terminals will be visible F0412 ai SUPPLY DO Figure 4 5 2 Terminal Configuration The description of the terminal symbols is shown in Table 4 5 1 Table 4 5 1 Terminal Symbols No Terminal Symbols Description Functional grounding SUPPLY Power supply and current output DO Digital output One output ...

Страница 32: ...0415 ai SUPPLY DO Power supply cable Figure 4 6 2 Electric Cable Wiring TIIS Explosion Proof Type IMPORTANT Connecting with the commercial AXR power supply will damage the flowmeter Be sure to use the DC power supply in the predetermined range Do not connect power supply with reversed polarities SUPPLY terminal connect SUPPLY terminal connect NOTE Supply voltage means the voltage necessary to prov...

Страница 33: ... other Power line 15 cm 6 in or more Avoid parallel wiring Input Impedance of Communicating Device 10 kΩ or more at 2 4 kHz 600 250 14 7 20 6 28 9 42 Power supply voltage E V DC R 0 0236 E 14 7 F0416 ai Digital Communication Range BRAIN or HART External Load Resistance R Ω Figure 4 6 3 Relationship between Power supply voltage and external load resistance HART Communication signal HART communicati...

Страница 34: ...transistor contact output IMPORTANT Precaution for Pulse Output As this is a transistor contact insulated type give attention to proper voltage and polarity when wiring Do not apply a voltage larger than 30 V DC or a current larger than 120 mA in order to prevent damage to the instrument When input filter constant of the electronic counter is large in relation to the pulse width the signal will de...

Страница 35: ... from the DO terminal parameters must be set Read Chapter 6 in this manual 3 Simultaneous Current Pulse Output When simultaneous output of current and pulse output are used no communication is possible in some cases Read Table 4 6 3 or Table 4 6 6 as wiring examples Read 2 for specifications and precautions of the pulse output 4 The Wiring of Digital External Indicator Using Current Output Read Ta...

Страница 36: ...voltage requires a power source with a maximum output current of no less than E3 R Electric counter Pulse Output In this case No communication is possible when a three wire cable is used R E4 0 0236 R1 R2 14 7 E4 V 30 7 2 This supply voltage requires a power source with a maximum output current of no less than E4 R 0 0236 SUPPLY DO AXR Terminal Electric counter 6 2 Cable Resistance R2 Ω 9 Cable Re...

Страница 37: ...two wire shielded cables separately for SUPPLY and DO E1 AXR Terminal E3 30 V DC max 0 0236 x R1 R2 R3 14 7 E1 V 42 10 In the case of R3 250 Ω 0 0236 x R1 R2 20 6 E1 V 42 10 8 7 6 Cable Resistance R1 Ω 9 Cable Resistance R2 Ω 9 Electric counter R3 Ω Load Resistance 4 4 This supply voltage requires a power source with a maximum output current of no less than E3 R Example 3 In this case No communica...

Страница 38: ... 9 Cable Resistance R2 Ω 9 Transmission of AXR output might fail when the external indicator breakdown occurs SUPPLY DO Distributor etc R3 AXR Terminal E1 Analog External Indicator Relaying terminal Internal resistance 10 Ω or less 0 0236 R1 R2 R3 R4 10 14 7 E1 V 42 10 In the case of R3 250 Ω 0 0236 R1 R2 R4 10 20 6 E1 V 42 10 R3 Ω Load Resistance 6 To avoid the influence of external noise use an ...

Страница 39: ...azardous area 1 This supply voltage requires a power source with a maximum output current of no less than E3 R Grounding resistance of 100 Ω or less When the optional code A is selected grounding resistance of 10 Ω Pulse Output In this case No communication is possible when a four wire cable is used Cable Resistance R1 Ω 9 Cable Resistance R2 Ω 9 R E4 0 0236 R1 R2 14 7 E4 V 30 7 AXR Terminal Elect...

Страница 40: ... example use two wire shielded cables separately for SUPPLY and DO E1 AXR Terminal E3 30 V DC max 8 7 6 3 3 This supply voltage requires a power source with a maximum output current of no less than E3 R Electric counter R3 Ω Load Resistance JIS Class A SUPPLY DO 0 0236 x R1 R2 R3 14 7 E1 V 42 10 In the case of R3 250 Ω 0 0236 x R1 R2 20 6 E1 V 42 10 Cable Resistance R1 Ω 9 Cable Resistance R2 Ω 9 ...

Страница 41: ... resistance R for the pulse output The range of load resistance R for the pulse output must basically be 1 kΩ and 2 W The load resistance should be selected by calculation as shown below when proper transmission is impossible due to the length of cable or frequency of pulse output P mW 2 R kΩ E2 V R kΩ 1 120 E V C μF f kHz 0 1 E Supply voltage V f Frequency of pulse output kHz R Value of load resi...

Страница 42: ...ying terminal Transmission of AXR output might fail when the external indicator breakdown occurs Cable Resistance R1 Ω 9 Cable Resistance R2 Ω 9 Hazardous area Non hazardous area Grounding resistance of 100 Ω or less When the optional code A is selected grounding resistance of 10 Ω 6 To avoid the influence of external noise use an electric counter which fits to the pulse frequency 7 Resistor is no...

Страница 43: ...ton Switches Open the cover when operating push button switches Read Section 11 2 for details on opening the cover Do not open the cover in wet weather or high humidity in order to prevent condensation The push button switches cannot be used in these conditions as the cover would need to be opened In this case use magnet switches to set parameters Do not touch the push button switches with wet or ...

Страница 44: ...isplays the instantaneous flow rate for the span as a percentage Actual instantaneous flow rate FR Displays the actual reading for instantaneous flow rate Instantaneous flow rate mA FR Displays the instantaneous flow rate for the span as a current output value Bar graph indicating instantaneous flow rate None Displays the instantaneous flow rate for the span as a percentage using bar graph Totaliz...

Страница 45: ...rameter Search Mode Major Item Parameter Search Mode Sub item Parameter Search Mode Parameter Replacement Mode Setting modes F0502 EPS The term mode is used to read a situation where display and setting are possible Select Yes ESC ESC ESC SET SET SET Sample Display Procedure for moving from Display Mode to Setting Mode 100 0 FR FTL 3274m3 0 100 m3 h ESC SET SET DEC SHIFT INC SET ESC INC DEC SHIFT ...

Страница 46: ...entrying the Setting Mode again within 1 minute after returning from Setting Mode to Display Mode When Yes has been selected touch the SET switch NOTE When no operations in this display are carried out for 20 seconds the system will automatically return to the Display Mode When the operations except SET switch are carried out the system will automatically return to the Display Mode In order to req...

Страница 47: ... tag numbers special units and the like With this format setting can be carried out using up to 16 of the characters shown below Regarding the alphanumeric type format iii the following alphanumerics are displayed in the following sequence 0123456789 ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz space 5 3 Parameter Setting Procedure Once the system is in Setting Mode the parameters for sett...

Страница 48: ...meter Search Mode has been accessed in this screen Touch the INC switch to move the cursor to B21 Base Flow Unit The cursor has been moved to B21 Base Flow Unit in this screen Sub item selection screen A In this screen Parameter Replacement Mode has been called up using the SET switch Touch the INC switch to move the cursor to the unit item for selection In this example the INC switch is touched t...

Страница 49: ...g items to those being currently displayed may also be selected Use the INC switch to cycle through these items Sub Item Parameter Search Mode has been accessed in this screen Touch the INC switch to move the cursor to B23 Flow Span The cursor has been moved to B23 Flow Span in this screen Sub item selection screen B Touch the SET switch to access Parameter Replacement Mode Once Parameter Replacem...

Страница 50: ...de the valid selection range the message Out of range Touch any key will be displayed In such a case touch any switch to return to Parameter Replacement Mode and redo the setting NOTE If more than one decimal point has been input the message Invalid value Touch any key will be displayed In such a case touch any switch to return to Parameter Replacement Mode and redo the setting 5 3 3 Setting Examp...

Страница 51: ...he cursor will flash on and off on the left of the tag number As FI 1201 is to be setup in this example touch the DEC SHIFT switch to move the cursor to the position for multiples of 100 At the position for multiples of 100 touch the INC switch to change the 1 to 2 When the setting has been changed to FI 1201 touch the SET switch When the SET switch is touched the entire display flashes on and off...

Страница 52: ...re additional setting If a flow rate span was specified upon ordering this will be set before shipment If this is not the case however it will be necessary for the appropriate value to be set by the user 6 2 Parameter Lists Parameter lists are comprised of the following items Item Name Data range Default value Units Position of decimal point R W Description T0601 ai Describes the parameter content...

Страница 53: ...isplay Mode only A60 SELF CHECK R Good Error Read Section 6 5 Alarm Functions 2 Item B Menu B Easy Setup items Those parameters with a high frequency of use have been grouped together in Menu B All basic functions can be controlled using only the parameters from this block Item Name R W Data range Units Position of decimal point Default value Indicated item Description Display unit BRAIN Display u...

Страница 54: ...Pulse s Selects the flow rate unit per one pulse as used for pulse output Linked with E10 B33 Pulse Scale PULSE SCALE W 0 to 32000 B32 E10 0 to 4 0 Sets the flow rate per one pulse as used for pulse output Linked with E11 B40 Display Select1 DISP SELECT1 W Flow Rate Flow Rate Flow Rate mA Forward Total Reverse Total Dif Total Flow Rate Selects content of the first line for Display Mode Linked with...

Страница 55: ...High MF IEM HIGH MF IEM W 0 0100 to 3 0000 4 1 0000 Sets high frequency meter factor Excitation current Middle C24 Low MF IEH LOW MF IEH W 0 0100 to 3 0000 4 1 0000 Sets low frequency meter factor Excitation current High C25 High MF IEH HIGH MF IEH W 0 0100 to 3 0000 4 1 0000 Sets high frequency meter factor Excitation current High C30 Nominal Size Unit SIZE UNIT W mm inch mm inch Selects the nomi...

Страница 56: ...velocity m s C45 Density Unit DENSITY UNIT W kg m3 lb gal lb cf kg m3 Sets units for density when mass flow rate is selected C46 Mass Flow Density MASS DENSITY W 0 to 32000 C45 0 to 4 0 Sets density when mass flow rate is selected with units from C45 C50 User Span Select USER SPN SEL W No Yes No Selects whether or not special units are used for flow rate units C51 Flow User Unit FL USER UNIT W 8 a...

Страница 57: ...halted D14 Total Rate Check TL RATE CHK R 0 to 999999 Pulse s 0 to 5 0 0 Displays the totalization rate in Pulse s D20 Total Execution TOTAL EXEC W Start Stop Preset Total Preset Rev Total Start Executes Start or Stop of the totalization function or executes Preset Total or Preset Rev Total D21 Ttl Set Val Lower TL SET VAL L W 0 to 999999 0 0 Sets the totalization preset value in the lower 6 digit...

Страница 58: ...low rate unit per one pulse as used for pulse output Linked with B32 E11 Pulse Scale PULSE SCALE W 0 to 32000 E10 B32 0 to 4 0 Sets the flow rate per one pulse as used for pulse output Linked with B33 E12 Pulse Width PULSE WIDTH W 50 Duty 0 05 ms 0 1 ms 0 5 ms 1 ms 20 ms 33 ms 50 ms 100 ms 200 ms 330 ms 500 ms 1000 ms 2000 ms 50 Duty Selects the pulse width for pulse output E13 Pulse Low Cut PULSE...

Страница 59: ...Rngs Pulse Output Selects function for the DO terminal F11 DO Active Mode DO ACT MODE W Closed On Act Open Off Act Closed On Act Selects whether DO terminal will be set to On Active or Off Active F20 Forward Span2 FWD SPAN2 W 0 00001 to 32000 C40 C41 0 to 4 1 m s Sets flow rate span for forward No 2 range F21 Reverse Span REV SPAN W 0 00001 to 32000 C40 C41 0 to 4 1 m s Sets flow rate span for rev...

Страница 60: ...larm is to be specified as an alarm G27 Alm Emp Pipe ALM EMP PIPE W No Yes No Selects whether an empty pipe alarm is to be specified as an alarm G28 Alm H L ALM H L W No Yes No Selects whether a flow rate high or low alarm is to be specified as an alarm G29 Alm Adhesion ALM ADHESION W No Yes No Selects whether an electrode adhesion alarm is to be specified as an alarm G30 4 20 Setting Alm 4 20 SET...

Страница 61: ...E 2 R 0D 00 00 to 9999D 23 59 Displays the operation time at occurrence of the second most recent alarm G45 Alm Record3 ALM RECORD3 R Same as G41 Alm Record 1 Displays the content of the third most recent alarm G46 Alm Record Time3 ALM TIME 3 R 0D 00 00 to 9999D 23 59 Displays the operation time at the occurrence of the third most recent alarm G47 Alm Record4 ALM RECORD4 R Same as G41 Alm Record 1...

Страница 62: ...Total Adhesion Check Communication 1 Tag No Long Tag No Hi 2 Long Tag No Lo 2 Off Selects content of the second line for Display Mode Linked with B41 1 Displays communication type according to Output Signal and Communication code D BRAIN E HART5 J HART5 or HART7 2 Long tag No Hi and Long Tag No Lo are only for HART 7 H12 Display Select3 DISP SELECT3 W Same as H11 Display Select2 Off Selects conten...

Страница 63: ...ets the dead time to reduce output fluctuation When 0 is set rate limit function is not available J23 Pulsing Flow PULSING FLOW W No Yes No Selects whether pulsing flow is to be supported J25 T P Damp Select T P DAMP SEL W Damping No Damping Damping Selects whether the flow rate value obtained through damping calculation for total pulse or the instantaneous flow rate value no damping for total pul...

Страница 64: ... the electorode K14 Adhesion Level2 ADH LEVEL2 W 0 00 to 100 00 M ohm 2 0 40 Sets the resistance value for adhesion Level 2 to the electorode K15 Adhesion Level3 ADH LEVEL3 W 0 00 to 100 00 M ohm 2 0 45 Sets the resistance value for adhesion Level 3 to the electorode K16 Adhesion Level4 ADH LEVEL4 W 0 00 to 100 00 M ohm 2 0 60 Sets the resistance value for adhesion Level 4 to the electorode K17 Ad...

Страница 65: ...M21 Adjustment 20mA ADJUST 20mA W 10 00 to 10 00 2 0 00 Sets adjustment for 20mA output M60 SELF CHECK R Good Error Read Section 6 5 Alarm Functions 12 Item N Menu N Loop Test Setting items Menu N contains items that are relevant to the execution of loop testing Item Name R W Data range Units Position of decimal point Default value Indicated item Description Display unit BRAIN Display unit BRAIN N...

Страница 66: ...to 9999 0 Parameter of the display restriction P20 Write Protect W PROTECT R No Yes No Displays whether or not overwriting of parameter data is prohibited P21 Enable Wrt Passwd ENABLE WRITE W ASCII 8 characters Sets the correct password so that write protection function will be released P22 New Password NEW PASSWORD W ASCII 8 characters Sets the password for write protection funcion P23 Software S...

Страница 67: ...mping time constant should be modified to suppress an output fluctuation or to change the response time This time constant has an effect on analog output and on the flow rate display i e actual instantaneous flow rate current value and in addition it also affects pulse output and totalization However when No Damping has been set for J25 T P Damp Select there will be no effect on pulse output or to...

Страница 68: ...milarly if 3 is set for this highest order digit it will not be possible to set a number of 2 or greater for the next digit to the right regardless of the position of the decimal point Example A value of 333 33 is represented by the character string 33333 and since this exceeds 32000 it cannot be set In such a case the value 333 3 should be set instead B24 Flow Decimal Pnt Setting of the decimal p...

Страница 69: ...erse flow rate and for the differential flow rate is carried out only when Fwd Rev Ranges is selected for F10 DO Function The totalized units are indicated on the display unit when B31 D11 is 0 00001 0 0001 0 001 0 01 0 1 1 10 100 1000 or 10000 In the case of other setting values the totalized units are not indicated Example 1 To count in 1 Ml mega liter steps with flow rate span 1000 m3 h Since 1...

Страница 70: ...ng of the first line for display unit This setting is linked with that of parameter H10 This parameter selects the display content of the first line for display unit The size of the characters which are displayed will depend on the selections made for B41 H11 Display Select2 and B42 H12 Display Select3 as described below For more details read Chapter 5 CAUTION It is not possible to set Display Sel...

Страница 71: ...ameter sets the low frequency meter factor for excitation current Low C21 High MF IEL Setting of the high frequency meter factor Excitation current Low This parameter sets the high frequency meter factor for excitation current Low C22 Low MF IEM Setting of the low frequency meter factor Excitation current Middle This parameter sets the low frequency meter factor as required for excitation current ...

Страница 72: ... density is about 1000kg m3 set the parameter below kg m3 is set for C45 Density Unit 1000 is set for C46 Mass Flow Density Set the suitable value under the actual use because the density changes by temperature C50 User Span Select Selection of the use of special flow rate units This parameter selects whether or not special units are used for instantaneous flow rate Actual setting of these units i...

Страница 73: ...may occur at the flow rate of zero and the totalization may be carried out Use the instrument with the default setting 3 If the span is small the damping time is short or the fluid is low conductivity the totalization may be carried out easily at the flow rate of zero In this case set the span to be large set the damping time to be long or set the low cut to be large D14 Total Rate Check Display o...

Страница 74: ...or not special units are used for totalization unit Actual setting of these units is carried out using D31 Ttl User Unit D31 Ttl User Unit Setting of special totalization units Units of up to maximum 8 characters in length can be specified using this parameter The units set with this parameter are displayed whenever totalization i e FTL RTL DTL is selected in the Display Mode and they are displaye...

Страница 75: ...an Flow rate span 1 m s Input value or 3 cm s whichever is bigger Flow rate span 1 m s Input value To confirm the flow rate span velocity in m s unit read C44 Velocity Check If the multiple ranges or forward reverse ranges is used low cut is carried out at the setting value for the smallest span However the low cut function will be terminated if this parameter is set to 0 NOTE When the low cut is ...

Страница 76: ...hing Example 2 When the Alarm Output function is selected for the DO terminal the following signals are output from the terminal F11 setting Function DO status output Closed On Active Alarm Alarm status Closed Good Normal Open Open Off Active Alarm Alarm status Open Good Normal Closed Example 3 When the Total Switch function is selected for the DO terminal the following signals are output from the...

Страница 77: ...mode has been set to Open Off Act using F11 DO Active Mode Table 6 4 1 Status Output for Automatic Multiple Ranges Switching F10 setting Function DO status output No Function Forward single range Fwd Rev Rngs Auto forward reverse range Forward Reverse Open Closed Auto 2 Rngs Auto forward 2 ranges Forward 1 range Forward 2 range Open Closed No Function is the default value Only DO is used for singl...

Страница 78: ...ng items Menu G principally contains setting items relevant to alarms Read Section 6 5 G10 Low Alarm Low alarm setting This parameter sets the low limit L alarm value and this is done using a value of the maximum span A setting value of 105 indicates that the alarm is disabled G11 High Alarm High alarm setting This parameter sets the high limit H alarm value and this is done using a value of the m...

Страница 79: ...lue using a value of the maximum span Output Example The hysteresis width is set to 5 Settings are G10 Low Alarm 30 G11 High Alarm 80 G12 H L Alarm Hys 5 0 Time t 35 Instantaneous flow rate 30 50 80 100 Select H L Alarm O for F10 DO Function Select Closed On Act for F11 DO Active Mode Select Yes for G28 Alm H L High Alarm Low Alarm F0607 ai 75 DO Open Closed Open Open Closed G20 4 20mA System Alar...

Страница 80: ... alarms will be recognized as an alarm Setting Function No Not recognized as an alarm Yes Recognized as an alarm G28 Alm H L Alarm recognition of H LAlarm This parameter specifies whether H L alarm in process alarms will be recognized as an alarm Setting Function No Not recognized as an alarm Yes Recognized as an alarm NOTE To set H LAlarm as an alarm it is necessary to set H LAlarm according to F...

Страница 81: ... the most recent alarm and the alarms that can be displayed are as follows Alarm Items Item Description 16 space characters i e no display NO issuing of alarms 10 uP Fault Microprocessor CPU failure 11 EEPROM Fault EEPROM failure 12 Sub uP Fault Sub Microprocessor Sub CPU failure 13 EX Pwr Fault Excitation power failure 14 A D S Fault A D converter flow velocity signal failure 15 A D I Fault A D c...

Страница 82: ...rms that can be displayed are the same as those for G41 Alm Record1 G48 Alm Record Time4 Display the operation time of alarm record4 This parameter is used to display the operation time at which the alarm indicated by G47 Alm Record4 was occurred For example 1D23 45 indicates that an alarm was occured at the operation time of 1 day 23 hours and 45 minutes 7 Menu H Display Setting items Menu H cont...

Страница 83: ...st span However the low cut function will be terminated if this parameter is set to 0 The indications of the instantaneous flow rate Actual instantaneous flow rate mA Bar graph on the display unit are the same action NOTE The default setting is 3 When the low cut is small an incorrect output may occur at the flow rate of zero Use the instrument with the default setting 3 If the span is small the d...

Страница 84: ...al Select this parameter when the current output or Simultaneous Current Pulse output is used Pulse Only Select this parameter when the pulse output as pulse special mode is used only The current output is fixed at 12 mA NOTE The pulse output function does not work unless setting the Pulse Output at F10 DO Function when the Pulse only is selected at J15 Pulse Special Mode J20 Flow Direction Settin...

Страница 85: ...determined that the signal is in excess of the rate limit value and the response becomes 1 However the actual output applies damping and therefore the output turns out to be as indicated by the solid line 2 Subsequent flow values within the dead time zone correspond to signals of post damping flow value rate limit value 1 3 Since input signals do not return to within the rate limit value during th...

Страница 86: ... function This parameter is used to execute the adhesion diagnostic function If Execution is selected this function will be started Now Adhesion Check Executing is displayed while the adhesion diagnostic function is being carried out The result of adhesion diagnosis can be confirmed by using K12 Read Chapter 11 Setting Function No Execution Adhesion diagnosis is not executed Execution Adhesion dia...

Страница 87: ...The process alarm as 33 Adhesion Alm is displayed if Yes is selected at G29 Alm Adhesion and the value is beyond the judgment at Level 4 Alarm output will be performed if Alarm Output has been selected for F10 DO Function and Yes for G29 Alm Adhesion The warning as 80 Adhesion Wng is displayed if No is selected at G29 Alm Adhesion and the value is beyond the judgment at Level 4 K17 Adhesion Check ...

Страница 88: ...r Low accordingly K20 Empty Status Display of empty pipe status This parameter specifies the status of empty pipe inside the flowtube Setting Status Normal Filled situation Empty Unfilled situation K21 DC Voltage A Display of the voltage level at electrode A This parameter is used to display the DC voltage level at electrode A The possibility of adhesion at the electrode A is higher when this valu...

Страница 89: ...ce 11 Menu N Loop Test Setting items Menu N contains items that are relevant to loop testing N10 Test Mode Setting for loop test execution Setting Function Normal No execution of loop testing Test Loop testing is started IMPORTANT 1 Test output has priority over flow rate measurement signals When carrying out flow rate measurements be sure to always return to Normal 2 Upon entry to the Test Mode c...

Страница 90: ...ator N40 Average Execution Selection of execution for measurement of averaged flowrate This parameter is used to select whether the execution for measurement of averaged flowrate is occurrence in a constant time Setting Function Stop Stopping the execution of measurement for averaged flowrate Start Starting the execution of measurement for averaged flowrate The totalization is started in a time wh...

Страница 91: ...he release of write protection When set it will be possible to make write protect settings on the software side P22 New Password F0618 ai Default setting The default setting for this parameter is a string of 8 spaces i e Enable and thus the password field will be empty When the cursor is flashing the password should be input Press the SET key twice to confirm the password The display will go back ...

Страница 92: ...ng a description appears in the 3rd line only when a warning is occurred Alarm name Description Countermeasure message Description of warning F0620 ai Process Alarm 30 Sig Overflow Check signal cable and grounding 6 5 2 Alarm Selection The display and output differs depending on the alarm levels Certain types of alarm may or may not be recognized as alarms according to the settings of certain para...

Страница 93: ...Mode is shown in above table The output value is performed in accordance with the setting of the burnout switch For information about this switch read Subsection 11 3 1 2 Display and output condition for process alarms Alarm description Selection parameter number Alarm output 4 20 mA output Totalization Pulse output Displayunit Alarm record 30 Sig Overflow Input signal error YES G26 Open Off Fixed...

Страница 94: ...age No Pulse rate is 10000 pps or more with 0 05 ms selection 61 PLS 5000p s Pulse rate is 5000 pps or more with 0 1 ms selection 62 PLS 1000p s Pulse rate is 1000 pps or more with 0 5 ms selection 63 PLS 500p s Pulse rate is 500 pps or more with 1 ms selection 64 PLS 25p s Pulse rate is 25 pps or more with 20 ms selection 65 PLS 15p s Pulse rate is 15 pps or more with 33 ms selection 66 PLS 10p s...

Страница 95: ...rcuit failure 20 Pulse Error F Discrepancy of pulse count 21 EEPROM Dflt F EEPROM default values Process Alarms Device is normal but process related errors make correct measurement impossible Display unit BRAIN 60 content Alarm countermeasure message on display unit NE 107 status Alarm description Countermeasure 30 Sig Overflow Check signal cableand grounding S Input signal error Carry out an inve...

Страница 96: ... E10 E11 and E12 S Pulse rate is 11000 pps or more with 50 duty selection Pulse rate is 10000 pps or more with 0 05 ms selection Check whether parameters E10 E11 and E12 are correct 61 PLS 5000p s Check parameter E10 E11 and E12 S Pulse rate is 5000 pps or more with 0 1 ms selection 62 PLS 1000p s Check parameter E10 E11 and E12 S Pulse rate is 1000 pps or more with 0 5 ms selection 63 PLS 500p s ...

Страница 97: ... during instantaneous flow rate display Check whether parameter C43 is correct 90 Disp SW Wng only for display unit Display unit switches are not operating Replace the display unit 91 Disp Cur Wng F Excessive current is used on the display unit Replace the display unit 93 Dev Sim Wng C In HART simulation Check whether the device is in HART Simulation 6 5 4 NE 107 status When G35 Alarm Display is s...

Страница 98: ...NU A DISPLAY B EASY SETUP C BASIC SETUP D TOTAL SET E PULSE SET F STATUS FUNC BATTERY HOME SET ADJ ESC Function commands Parameter Screen DATA DIAG PRNT ESC Parameters up to three are displayed Function commands If BATTERY is displayed on the screen it indicates that the battery voltage has dropped 7 1 2 Key Descriptions 1 Alphanumeric keys and shift keys You can use the alphanumeric keys in conju...

Страница 99: ...ands Function keys F0706 ai MENU A DISPLAY B EASY SETUP C BASIC SETUP D TOTAL SET E PULSE SET F STATUS FUNC HOME SET ADJ ESC Table 7 1 Function Command List Command Function ADJ Displays the ADJ menu CAPS caps Selects uppercase or lowercase CODE Selects symbols CLR Erases input data or deletes all data DATA Updates parameter data DEL Deletes one character DIAG Calls the self check panel ESC Return...

Страница 100: ...unication signal Before online communication confirm that communication signal does not give effect on the upper system IMPORTANT Restrictions exist with regard to the distance over which communication is possible When simultaneous output of current and pulse output or pulse output are used no communication is possible depending on the wiring Read Section 4 6 and Chapter 12 in detail IMPORTANT If ...

Страница 101: ... FLOW SPAN H11 B41 DISP SELECT2 C43 B24 FLOW DECIMAL H12 B42 DISP SELECT3 7 2 3 BT200 Screens Flow Rate Data Display Use the following procedure to display flow rate data on the BT200 The display of flow rate data is updated every 5 seconds When the BT200 is turned on the message Please wait is displayed for several seconds and then the screen on the left is shown Press the key or Press the key to...

Страница 102: ...tes using a BT200 IMPORTANT If the power of flowmeter is turned off within 30 seconds after parameters have been set these settings will be canceled Accordingly please keep the power on for at least 30 seconds after setting parameters NOTE Before updating any setting remember to always check the data content you want to change as described in Chapter 6 ...

Страница 103: ...ng for units can now be confirmed Press the key to return to Menu Screen Major Item Parameter Search Mode When Menu Screen Major Item Parameter Search Mode has been entered as shown here press the key to move to B EASY SETUP When the cursor has been moved to B EASY SETUP press the key to access Parameter Screen Sub Item Parameter Search Mode Press the key twice to move the cursor to B21 FLOW UNIT ...

Страница 104: ... CLR ESC SETTING B23 FLOW SPAN 100 000l min 120 PRINTER OFF F2 PRINTER ON FEED POFF NO After moving the cursor to B23 FLOW SPAN press the key to access Setting Screen Parameter Replacement Mode When Menu Screen Major Item Parameter Search Mode has been entered as shown here press the key to move to B EASY SETUP When the cursor has been moved to B EASY SETUP Press the key to access Parameter Screen...

Страница 105: ...S CLR ESC SETTING C10 TAG NO FI 1101 FI 1201 CODE CAPS CLR ESC SETTING C10 TAG NO FI 1101 FI 1201 FEED POFF NO PARAM C10 TAG NO FI 1201 C11 FLOW DAMPING 5 0s C20 LOW MF IEL 1 0000 DATA DIAG PRNT ESC OK An underscore small cursor will start to flash on and off at the furthest left character in the tag number as displayed in the data overwrite section Press the key four times to move the flashing un...

Страница 106: ...uration tool 5 7 Protocol revision of the device 5 7 Communication OK Communication NG NOTE In this User s Manual HART protocol revision 5 and 7 are described as HART 5 and HART 7 respectively NOTE When the output signal code of the device is J HART protocol revision can be changed Read Subsection 8 8 5 about the procedure of the revision change of HART 5 and HART 7 8 2 Device Description DD on a ...

Страница 107: ...ad resistance 250 to 600 Ω Distributor Figure 8 3 Connecting the HART Communicator WARNING Be sure to set parameters as Protect on the write protect function after finish of parameter setting work Read Chapter 6 Menu P and Subsection 11 3 2 how to use the write protect function in detail IMPORTANT If the power of flowmeter is turned off within 30 seconds after parameters have been set these settin...

Страница 108: ...d yy mm month dd day yy year 8 5 Parameters Configuration The parameter structure of the HART configuration tool is hierarchical Read Section 8 9 or Section 8 10 Menu Tree Example for the corresponding parameters The menu tree shows a cross reference of the parameters for HART and BRAIN Read Chapter 6 for the functions of parameters Note that some display parameters of AXR are different from those...

Страница 109: ...vice detects any illegal parameter settings or functional faults Procedure to call up the Device Status display Device Status If no error is detected Status Normal is displayed on the configuration tool If the specific diagnostic item is known for the check you can directly call up the item by using the Diagnostic List in the Device Status display The Diagnostic List is categorized to Device Statu...

Страница 110: ...crnt The data is sent intermittently as a digital signal at 3 times a second The burst mode is set as follows 1 Setting the data to be sent Procedure to call up the display DD Device Setup Detailed setup HART output Burst option DTM Configuration HART Burst option Select the type of data to be sent from the following options Instantaneous flow rate PV Output in and current output range current Ins...

Страница 111: ...rocedure shown below IMPORTANT When changing the protocol revision confirm the items below Protocol revision supported by HART configuration tool must be the same or higher than new protocol revision of the device Confirm that the DD or DTM which is suitable to new protocol revision of the device is installed in the configuration tool Read Section 8 2 or Section 9 2 1 Call up the parameter for pro...

Страница 112: ...T protocol revision can also be confirmed on the second line and third line of the device display Procedure to call up the Display Select Second line DD Device setup Detailed setup Function Set Display Display Select2 DTM Configuration Display Set Display Select2 Third line DD Device setup Detailed setup Function Set Display Display Select3 DTM Configuration Display Set Display Select3 Protocol Re...

Страница 113: ...A20 A21 A30 A31 A32 R R R R R R B50 M10 M11 M12 M13 M14 M15 M20 M21 W R W W W W W R R W W W N10 N11 N12 N15 N20 N30 N40 N41 N42 W W W W W W W W W W R F0803 ai 1 Adh Check Execute 2 Adhesion Check 3 Adhesion Status 4 Adh Measure Value 5 Adhesion Level1 6 Adhesion Level2 7 Adhesion Level3 8 Adhesion Level4 9 Adh Check Cycle Empty Check Empty Status DC Voltage A DC Voltage B Empty Level 4 Diagnosis 3...

Страница 114: ...otal Set 1 Total Unit 2 Total Scale 3 Total Decimal Pnt 4 Total Low Cut 5 Total Rate Check 6 Total Execution 7 Ttl Set Val Lower 8 Ttl Set Val Upper 9 Ttl Switch Lower Ttl Switch Upper Ttl User Select Ttl User Unit 3 Pulse Set 1 Pulse Unit 2 Pulse Scale 3 Pulse Width 4 Pulse Low Cut 5 Pulse Rate Check 4 Function Set 1 DO Function Set 1 DO Function 2 DO Active Mode 3 Forward Span2 4 Reverse Span 5 ...

Страница 115: ...A Low Limit 3 4 20mA High Limit 4 Pls Special Mode 5 Flow Direction 6 Rate Limit 7 Dead Time 8 Pulsing Flow 9 T P Damping Select Basic Frequency Memo1 Memo2 Memo3 Software Rev No J10 J11 J12 J15 J20 J21 J22 J23 J25 J30 J35 J36 J37 J50 W W W W W W W W W W W W W R W R W W S S S S S S S S S S S S S S F0805 ai continued on next page D D P20 P23 R W W R Revision s Universal rev Fld dev rev Software rev...

Страница 116: ... 5 Review 1 Data Renewing D Periodic Data Renewing S Discretionary Data Renewing Others Method etc 2 Parameter of BRAIN protocol HART only 3 Review1 to 4 Read the table at the end of Section 8 9 1 Review1 2 Review2 3 Review3 4 Review4 F0806 ai Hot Key Configration 1 PV Span 2 Write Protect Menu 1 Write protect 2 Enable Wrt 10min 3 New Password 4 Software Seal ...

Страница 117: ... Basic Frequency Memo1 Memo2 Memo3 MS Code1 MS Code2 MS Code3 MS Code4 MS Code5 MS Code6 Software Rev No Use Lining Electrode Material Electrode Struct Grounding Ring Process Conn Lay Length Electrical Connect Sensor Serial No Adhesion Check Adhesion Status Adh Measure Value Adhesion Level1 Adhesion Level2 Adhesion Level3 Adhesion Level4 Adh Check Cycle Empty Check Empty Status DC Voltage A DC Vol...

Страница 118: ... B23 C42 B20 C11 A30 A31 A32 R R R W W R R R Read Write D D D D D D D D Data Renewing 1 Root Menu Process Variables Device Status Diag and Service Easy Setup Configuration Calibration Write Protect A B C D E F G A B PV PV rnge Totl Reverse Totl Dif Totl Device Status Process Variables Diagnostic List Device Status Hardware Failure Transducer Status Configuration Parameter of BRAIN protocol 2 ...

Страница 119: ...ecord2 Alm Record Time2 Alm Record3 Alm Record Time3 Alm Record4 Alm Record Time4 G40 G41 G42 G43 G44 G45 G46 G47 G48 R R R R R R R R R D D D D D D D D D Diagnosis Adh Check Execute Adhesion Check Adhesion Status Adh Measure Value Adhesion Level1 Adhesion Level2 Adhesion Level3 Adhesion Level4 Adh Check Cycle Empty Check Empty Status DC Voltage A DC Voltage B Empty Level K10 K11 K12 K13 K14 K15 K1...

Страница 120: ...al Rate Check Total Execution Ttl Set Val Lower Ttl Set Val Upper Ttl Switch Lower Ttl Switch Upper Ttl User Select Ttl User Unit Characterize Meter Flow Condition C20 C21 C22 C23 C24 C25 C30 C31 W W W W W W W W S S S S S S S S B20 C11 B21 C40 B22 C41 B23 C42 B24 C43 C50 C51 C52 C44 C45 C46 W W W W W W W W R W W S S S S S S S S D S S B30 D10 B31 D11 D12 D13 D14 D20 D21 D22 D23 D24 D30 D31 W W W W ...

Страница 121: ...ng Ring Process Connect Lay Length Electrical Conn Sensor Serial No Device Information Model Manufacturer Descriptor Message Date MS Code1 MS Code2 MS Code3 MS Code4 MS Code5 MS Code6 Write protect Software rev HART Tag Poll addr Dev id Universal rev Fld dev rev Next universal rev Chg universal rev Num req preams Physical signl code Burst mode Burst option B40 H10 B41 H11 B42 H12 H20 B10 H30 H40 W...

Страница 122: ... Zero Time Flow Zero IEL Flow Zero IEM Flow Zero IEH Flow Span Adjust Adjust 4mA Adjust 20mA D A trim Scaled D A trim Clear D A trim B50 M10 M11 M12 M13 M14 M15 W R W W W W W R R W W W D S S S S S S S Write protect Enable Wrt 10min New Password D P20 P21 P22 R W W 1 Data Renewing D Periodic Data Renewing S Discretionary Data Renewing Others Method etc 2 Parameter of BRAIN protocol HART only ...

Страница 123: ...o the device 2 Call up Review4 display Root Menu Review Review4 3 HART protocol revision is displayed on the Universal rev column IMPORTANT Protocol revision supported by HART configuration tool must be the same or higher than that of the device Protcol revision supported by HART configuration tool 5 7 Protocol revision of the device 5 7 Communication OK Communication NG NOTE In this User s Manual...

Страница 124: ...l with the AXR and the connections must be non polarized Figure 9 3 illustrates the wiring connections for a direct interface at the AXR site The HART Configuration Tool can be used for remote access from any terminal strip as well AXR F0903 ai USB FieldMate modem Control room Terminal board USB PC FieldMate SUPPLY DO PC FieldMate Distributor PC FieldMate 4 to 20 mA DC signal line Relaying termina...

Страница 125: ...characters or numbers 1 Long tag Up to 32 characters or numbers 2 Descriptor Up to 16 characters or numbers 1 Message Up to 32 characters or numbers 1 Date mm dd yyyy DD yyyy mm dd DTM mm month 2 digits dd days 2 digits yyyy years 4 digits 9 5 Parameters Configuration The parameter structure of the HART configuration tool is hierarchical Read Section 9 9 Menu Tree Example for the corresponding par...

Страница 126: ...ssary Example of display Span 10 m s On Span 0 3 m s Off TTL 10000 p s Off TTL 0 0001 p s Off 4 20 Lmt Err Off 9 8 HART Specific Functions 9 8 1 Test Output Simulation and Squawk NOTE Fixed current output Flow Simulation Mode and Device Variable Simulation Function continue for a given holding time then is released automatically Even if the HART configuration tool power supply is turned off or the...

Страница 127: ...ly the loop current LCD display and communication output are directly corresponded to the simulate value The alarm output is also available according to the simulate value 3 Squawk This feature can be used to identify the communicating device by remotely causing LCD to display the particular pattern as shown in the Figure SQUAWK continues for approximately 60 seconds then is released automatically...

Страница 128: ... Mode Table 9 8 Burst parameters Command parameter Burst Command Burst Msg Trigger Mode Burst Trigger Source Burst Trigger Units PV Instantanous flow rate Cmd1 PV Continuous Window PV L min Cum h m s spcl 2 Rising Falling On change range current Output in and current output Cmd2 range current Continuous Window range Rising Falling On change Process vars current Loop current PV SV TV QV Cmd3 Dyn va...

Страница 129: ...igger Mode Update Period Max Update Period Burst Command Burst mode Burst Msg Trigger Mode Continuous Window Rising Falling On change Send to the device Send to the device Send to the device Send to the device Send to the device Cmd9 a Burst Command b Burst Variable Code c Update period and Max Update Period by Set Burst Period d Burst Msg Trigger Mode by Set Burst Trigger F0904 ai e Burst Mode Cm...

Страница 130: ...was set it is set automatically to become bigger than an operation period of the device For Update Period set the value that is smaller than Max Update Period Procedure to call up the display DD DTM Root Menu Detailed setup HART output Burst condition Burst Message 1 2 or 3 Set Burst Period Update Period Max Update Period 0 5 s 1 s 2 s 4 s 8 s 16 s 32 s 1 min 5 min 10 min 15 min 30 min 45 min 60 m...

Страница 131: ...Control Stop the event monitor Off Shift to the monitor state Enable event notification on token passing data link layer a Event Mask Set the status to detect in the Event Mask parameter Status group 1 Mask to 7 Mask Device Status Mask Ext dev status Mask Device Diagnostic Status 0 Mask b Event Notification Retry Time Max Update Time Event Debounce Interval Set to Event Notification Retry Time Max...

Страница 132: ...ing transmitters refer to the connection of several transmitters to a single communication transmission line Up to 63 transmitters can be connected when set in the multidrop mode To activate multidrop communication the transmitter address must be changed to a number from 1 to 63 This change deactivates the 4 to 20 mA analog output sending it to 4 mA The alarm current is also disabled Setting of Mu...

Страница 133: ...ut the new HART protocol revision number of 5 for HART 5 or 7 for HART 7 4 Applying the new protocol revision a Close the configuration tool After completion of Chg universal rev method close the HART configuration tool NOTE When using a FieldMate close the main display of FieldMate b Restart the device Turn off the power to the device and turn it on IMPORTANT New protocol revision is applied only...

Страница 134: ...c Device Diagnostics Process Variable C D E B A Process Variables Flow Rate Flow Rate Flow Rate mA Fwd Total Rev Total Dif Total Process Vars Status PV PV Data quality PV Limit status SV SV Data quality SV Limit status TV TV Data quality TV Limit status QV QV Data quality QV Limit status Percent Range PR Data quality PR Limit status Loop Current LC Data quality LC Limit status R R R R R R R R R R ...

Страница 135: ...15 M20 M21 W R W W W W W R R W W N10 N11 N12 N15 N20 N30 N40 N41 N42 W W W W W W W W W W W W R F0907 ai Adh Check Execute Adhesion Check Adhesion Status Adh Measure Value Adhesion Level1 Adhesion Level2 Adhesion Level3 Adhesion Level4 Adh Check Cycle Empty Check Empty Status DC Voltage A DC Voltage B Empty Level Diagnosis Easy Setup Language Flow Damping Base Flow Unit Base Time Unit Flow Span Flo...

Страница 136: ... B30 D10 B31 D11 D12 D13 D14 D20 D21 D22 D23 D24 D30 D31 W W W W R W W W W W W W F0908 ai Pulse Unit Pulse Scale Pulse Width Pulse Low Cut Pulse Rate Check Pulse Set Read Write S S S S S S S S S S S S S S S D S S S S S S S S S D S S S S S S S continued on next page Data Renewing 1 Tag Long tag Flow Damping Low MF IEL High MF IEL Low MF IEM High MF IEM Low MF IEH High MF IEH Nominal Size Unit Nomin...

Страница 137: ...splay Select2 Display Select3 Display Cycle Language LCD Contrast Aux 4 20mA Low Cut 4 20mA Low Limit 4 20mA High Limit Pls Special Mode Flow Direction Rate Limit Dead Time Pulsing Flow T P Damping Select Basic Frequency Memo1 Memo2 Memo3 Software Rev No F10 F11 F20 F21 F30 F31 W W W W W W F0909 ai Read Write S S S S S S G10 G11 G12 G20 G25 G26 G27 G28 G29 G30 G31 G35 W W W R W W W W W W W W S S S...

Страница 138: ...val Burst Variables Set Burst Trigger Set Burst Period Burst Msg Trigger Mode Burst Trigger Units Burst Trigger Level Update Period Max Update Period Burst Variable Code Burst Variable Code Burst Variable Code Burst Variable Code Burst Variable Code Burst Variable Code Burst Variable Code Burst Variable Code Status group 1 Mask Status group 2 Mask Status group 3 Mask Status group 4 Mask Status gro...

Страница 139: ... R R W R W W W W W W F0911 ai Read Write S S S S S S S S S S S S S S S S S S P20 P23 R W W R D D R R R R W S S S S Data Renewing 1 W W W W W W W W W S S S S S S S S S TAB 3 TAB 3 TAB 3 Parameter of BRAIN protocol 2 Parameter of BRAIN protocol 2 Read Write Data Renewing 1 P20 P21 P22 P23 R W W R B23 C42 W W D D S 1 Data Renewing D Periodic Data Renewing S Discretionary Data Renewing Others Method e...

Страница 140: ...de1 MS Code2 MS Code3 MS Code4 MS Code5 MS Code6 Software Rev No Use Lining Electrode Material Electrode Struct Grounding Ring Process Connect Lay Length Electrical Conn Sensor Serial No Adhesion Check Adhesion Status Adh Measure Value Adhesion Level1 Adhesion Level2 Adhesion Level3 Adhesion Level4 Adh Check Cycle Empty Check Empty Status DC Voltage A DC Voltage B Empty Level Review4 Poll addr Loo...

Страница 141: ...its operating conditions This section describes the zero adjustment procedure using display unit switches from the converter and using the external status input accordingly one of these methods should be selected and implemented 10 ACTUAL OPERATION IMPORTANT Zero adjustment should be carried out before actual operation Note that parameter settings and update functions cannot be carried out during ...

Страница 142: ...ter Replacement execute Mode Start Major Item Parameter Search Mode M Adjustment 21 Adjustment 20mA 10 Auto Zero Exe 11 Autozero Time SET SET INC SET SET Once in Setting Mode use the INC switch to move the cursor to M Adjustment Touch the SET switch to access Sub item Parameter Search Mode Upon selection of M Adjustment the cursor will be positioned at M10 Auto Zero Exe Sub item selection D Touch ...

Страница 143: ...ting 0 100 Auto zero adjustment function is being executed about 450 seconds When zero adjustment function has been completed the system automatically returns to the sub item selection screen D NOTE The results of M10 Auto Zero Exe can be displayed using M12 M13 and M14 Alternatively if the results of the automatic zero adjustment exceed the rated value the warning 82 Auto Zero Wng will be display...

Страница 144: ... and be disassembled and reassembled to the original state For details INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT at the end of this manual The cover is locked by the special screw In case of opening the cover use the hexagonal wrench nominal size 3 Be sure to lock the cover by the special screw using this hexagonal wrench after installing the cover 11 1 Changing Directio...

Страница 145: ...board for example by preventing static electrification by using grounded wrist straps when handing the assembly Also take precautions such as placing a removed amplifier assembly into a bag with an antistatic coating 11 2 1 Display Unit Replacement CAUTION When using this instrument for a long time in conditions of high temperature and humidity the visibility of the display unit may deteriorate In...

Страница 146: ...isplay unit 90 degrees clockwise and confirm the assembling position 4 Align the display unit in a straight with its connector located its backside facing the connector of amplifier assembly and then make the required connection 5 Secure the display unit using its four mounting screws F1105 ai Turn the display unit 90 degrees clockwise Figure 11 2 3 Assembling the Display Unit NOTE Secure to displ...

Страница 147: ...ly connect the cable 1 to the connector 4 making sure that the connectors direction are correct 3 Replace the amplifier assembly by pushing it in the converter with folding back the cable 1 and 2 taking care not to entangle these tow cables during installing the hexagonal screws 4 Align the display unit in a straight with the connector 2 facing the connector of amplifier assembly and then make the...

Страница 148: ...board the burnout setting switch Switch 2 and the write protect switch Switch 1 are located adjacent to each other Accordingly special care should be taken when making switch settings Switch 2 Switch 1 Enable Protect L H 1 2 ON F1108 ai BO Burnout setting switch WR Write protect setting switch Figure 11 3 Switch Configuration 11 3 2 Setting of Write Protect Switch By setting the write protect func...

Страница 149: ... on the display unit using four different levels If the judgment value for Level 3 is exceeded a warning is displayed and if the value for Level 4 is exceeded an alarm or warning is displayed depending on the setting condition at G29 Available conductivity for this function is limited to 10 µS cm Make sure to use the adhesion diagnostic function with the greater conductivity than the above mention...

Страница 150: ... used in the following description Setting Mode Major item parameter Setting mode J Aux K Diagnosis M Adjustment K10 Adhesion Check No Execution No Execution Execution K10 Adhesion Check No Execution Execution No Execution Major item Sub item selection D K10 Adhesion Check Execution Sub item Parameter Search Mode Parameter Replacement execute Mode Start Major Item Parameter Search Mode K Diagnosis...

Страница 151: ...as been completed the system automatically returns to the sub item selection screen D IMPORTANT In the event of a warning or alarm when executing the adhesion diagnostic function take one of the following actions Clean the electrodes and then execute the adhesion diagnostic function Set the values of adhesion diagnostic level3 K15 Adhesion Level3 and level4 K16 Adhesion Level4 bigger than the resu...

Страница 152: ...nds during discharge Furthermore never short discharge without inserting a resister Table 11 6 1 Test terminal for insulation resistance test Inspection location Terminal Test voltage Standard Power Supply Digital Output Functional Grounding SUPPLY DO 500 V DC 100 MΩ or more When the optional code A is selected with the lightning protector values are as follows Power Supply Digital Output Function...

Страница 153: ...Check whether the flowtube is filled with fluid Is the flowtube full of fluid Remove the tube and inspect the inside of the pipe Is foreign matter adhering to the walls Does the arrow on the tube match the flow direction Perform either of the following a Reinstall the flowtube in order to make the arrow and flow direction match b Reverse the setting for the flow direction Change the piping or the ...

Страница 154: ...he flow velocity to being in the vicinity of the lower conductivity limit Remove dirt and scale of and near electrodes Use a soft brush or cloth to perform scale removal and make sure that the lining is not damaged Provide the meter with sufficient shielding or move it away from the electrical equipment NO NO NO NO NO NO NO YES YES YES YES YES YES YES Are there bubbles in the fluid Are valves leak...

Страница 155: ...ity Use a soft brush or cloth to perform scale removal and make sure that the lining is not damaged YES If any valve located immediately upstream of the flowtube is used in a half open condition the indication may be affected by turbulence in the flow Relocate the valve to the downstream side If the valve must be located on the upstream side ensure that the minimum distance to the flowmeter is 10 ...

Страница 156: ...can be connected with almost all distributors signal conditioner cards and I O modules except certain devices Read the following table for Yokogawa s devices choose an appropriate connecting device and the corresponding length of cable For devices other than those in the table decide on the connection by reading the supply voltage specifi cations and the description in Section 4 6 Connecting devic...

Страница 157: ...power supply and digital output terminals Protection General purpose Use TIIS Flameproof type IP66 IP67 Type 4X Explosion proof type except for TIIS In the case of explosion proof type except TIIS read description of Enclosure in HAZARDOUS AREA CLASSIFICATION Converter Coating Case and Cover Corrosion resistant coating Coating Color Mint green paint Munsell 5 6 BG 3 3 2 9 or its equivalent Convert...

Страница 158: ...rms can be activated or deactivated for each item The current output for an alarm can be selected from the follow ing settings If any System Alarm occurs turn the power off and back on again to return to the normal condition System Alarm 21 6 mA or more 3 2 mA or less Process Alarm Setting Alarm 21 6 mA or more 20 5 mA HOLD fixed to the current value before the alarm 4 mA 3 8 mA 3 2 mA or less The...

Страница 159: ...lange type Housing Flange Flange type only Corrosion resistant coating Coating color Mint green Munsell 5 6 BG 3 3 2 9 or its equivalent Flowtube Material Size 25 to 100 mm 1 to 4 in Part Name Material Housing Stainless steel JIS SUS304 AISI 304 SS EN 1 4301 equivalent Flange Stainless steel JIS SUS304 or SUSF304 AISI 304 SS EN 1 4301 equivalent Mini Flange Wafer type Size 25 mm 1 0 in Stainless s...

Страница 160: ...pes Viton GC Acid resistant fluororubber for PVC pipes Viton GD Alkali resistant fluororubber for PVC pipes Viton Use General purpose Use Explosion Proof Type Optional code BSF or BSC Grounding ring Flange of user s pipe Gasket for user s flange Gasket Material for user s flange BSF PTFE sheathed non asbestos BSC Chloroprene rubber Recommended Gaskets Between Flowtubes And User s Flanges Gaskets T...

Страница 161: ... 1 1 Vs 3 3 0 30 cm s at indications less than 50 of span 0 3 0 2 Vs of rate at indications 50 or more of span 1 Vs 2 3 3 Vs 6 7 0 3 of span at indications less than 35 of span 0 5 of rate at indications 35 or more of span 2 Vs 10 6 7 Vs 33 0 16 of span at indications less than 30 of span 0 5 of rate at indications 30 or more of span 150 to 200 6 to 8 0 3 Vs 1 1 Vs 3 3 0 50 cm s at indications les...

Страница 162: ... following specifications Optional Code FF1 CF1 SF2 JF3 Safety Requirement Standards CAN CSA C22 2 No 61010 1 04 Altitude of installation site Max 2000 m above sea level Installation category I Overvoltage category Installation category describes a number which defines a transient overvoltage condition It implies the regulation for impulse withstand voltage I applies to electrical equipment which ...

Страница 163: ...1 0 or less 1 0 or less 500 0 6 or less 1 0 or less Measurable Flow Rate Range SI Units Size mm Flow rate m3 h Size mm 0 to Min Span Flow Rate 0 3 m s 0 to Max Span Flow Rate 10 m s 25 0 to 0 5302 m3 h 0 to 17 671 m3 h 40 0 to 1 3572 0 to 45 23 50 0 to 2 1206 0 to 70 68 65 0 to 3 584 0 to 119 45 80 0 to 5 429 0 to 180 95 100 0 to 8 483 0 to 282 74 150 0 to 19 090 0 to 636 1 200 0 to 33 930 0 to 1 ...

Страница 164: ... Wafer JIS 20K Wafer JIS F12 JIS75M Wafer Size 200 mm 8 0 in Size 65 mm 2 5 in to 200 mm 8 0 in Size 25 mm 1 0 in to 50 mm 2 0 in Size 80 mm 3 0 in to 200 mm 8 0 in Lay Length 1 2 Lay length code 1 7 Lay length code 2 8 Size 80 mm 3 0 in to 200 mm 8 0 in Electrical Connection 9 0 2 4 JIS G1 2 female ANSI 1 2 NPT female ISO M20 1 5 female Indicator 10 11 1 2 N Integral Flowmeter with indicator Hori...

Страница 165: ... lay length code 1 in the AXF series For details read EXTERNAL DIMENSIONS 8 Excluding the size of 65 mm dimensions of lay length code 2 are the same as those of PFA lining replacement models lay length code 2 in AXF series Lay lengths for special gaskets optional codes GA GC GD are different For details read EXTERNAL DIMEN SIONS 9 For an explosion proof type except for TIIS select ANSI 1 2 NPT fem...

Страница 166: ...alent Platinum iridium HASTELLOY C 276 Equivalent Tantalum Process Connection 4 5 BA1 BA2 BD1 BD2 BD4 BJ1 BJ2 BG1 CA1 CA2 CD1 CD2 CJ1 CJ2 CG1 ANSI Class 150 Flange JIS SUS304 or SUSF304 ANSI Class 300 Flange JIS SUS304 or SUSF304 DIN PN 10 Flange JIS SUS304 or SUSF304 6 DIN PN 16 Flange JIS SUS304 or SUSF304 6 DIN PN 40 Flange JIS SUS304 or SUSF304 6 JIS 10K Flange JIS SUS304 or SUSF304 JIS 20K Fl...

Страница 167: ...act Yokogawa for detailed information of the wetted parts material 3 Available only for metal piping 4 Mating dimensions are based on standards as follow ANSI ASME B 16 5 DIN DIN 2501 JIS JIS B 2220 and JIS G 3443 2 5 Allowable fluid pressure should also be limited according to fluid temperature and pressure 6 Even when DIN PN10 16 or 40 is required for a model of size 25 to 50 mm 1 0 to 2 0 in se...

Страница 168: ...umeric within the value of 0 0001 to 32000 And it can be up to five digits to a maximum of 32000 ignoring the decimal point A fraction is limited to the fourth decimal place b Mass Units Available mass units t kg g klb lb Available time units d h min s Note1 In the case of specifying the mass flow span calculate the volumetric flow span by the setting density and specify the available value in the...

Страница 169: ...rings are assembled and packed with polyethyl ene including desiccants after being cleaned with water and acetone and dried with air The label OIL WATER FREE is affixed K5 Epoxy Resin Coating Epoxy resin coating which has alkali resistance instead of standard polyurethane resin coating The color is same as standard type X1 High Anti corro sion Coating Three layer coating polyurethane coating on tw...

Страница 170: ...OUS AREA CLASSIFICATION Need to select optional code G11 JF3 Flameproof packing adapter for TIIS Flame proof Type 7 One flameproof packing adapter and one blind plug G11 One flameproof packing adapter addition G32 1 Standard 90 degree rotation 180 degree rotation 90 degree rotation Optional Code RA Optional Code RB Optional Code RC Electrical Connection Indicator Electrical Connection Indicator 2 ...

Страница 171: ... ø d 1 33 1 30 1 Grounding Ring Code S L H P T N None 0 26 1 02 2 0 08 GA GC GD Special Gaskets 8 0 31 30 1 18 Optional Code Lay Length Code 1 AXR150 AXR200 Wafer Type F1213 ai 1 When indicator code N is selected subtract 5 mm 0 2 inch from the value in the figure 2 Depending on the selection of grounding ring code and optional code add the following value to L face to face length Hi Max Height We...

Страница 172: ...2 Optional Code 18 5 0 73 90 3 54 Lay Length Code 2 AXR040 AXR065 Wafer Type Unit mm approx inch F1215 ai 1 When indicator code N is selected subtract 5 mm 0 2 inch from the value in the figure 2 Depending on the selection of grounding ring code and optional code add the following value to L face to face length AXR040 AXR050 AXR065 G C 1 A 1 A 2 Hi Max Height Weight kg lb Height H1 Size code Size ...

Страница 173: ...5 04 Grounding Ring Code S L H P T N None 0 22 0 87 2 0 08 GA GC GD Special Gaskets 8 0 31 26 1 02 Optional Code Lay Length Code 2 AXR150 AXR200 Wafer Type Unit mm approx inch F1217 ai 1 When indicator code N is selected subtract 5 mm 0 2 inch from the value in the figure 2 Depending on the selection of grounding ring code and optional code add the following value to L face to face length AXR150 G...

Страница 174: ... 87 108 0 4 25 18 2 0 72 28 1 10 79 2 3 12 45 15 7 0 62 4 112 4 40 58 2 28 273 10 76 5 6 12 3 025 25 1 A 200 7 87 124 0 4 88 21 5 0 85 28 1 10 88 9 3 50 45 19 1 0 75 4 120 4 74 58 2 28 281 11 07 6 7 14 7 BD4 DIN PN40 025 25 1 A 200 7 87 115 4 53 22 0 87 28 1 10 85 3 35 45 14 0 55 4 115 4 54 58 2 28 277 10 90 6 4 14 1 164 6 46 1 33 1 1 30 28 1 10 33 1 30 70 2 76 Hi H1 H2 73 2 87 49 1 93 154 6 06 t ...

Страница 175: ... 127 0 5 00 21 5 0 85 41 1 61 98 6 3 88 45 15 7 0 62 4 131 5 17 68 2 67 293 11 53 7 2 15 8 200 7 87 152 4 6 00 23 1 0 91 53 2 09 120 7 4 75 45 19 1 0 75 4 155 6 11 79 3 11 317 12 47 9 3 20 5 200 7 87 177 8 7 00 26 4 1 04 66 2 60 139 7 5 50 45 19 1 0 75 4 177 6 97 89 3 50 339 13 35 12 8 28 2 200 7 87 155 4 6 12 24 6 0 97 41 1 61 114 3 4 50 45 22 4 0 88 4 146 5 73 68 2 67 307 12 09 9 6 21 1 200 7 87...

Страница 176: ...68 45 19 0 75 4 225 8 85 106 4 16 386 15 21 18 3 40 3 200 7 87 190 5 7 50 27 9 1 10 77 3 03 152 4 6 00 45 19 1 0 75 4 190 7 48 95 3 74 352 13 86 14 6 32 2 250 9 84 228 6 9 00 27 9 1 10 102 4 02 190 5 7 50 22 5 19 1 0 75 8 220 8 66 106 4 16 382 15 02 20 5 45 2 200 7 87 209 6 8 25 32 4 1 28 77 3 03 168 1 6 62 22 5 22 4 0 88 8 200 7 87 95 3 74 362 14 25 18 3 40 3 250 9 84 254 0 10 00 35 8 1 41 102 4 ...

Страница 177: ...62 298 5 11 75 22 5 22 4 0 88 8 337 13 29 166 6 54 499 19 66 50 6 71 2 300 11 81 317 5 12 50 41 5 1 63 146 1 5 75 269 7 10 62 15 22 4 0 88 12 300 11 80 141 5 55 462 18 18 53 9 118 8 350 13 78 381 0 15 00 46 1 1 81 193 6 7 62 330 2 13 00 15 25 4 1 00 12 357 14 04 166 6 54 519 20 41 80 2 176 8 350 13 78 340 13 39 29 1 14 193 6 7 62 295 11 61 15 22 0 87 12 336 13 23 166 6 54 498 19 61 43 3 95 5 150 1...

Страница 178: ...lerance Category of basic dimension Tolerance Above Equal or below Above Equal or below 3 0 12 0 7 0 03 500 19 69 630 24 80 5 5 0 22 3 0 12 6 0 24 0 9 0 04 630 24 80 800 31 50 6 25 0 25 6 0 24 10 0 39 1 1 0 04 800 31 50 1000 39 37 7 0 0 28 10 0 39 18 0 71 1 35 0 05 1000 39 37 1250 49 21 8 25 0 32 18 0 71 30 1 18 1 65 0 06 1250 49 21 1600 62 99 9 75 0 38 30 1 18 50 1 97 1 95 0 08 1600 62 99 2000 78...

Страница 179: ...3 EC until July 18th 2016 Article 4 paragraph 3 of Directive 2014 68 EU from July 19th 2016 4 Models classified in CATEGORY II shall not be used for unstable gases of Group 1 2 Installation WARNING Tighten the bolts of the piping joints according to the prescribed torque values Take measures to protect the flowmeters from forces caused by vibration channeled through the piping 3 Operation WARNING ...

Страница 180: ...e products are locked Use this hexagonal wrench to open and close the cover Before opening the cover be sure to check that the power of flowmeter has been turned off Once the cover is closed be sure to re lock the product Be sure to lock the cover with the special screw using the hexagonal wrench after tightening the cover 14 1 ATEX WARNING Only trained persons use this instrument in industrial lo...

Страница 181: ...try devices shall be of a certified ATEX flameproof type suitable for the conditions of use and correctly installed Unused apertures shall be closed with suitable flameproof certified blanking elements The plug attached is flameproof certified In order to prevent the grounding ring conductor from loosening the conductor must be secured to the terminal tightening the screw with appropriate torque C...

Страница 182: ...ows is year 2008 No S5EA05158 845 7 Produced in 2008 2 180 8750 is a zip code which represents the following address 2 9 32 Nakacho Musashino shi Tokyo Japan 3 The identification number of the notified body 0344 DEKRA Netherland 4 The product producing country 14 2 FM 1 Technical Data Applicable Standard FM3600 FM3610 FM3615 FM3810 ANSI NEMA 250 Type of Protection Explosionproof for Class I Divisi...

Страница 183: ...icable Standard CAN CSA C22 2 No 0 M91 CAN CSA C22 2 No 0 4 04 C22 2 No 0 5 1982 C22 2 No 25 1966 C22 2 No 30 M1986 CAN CSA C22 2 No 94 M91 CAN CSA C22 2 No 157 92 CAN CSA C22 2 No 61010 1 04 Type of Protection Class I Groups A B C and D Class II Groups E F and G Class III With Intrinsically Safe Electrodes for Class I Groups A B C and D Specification of Protection Electrode Circuit Um 250 V Power...

Страница 184: ...131 F Process Sealing Certification Dual Seal certified by CSA to the requirements of ANSI ISA 12 27 01 2003 No additional sealing required Primary seal failure annunciation Deterioration of the flowrate output at nonzero flow point Unstable flowrate output at zero flow point 2 Installation For Division WARNING All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Codes...

Страница 185: ... IEC 60079 1 2014 IEC 60079 7 2006 IEC 60079 11 2011 IEC 60079 31 2013 Certificate IECEx DEK 11 0053 Type of Gas Atmosphere Protection Type of Protection Ex db e ia IIC T6 T4 Gb Specification of Protection Electrode Circuit Um 250V Power Supply Current Output 42Vdc max 4 to 20mA Um 250V Digital Output ON 2Vdc 120mA max OFF 30Vdc max 4mA Um 250V Excitation Circuit 29 V max Enclosure IP66 IP67 Proce...

Страница 186: ...ts The plug attached is certified as the flameproof and IP66 or IP67 as a part of this apparatus In case of ANSI 1 2 NPT plug ANSI hexagonal wrench should be applied to screw in In order to prevent the grounding ring conductor from loosening the conductor must be secured to the terminal tightening the screw with appropriate torque Care must be taken not to twist the conductor The grounding termina...

Страница 187: ...iteria for explosion proof construction of electric machinery and equipment Standards Notification No 556 from the Japanese Ministry of Labor conforming to IEC standards is designed for hazardous areas where inflammable gases or vapors may be present This allows installation in Zone 1 and 2 areas To preserve the safety of flameproof equipment requires great care during mounting wiring and piping S...

Страница 188: ...of type with wiring using a flameproof packing adapter wire cables through the packing adapters approved by Yokogawa optional code G11 G32 T1 T2 L 18 0 71 G F D C 16 5 0 65 Packing Choose from the table below depend on cable outside diameter Unit mm Approx inch Adapter body M Screw Packing case Hexagon socket set screw O Ring Packing O Ring O Ring Washer Union nut Packing gland Clamp ring Clamp nu...

Страница 189: ...s will be compromised h Fasten the cable by tightening the clamp nut i Tighten the lock nut on the union cover j Connect the cable wires to each terminal F1408 ai Adapter body Rubber packing Washer Packing box Gland Clamp ring Clamp nut Union coupling Union cover Wrench O ring Lock nut Wrench Lock nut Cable Apply a non hardnening sealant to the threads for waterproofing Figure 14 5 3 Installing Fl...

Страница 190: ...n be verified by reading these parameters from the optional local display or by checking actual calibration of the flowmeter The calibration of the flowmeter must be performed after parameters are set A1 2 4 Required Parameter Settings The following parameters need to be set in order to maintain the designed safety integrity Table A1 2 1 Required Parameter Settings Item Description Burnout directi...

Страница 191: ...e bypass and otherwise restore normal operation For details refer to the FMEDA No YOK 10 06 091 R001 V2R3 The manuals can be downloaded from the website of Yokogawa or purchased from the Yokogawa representatives Website address http www yokogawa com fld A1 2 6 Repair and Replacement If repair is to be performed with the process online the AXR will need to be bypassed during the repair The user sho...

Страница 192: ...2R3 A1 2 11 Environmental Limits The environmental limits of the AXR are specified in this manual A1 2 12 Application Limits The application limits of the AXR are specified in this manual If the flowmeter is used outside of the application limits the reliability data listed in Subsection A1 2 9 becomes invalid A1 3 Definitions and Abbreviations A1 3 1 Definitions Safety Freedom from unacceptable r...

Страница 193: ...ed Systems Installation A1 4 IM 01E30D01 01EN A1 3 2 Abbreviations FMEDA Failure Mode Effects and Diagnostic Analysis SIF Safety Instrumented Function SIL Safety Integrity Level SIS Safety Instrumented System SLC Safety Lifecycle ...

Страница 194: ...n by flameproof enclosures d Flameproof enclosure d has an enclosure s in which the parts which can ignite an explosive gas atmosphere are placed and which can withstand the pressure developed during an internal explosion of an explosive mixture and which prevents the transmission of the explosion to the explosive gas atmosphere surrounding the enclosure In this manual the word ʻ flameproof enclos...

Страница 195: ... External Wiring for Flameproof Equipment Flameproof equipment requires cable wiring for their electrical connections For cable wiring cable glands cable entry devices for flameproof type to wiring connections shall be attached All non live metal parts such as the enclosure shall be securely grounded For details read USER S GUIDELINES for Installations for Explosive Atmospheres in General Industry...

Страница 196: ... to a safety non hazardous location Observe the following points before attempting to repair the equipment a Make only such electrical and mechanical repairs as will restore the equipment to its original condition For the flameproof equipment the gaps and path lengths of joints and mating surfaces and mechanical strength of enclosures are critical factors in explosion protection Exercise great car...

Страница 197: ...d with a product Please keep the Identification Tag with this document Identification Tag Sample RoHS 2011 65 EU Directive For conformity with the RoHS Directive read GS 01E20S00 01EN ADMAG Series Magnetic Flowmeter List of RoHS 2011 65 EU Directive Compliant Products Some parts of this product include the restricted substances of RoHS Directive but their applications are under the exemption of th...

Страница 198: ... Technical Data 3rd Aug 2012 1 1 1 Changed the style Changed the Note 4 1 to 4 15 4 Changed the Terminal Configuration Added the Terminal Configuration 4 6 to 4 7 4 6 1 Changed the Supply Voltage Added the Connection Device JUXTA VJA7 6 3 6 11 6 3 2 8 Added Long Tag No Hi and Long Tag No Lo to Data range for B41 and H11 6 6 6 22 6 3 4 6 4 3 Changed the default value and the setting value for D13 6...

Страница 199: ... 7 3 7 2 1 Added the load resistance in Figure 7 2 Added the IMPORTANT for communication 8 1 8 1 Changed the name plate 8 2 8 3 Added the load resistance in Figure 8 3 9 1 9 1 Changed the name plate 9 2 9 3 Added the load resistance in Figure 9 3 9 9 9 8 3 2 Added the IMPORTANT for HART7 Burst communication 11 2 11 2 Added the IMPORTANT for component replacement 12 5 12 1 Changed the sentence for ...

Страница 200: ... 14 1 6 Corrected the figure for name plate 14 4 to 14 6 14 3 Added the sentence for CSA certification 14 8 14 4 6 Corrected the figure for name plate Appendix Added EU DECLARATION OF CONFORMITY 6th Mar 2017 1 1 Added a description at Regarding This User s Manual 3 6 Deleted the optional codes BCF and BCC 3 7 Deleted the optional code BCF 3 8 Deleted the optional code BCF 3 9 Deleted the optional ...

Отзывы: