<6. PARAMETER DESCRIPTION>
6-2
IM 01E30D01-01EN
6.3 Parameter List Overview
(1) Item A (Menu A): Display items
Menu A contains the instantaneous flow rate, totalization values, and other items relevant to display.
Item
Name
R/W
Data range
Units
Position
of decimal
point
Default value
(*): Indicated item
Description
Display unit
(BRAIN)
Display unit
/BRAIN
A00 Display
(DISPLAY)
A10 FR
(FLOW RATE (%))
R
-103.1 to 103.1
%
1
For Display Mode only
A20 FR
(FLOW RATE)
R
-999999 to 999999 B21/B22
(C40/C41)
0 to 3
For Display Mode only
A21 FR
(FLW RATE (mA))
R
3.800 to 20.500
mA
3
For Display Mode only
A30 FTL
(TOTAL)
R
0 to 99999999
B30
(D10)
0 to 7
For Display Mode only
A31 RTL
(REV TOTAL)
R
0 to 99999999
B30
(D10)
0 to 7
For Display Mode only
A32 DTL
(DIF TOTAL)
R
-99999999
to 99999999
B30
(D10)
0 to 7
For Display Mode only
A60 —
(SELF CHECK)
R
Good
Error
Read Section 6.5 “Alarm
Functions”.
(2) Item B (Menu B): Easy Setup items
Those parameters with a high frequency of use have been grouped together in Menu B. All basic functions can
be controlled using only the parameters from this block.
Item
Name
R/W
Data range
Units
Position
of decimal
point
Default value
(*): Indicated item
Description
Display unit
(BRAIN)
Display unit
/BRAIN
B00 Easy Setup
(EASY SETUP)
B10 Language
(LANGUAGE)
W
English
Japanese
French
German
Italian
Spanish
English
Selects the language used for
the display unit. Linked with
H30.
B20 Flow Damping
(FLOW DAMPING)
W
1.0 to 200.0
s
1
5.0 s
Sets damping time. Linked with
C11.
B21 Base Flow Unit
(FLOW UNIT)
W
Ml(Megaliter)
m
3
kl (Kiloliter)
l (Liter)
cm
3
m
t
kg
g
kcf
cf
mcf
Mgal (US)
kgal (US)
gal (US)
mgal (US)
kbbl (US Oil)
bbl (US Oil)
mbbl (US Oil)
ubbl (US Oil)
kbbl (US Beer)
bbl (US Beer)
mbbl (US Beer)
ubbl (US Beer)
ft
klb (US)
lb (US)
m (*)
Selects flow units for the flow
rate span. Linked with C40.