12
9. ENABLING & LOCKING OUT MENU ITEMS
For security reasons and ease of operation, any and all menu items
may be disabled or "locked out" so that they are no longer directly
accessible from the front panel. Each function to be enabled is set
to "0" and each function to be disabled is set to "1" in menu items
Loc 1
-
4
. These menu items can in turn be locked out by installing an
internal hardware jumper. With the jumper installed, the operator
only has access to enabled menu items. With the jumper removed,
the operator also has access to the
Loc 1-4
menu items
.
SETTING HARDWARE LOCKOUT JUMPER
To access the lockout jumper, remove the rear panel per Section 9
and locate jumper “
a”
in the lower portion of the power supply board
next to the input connectors (see figure at right).
SETTING SOFTWARE LOCKOUTS
When setting up the meter, it may be neces-
sary to enable specific menu items by setting
the corresponding lockout digit to 0. Be sure
to reset the lockout digit to "1" if you do not
want the menu item to be changed by an
operator.
_
Loc 1
_
Loc 2
_
Loc 3
_
Loc 4
Press the
MENU key until
Loc 1, Loc 2,
Loc 3
or
Loc 4
is displayed, as desired.
Note:
the lockout jumper must be removed (see
above).
111111
Press
to display the lockout status, con-
sisting of 0’s and 1’s. The left digit will flash.
Press again to step to the next digit, which
will flash.
000000
123456
Press
to set the flashing digit to "0" to
enable the menu item or to "1" to disable.
Press
MENU
to enter. See the table to the
right for list of menu items that can be
enabled or disabled.
Enabled / Disabled Menu Items
_
Loc 1
3
- Input type selection
4
- Setup, Config, Dspyno
5
- Gate time, timeout, batch setup
6
- Filter setup
_
Loc 2
3
- Slope, decimal points
4
- Scale, offset, resolution, 2-coord.
5
- Alarm config, DevHy
6
- Alarm setpoint programming
_
Loc 3
3
- Analog output setup & scaling
4
- Serial communications configuration
5
- Calibration
6
- Change displayed Item #
_
Loc 4
3
- View peak value
4
- View alarm setpoints
5
- Front panel resets (peak & latched
alarms)
6
- Front panel reset (cold reset only)
Содержание 800 plus
Страница 63: ...63 SERIAL CONNECTION EXAMPLES ...