58
Press
Menu
Press Digit
Select Key
Press Value Select
Key
ALS 34
Alarm Setup
for relays 3 & 4
if detected.
0
0000
Relay alarm state when
alarm is active.
0
Relay 3 active on
Relay 4 active on
1
Relay 3 active off
Relay 4 active on
2
Relay 3 active on
Relay 4 active off
3
Relay 3 active off
Relay 4 active off
0
0
000
Alarm latching or non-
latching (auto reset).
(see Glossary)
0
AL3 non-latching
AL4 non-latching
1
AL3 latching
AL4 non-latching
2
AL3 non-latching
AL4 latching
3
AL3 latching
AL4 latching
00
0
00
Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).
(see Glossary)
0
AL3 active high
AL4 active high
1
AL3 active low
AL4 active high
2
AL3 disabled
AL4 active high
3
AL3 active high
AL4 active low
4
AL3 active low
AL4 active low
5
AL3 disabled
AL4 active low
6
AL3 active high
AL4 disabled
7
AL3 active low
AL4 disabled
8
AL3 disabled
AL4 disabled
000
0
0
Hysteresis mode or band
deviation mode
(see Glossary)
0
AL3 band deviation AL4 band deviation
1
AL3 hysteresis
AL4 band deviation
2
AL3 band deviation AL4 split hysteresis
3
AL3 hysteresis
AL4 hysteresis
0000
0
Number of consecutive
readings in alarm zone to
cause an alarm.
0
After 1 reading
4
After 16 readings
1
After 2 readings
5
After 32 readings
2
After 4 readings
6
After 64 readings
3
After 8 readings
7
After 128 readings
Press
Menu
Press Digit
Select Key
Press Value Select
Key
dEUn1H
Alarm 1 hysteresis
0
.00000 0.
0
0000 0.0
0
000
0.00
0
00 0.000
0
0
0.0000
0
Select digit to flash
Select
-9
thru
9
for flashing
first digit,
0
thru
9
for other
flashing digits. Alarms will
activate above the setpoint
by the value entered and
deactivate below the setpoint
by the value entered. For
span hysteresis, the alarms
will activate (deactivate) at
the setpoint and deactivate
(activate). See Glossary.
DEUn2H
Alarm 2 hysteresis
DEUn1b
Alarm 1 band deviation
DEUn2b
Alarm 2 band deviation
dEUn1h
Alarm 1 span hysteresis
DEUn2h
Alarm 2 span hysteresis
dEUn3H
Alarm 3 hysteresis
DEUn4H
Alarm 4 hysteresis
DEUn3b
Alarm 3 band deviation
DEUn4b
Alarm 4 band deviation
Содержание 800 plus
Страница 63: ...63 SERIAL CONNECTION EXAMPLES ...