55
Additional programmable features
of the serial input meter are detailed in the “Command
Mode for Remote Display Operation of Counter / Timer” and “Data Formats” sections of the
Custom ASCII Protocol Serial Communications Manual
. In particular, Mode 12 (hex C), which
is invoked by setting the first digit under
ConFIG
to
C
, allows extraction of data from an ASCII
string that contains multiple data values or non-numeric characters. This mode can accom-
modate selected Start and Stop characters. Any number of characters between the Start
character and the data can be masked OFF. Up to 8 display characters (including sign and
decimal point) can be masked ON. Any number of characters between the last displayed
character and the Stop character can be masked OFF.
Instrument Setup
software is required to set up parameters for the Remote Display in Mode 12
(hex C). This software is downloadable from our website.
SELECTED FRONT PANEL SETUP ITEMS FOR SERIAL INPUT METER
(not consecutive)
If the
MENU
key does not work, see Section 9 “Enabling & Locking Out Menu Items.”
Press
Menu
Press Digit
Select Key
Press Value Select
Key
SEtuP
Setup
_000_
0
Control inputs 1 and 2
F
1 = Tare enable, 2 = Tare
Control input 1 must be at 0V or grounded for
Tare to operate.
ConFiG
Configu-
ration
__
0
000
Display mode
6
Remote display (H, K, L commands)
7
Single-value remote display
8
Show 1
st
string value, slaved to another meter
9
Show 2
nd
string value, slaved to another meter
A
Show 3
rd
string value, slaved to another meter
B
Show 4
th
string value, slaved to another meter
C
Custom Start, Stop, Skip, Show characters
.
ti_Out
.
Time-out
_
0
00.00 _0
0
0.00 _00
0
.00
_000.
0
0 _000.0
0
Select digit to flash.
Select
0
thru
9
for flashing digit to set time-out in
seconds. Decimal point location is fixed for 10 ms
resolution.
.
SEr 1
.
__0
0
0
U
Baud rate
Fixed parameters:
No parity, 8 data bits,
1 stop bit
0
300 baud
1
600 baud
2
1200 baud
3
2400 baud
4
4800 baud
5
9600 baud
6
19200 baud
.
SEr 2
.
__000
0U
Meter address
Select
0
thru
F
for addresses 1 thru 15. Select
0.
thru
F.
(with decimal point) for addresses 16 thru 31.
.
SEr 3
.
_
0
0000
U
RS485
0
Full duplex
1
Half duplex
SEr 4
.
___0
0
0
U
Serial protocol
0
Custom ASCII
1
Modbus RTU
2
Modbus ASCII
___00
0U
Parity
0
None
1
Odd
2
Even
_
Addr
___
0
00 __0
0
0 ___00
0
Modbus address
__
158
Select
0
through
9
for flashing digit. Address
range is 1 to 247.