<6. PARAMETER DESCRIPTION>
6-9
IM 01E30D01-01EN
(7) Item G (Menu G): Alarm Setting items
Menu G contains setting items relevant to alarm output, burnout, alarm record, etc.
Item
Name
R/W
Data range
Units
Position
of decimal
point
Default value
(*): Indicated item
Description
Display unit
(BRAIN)
Display unit
/BRAIN
G00 Alarm
(ALARM)
G10 Low Alarm
(LOW ALARM)
W
-105 to 105
%
0
-105%
Sets level setting value for low
flow rate limit (L)
G11 High Alarm
(HIGH ALARM)
W
-105 to 105
%
0
105%
Sets level setting value for high
flow rate limit (H)
G12 H/L Alarm Hys
(H/L ALM HYS)
W
0 to 10
%
0
5 %
Sets hysteresis width for high-
low flow rate limit alarm
G20 4-20 System Alm
(4-20 SYS ALM)
R
21.6mA (Read IM)
3.2mA (Read IM)
21.6mA (Read IM)
(*)
Displays the current output
during a system alarm
occurrence
G25 4-20 Process Alm
(4-20 PRO ALM)
W
21.6mA or More
20.5mA
Hold
4.0mA
3.8mA
3.2mA or Less
21.6mA or More (*) Selects the current output
during a process alarm
occurrence
G26 Alm-Sig Over
(ALM-SIG OVER)
W
No
Yes
Yes
Selects whether a signal
overflow alarm is to be
specified as an alarm.
G27 Alm-Emp Pipe
(ALM-EMP PIPE)
W
No
Yes
No
Selects whether an empty pipe
alarm is to be specified as an
alarm.
G28 Alm-H/L
(ALM-H/L)
W
No
Yes
No
Selects whether a flow rate
high or low alarm is to be
specified as an alarm.
G29 Alm-Adhesion
(ALM-ADHESION)
W
No
Yes
No
Selects whether an electrode
adhesion alarm is to be
specified as an alarm.
G30 4-20 Setting Alm
(4-20 SET ALM)
W
21.6mA or More
20.5mA
Hold
4.0mA
3.8mA
3.2mA or Less
21.6mA or More (*) Selects the current output
during a setting alarm
occurrence
G31 Alm-Setting
(ALM-SETTING)
W
No
Yes
Yes
Selects whether a setting alarm
is to be specified as an alarm.
G35 Alarm Display
(ALM DISPLAY)
W
Normal
NE107
Normal
Selects alarm display form
on the display unit and
configuration tools.
G40 Operation Time
(OPERATE TIME)
R
0D 00:00 to
9999D 23:59
Operation time
G41 Alm Record1
(ALM RECORD1)
R
10:uP Fault
11:EEPROM Fault
12:Sub uP Fault
13:EX Pwr Fault
14:A/D(S) Fault
15:A/D(I) Fault
16:Analog Fault
17:Coil Open
18:Coil Short
19:Excite Error
20:Pulse Error
21:EEPROM Dflt
22:Power Off
23:Inst Pwr Fail
28:WDT
30:Sig Overflow
31:Empty Pipe
33:Adhesion Alm
91:Disp Cur Wng
Displays the content of the
most recent alarm.