57
KEYSTROKES FOR SETUP
If the
MENU
key does not work, see Section 9 “Enabling & Locking Out Menu Items.”
Press
Menu
Press Digit
Select Key
Press Value Select
Key
SourcE
Source to com-
pare to setpoint
0
000
Setpoint 1 compared to:
1.
Filtered item
2
Item #2
1
Item #1
3
Item #3
0
0
00
Setpoint 2 compared to:
1.
Filtered item
2
Item #2
1
Item #1
3
Item #3
00
0
0
Setpoint 3 compared to:
1.
Filtered item
2
Item #2
1
Item #1
3
Item #3
000
0
Setpoint 4 compared to:
1.
Filtered item
2
Item #2
1
Item #1
3
Item #3
AL SEt
Alarm Setup
for relays 1 & 2
if detected.
Press
until
ALSEt
is
displayed.
0
0000
Relay alarm state when
alarm is active
0
Relay 1 active on
Relay 2 active on
1
Relay 1 active off
Relay 2 active on
2
Relay 1 active on
Relay 2 active off
3
Relay 1 active off
Relay 2 active off
0
0
000
Alarm latching or non-
latching (auto reset)
(see Glossary)
0
AL1 non-latching
AL2 non-latching
1
AL1 latching
AL2 non-latching
2
AL1 non-latching
AL2 latching
3
AL1 latching
AL2 latching
00
0
00
Alarm operates at and
above setpoint (active
high) or at and below
setpoint (active low).
(see Glossary)
0
AL1 active high
AL2 active high
1
AL1 active low
AL2 active high
2
AL1 disabled
AL2 active high
3
AL1 active high
AL2 active low
4
AL1 active low
AL2 active low
5
AL1 disabled
AL2active low
6
AL1 active high
AL2 disabled
7
AL1 active low
AL2 disabled
8
AL1 disabled
AL2 disabled
000
0
0
Hysteresis mode or band
deviation mode
(see Glossary)
0
AL1 band deviation AL2 band deviation
1
AL1 hysteresis
AL2 band deviation
2
AL1 band deviation AL2 hysteresis
3
AL1 hysteresis
AL2 hysteresis
4
No deviation or hysteresis on menu
5
AL1 span hysteresis AL2 band deviation
6
AL1 span hysteresis AL2 hysteresis
7
AL1 span hysteresis AL2 span hysteresis
0000
0
Number of consecutive
readings in alarm zone to
cause an alarm
0
After 1 reading
4
After 16 readings
1
After 2 readings
5
After 32 readings
2
After 4 readings
6
After 64 readings
3
After 8 readings
7
After 128 readings
Содержание 800 plus
Страница 63: ...63 SERIAL CONNECTION EXAMPLES ...