<6. PARAMETER DESCRIPTION>
6-3
IM 01E30D01-01EN
Item
Name
R/W
Data range
Units
Position
of decimal
point
Default value
(*): Indicated item
Description
Display unit
(BRAIN)
Display unit
/BRAIN
B22 Base Time Unit
(TIME UNIT)
W
/s
/min
/h
/d
/s (*)
Selects time units for the flow
rate span. Linked with C41.
B23 Flow Span
(FLOW SPAN)
W
0.00001 to 32000
B21/B22
(C40/C41)
0 to 4
1 m/s (*)
Sets flow rate span (with units
from B21 and B22). Linked with
C42.
B24 Flow Decimal Pnt
(FLOW DECIMAL)
W
Auto
0
1
2
3
Auto (*)
Selects decimal point
position for the display unit’s
instantaneous flow rate. Linked
with C43.
B30 Total Unit
(TOTAL UNIT)
W
n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s
Pulse/s (*)
Selects the flow rate unit
per one pulse as used for
totalization display. Linked with
D10.
B31 Total Scale
(TOTAL SCALE)
W
0 to 32000
B30
(D10)
0 to 4
0 (*)
Sets the flow rate per one pulse
as used for the totalization
display. Linked with D11.
B32 Pulse Unit
(PULSE UNIT)
W
n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/
Pulse/s
Pulse/s (*)
Selects the flow rate unit per
one pulse as used for pulse
output. Linked with E10.
B33 Pulse Scale
(PULSE SCALE)
W
0 to 32000
B32
(E10)
0 to 4
0 (*)
Sets the flow rate per one
pulse as used for pulse output.
Linked with E11.
B40 Display Select1
(DISP SELECT1)
W
Flow Rate(%)
Flow Rate
Flow Rate(mA)
Forward Total
Reverse Total
Dif Total
Flow Rate
Selects content of the first line
for Display Mode. Linked with
H10.
B41 Display Select2
(DISP SELECT2)
W
Off
Flow Rate(%)
Flow Rate
Flow Rate(mA)
Flow Rate(Bar)
Forward Total
Reverse Total
Dif Total
Adhesion Check
Communication (*1)
Tag No
Long Tag No(Hi) (*2)
Long Tag No(Lo) (*2)
Off
Selects content of the second
line for Display Mode. Linked
with H11.
(*1) Displays communication
type according to Output Signal
and Communication code:
●-D: BRAIN
●-E: HART5
●-J: HART5 or HART7
(*2) Long tag No(Hi) and Long
Tag No (Lo) are only for HART
7.
B42 Display Select3
(DISP SELECT3)
W
Same as B41
(Display Select2)
Off
Selects content of the third line
for Display Mode. Linked with
H12.
B50 Auto Zero Exe
(AUTOZERO EXE)
W
No Execution
Execution
No Execution
Selects whether or not
automatic zero adjustment is
carried out. Linked with M10.
B60 —
(SELF CHECK)
R
Good
Error
Read Section 6.5 “Alarm
Functions”.