<4. WIRING>
4-8
IM 01E30D01-01EN
Table 4.6.1 Connecting device and Applicable
maximum cable length (guideline)
Connecting device
Maximum length of cable
(rough guideline)
Name
Model
Cable
with cross
section of
2 mm
2
Cable
with cross
section of
1.25 mm
2
Signal
Conditioner
Card
EA1
EA2
2 km
2 km
I/O Module
AAM11
AAM11B
2 km
2 km
Analog I/O
Module
(for FIO)
AAI143
2 km
2 km
AAI141
AAI841
AAI135
AAI835
Not applicable
Not applicable
Analog I/O
Module (for
Prosafe-RS)
SAI143
1.4 km
0.8 km
Distributor
SDBT
SDBS
2 km
2 km
JUXTA
VJA1
2 km
2 km
VJA4
VJA7
Communication Requirement:
BRAIN
Communication signal:
BRAIN communication signal
(superimposed on 4 to 20 mA DC signals)
Conditions of Communication Line:
Supply Voltage: 20.6 to 42 V DC
Load Resistance: 250 to 600 Ω
(including cable resistance)
Read Figure 4.6.3.
Communication Distance:
Up to a distance of 2km when a CEV cable is
used (Read Table 4.6.2 to Table 4.6.7)
Load Capacitance: 0.22 μF or less
Load Inductance: 3.3 mH or less
Distance from other Power line:
15 cm (6 in.) or more (Avoid parallel wiring)
Input Impedance of Communicating Device:
10 kΩ or more at 2.4 kHz
600
250
14.7
20.6
28.9
42
Power supply voltage E (V DC)
R= 0.0236
E−14.7
F0416.ai
Digital
Communication
Range
(BRAIN or HART)
External
Load
Resistance
R (Ω)
Figure 4.6.3 Relationship between Power supply
voltage and external load resistance
HART
Communication signal:
HART communication signal (superimposed
on 4 to 20 mA DC signals)
Note: HART is a registered trademark of the FieldComm
Group. Use the setting tool that has the same
protocol revision as AXR. It is not possible to
communicate with HART7 AXR in using HART 5 or
HART 6 setting tool.
Conditions of Communication Line:
Supply Voltage: 20.6 to 42 V DC
Load Resistance: 250 to 600 Ω
(including cable resistance)
Read Figure 4.6.3.
HART Protocol Revision
HART protocol revision can be selected from 5 or
7 when ordering. (“-J” only)
The protocol revision can be changed by user
configuration.
The HART protocol revision at the time of
shipment is shown by the last number at the
serial number column of the name plate.
Note: Protocol revision supported by HART configura
-
tion tool must be the same or higher than that of
AXR.